Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131H5197 VLT HVAC Drive FC 102, a 37 kW three phase AC variable frequency drive designed for HVAC motor control, pumps, fans, ventilation and automation network applications.
£2,549.25
The Danfoss 131H5197 is a 37 kW / 50 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame B4, IP20 / chassis unit, built for mounting inside a control panel or enclosure.
This configuration has RFI class A1/B (C1), no brake chopper, a graphical LCP 102 control panel, and a DeviceNet MCA 104 fieldbus card. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 37 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 37 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP20 | |
| EMC Filter | Commercial | |
| Series | VLT® HVAC Drive FC 102 | |
| Product code | 131H5197 | |
| Product type | AC variable frequency drive | |
| Rated output power | 37 kW / 50 HP | |
| Input voltage | 380–480 V AC | |
| Input phases | 3-phase | |
| Frequency | 50 / 60 Hz | |
| Protection rating | IP20 | |
| Enclosure type | Chassis | |
| RFI filter | Class A1/B (C1) | |
| Brake chopper | No brake chopper | |
| Control panel | Graphical Local Control Panel | |
| PCB coating | Not coated | |
| Mains option | No mains option | |
| Communication option | DeviceNet MCA 104 | |
| Frame size | B4 | |
| Mounting type | Cabinet / panel mounting | |
| Gross weight | approx. 23.31 kg | |
| Net weight | approx. 22.24 kg |
This unit is fitted with a DeviceNet MCA 104 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.
Yes. IP20 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.
FC-102P37KT4E20H1XGXXXXSXXXXA4BXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 37 kW / 50 HP | P37K |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP20 / chassis | E20 |
| RFI filter Position 16–17 | RFI class A1/B (C1) | H1 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | DeviceNet MCA 104 | A4 |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |