131H3169 Danfoss VLT HVAC Drive 37 kW/50HP 380-480VAC IP20

131H3169 Danfoss VLT HVAC Drive 37 kW/50HP 380-480VAC IP20

Danfoss 131H3169 VLT HVAC Drive FC 102, a 37 kW three-phase AC variable frequency drive with 380-480 V AC input, IP20 chassis enclosure, brake chopper, Safe Stop, graphical local control panel, coated PCB and RFI Class A1/B C1 filter for HVAC motor control applications.

SKU: 131H3169Alt SKU: FC-102P37KT4E20H1UGCXXXSXXXXAXBXCXXXXDXMPN: 131H3169
Price
List Price £5,276.00 ex VAT
Your Price (ex VAT) Save 45%
£2,901.80 45% OFF
You save £2,374.20 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,901.80
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,901.80

Danfoss 131H3169 at a glance

The Danfoss 131H3169 is a 37 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame B4, IP20 / chassis unit, built for mounting inside a control panel or enclosure.

This configuration has RFI class A1/B (C1), brake chopper + Safe Stop, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP20 / chassis — built for mounting inside a control panel or enclosure.
  • EMC: RFI class A1/B (C1). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Smaller7.5 kWDanfoss 131F3239IP20 / chassis · frame A3View drive →
This drive37 kWDanfoss 131H3169IP20 / chassis · frame B4

Same 37 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 37 kW
Voltage 480 V
Phase Three Phase
IP Rating IP20
EMC Filter Commercial
Series VLT® HVAC Drive FC 102
Part Number 131H3169
Model Code FC-102P37KT4E20H1UGCXXXSXXXXAXBXCXXXXDX
Product type AC variable frequency drive
Rated output power 37 kW
Horsepower rating 50 HP
Input voltage 380-480 V AC
Input phases Three-phase
Protection rating IP20 / Chassis
RFI filter Class A1/B (C1)
Brake / safety function Brake chopper + Safe Stop
Control panel Graphical Local Control Panel
PCB coating Coated PCB
Mains option No mains option
Frame size B4

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

Does this drive need to go in an enclosure?

Yes. IP20 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.

Type code decoded

FC-102P37KT4E20H1UGCXXXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
37 kWP37K
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP20 / chassisE20
RFI filter
Position 16–17
RFI class A1/B (C1)H1
Brake / Safe Stop
Position 18
Brake chopper + Safe StopU
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Conformal-coated PCBsC
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX