131G8247 Danfoss VLT HVAC Drive 45 kW/60HP 380-480VAC IP20

131G8247 Danfoss VLT HVAC Drive 45 kW/60HP 380-480VAC IP20

Danfoss 131G8247 VLT HVAC Drive FC 102 variable speed drive, 45 kW / 60 HP, three-phase 380-480 V AC, IP20 chassis enclosure, with BACnet MCA 109 option for HVAC motor control applications.

SKU: 131G8247Alt SKU: FC-102P45KT4E20H3XGXXXXSXXXXAJBXCXXXXDXMPN: 131G8247
Price
List Price £5,561.00 ex VAT
Your Price (ex VAT) Save 45%
£3,058.55 45% OFF
You save £2,502.45 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £3,058.55
Trade pricing is personalised to your account

Manufacturer Lead Time

£3,058.55

Danfoss 131G8247 at a glance

The Danfoss 131G8247 is a 45 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame C3, IP20 / chassis unit, built for mounting inside a control panel or enclosure.

This configuration has RFI class A1/B (C1) with reduced motor cable length, no brake chopper, a graphical LCP 102 control panel, and a BACnet MCA 109 fieldbus card. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP20 / chassis — built for mounting inside a control panel or enclosure.
  • EMC: RFI class A1/B (C1) is met only with a reduced screened motor cable length. Check the maximum length for this frame in the Danfoss FC 102 Design Guide (Technical Documents tab); for longer runs, ask us about an H2 (A2/C3) variant.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Smaller22 kWDanfoss 131G8245IP20 / chassis · frame B4View drive →
This drive45 kWDanfoss 131G8247IP20 / chassis · frame C3

Same 45 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 45 kW
Current 80 A
Voltage 480 V
Phase Three Phase
IP Rating IP20
EMC Filter Commercial
Series VLT® HVAC Drive FC 102
Part Number 131G8247
Model Code FC-102P45KT4E20H3XGXXXXSXXXXAJBXCXXXXDX
Product type Variable speed drive / frequency converter
Rated output power 45 kW
Horsepower rating 60 HP
Current rating 80 A
Input voltage 380–480 V AC
Input phases Three-phase
Frequency 50 / 60 Hz
Protection rating IP20 / chassis
RFI filter Class A1/B (C1)
Brake chopper No brake chopper
Control panel Graphical Local Control Panel
PCB type Not coated PCB
Mains option No mains option
Communication option BACnet MCA 109
Frame size C3
Mounting type Panel / cabinet installation
Dimensions (H × W × D) approx. 550 × 308 × 333 mm
Net weight approx. 35.88 kg
EAN 5710107111558

Frequently asked questions

What is the maximum motor cable length with this RFI filter?

The 131G8247 has the H3 filter: RFI class A1/B (C1) with a reduced motor cable length. The exact limit for this frame is in the Danfoss VLT HVAC Drive FC 102 Design Guide (see Technical Documents). If your screened cable run is longer, contact us and we will suggest an alternative.

Which communication protocols does it support?

This unit is fitted with a BACnet MCA 109 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.

Does this drive need to go in an enclosure?

Yes. IP20 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.

Type code decoded

FC-102P45KT4E20H3XGXXXXSXXXXAJBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
45 kWP45K
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP20 / chassisE20
RFI filter
Position 16–17
RFI class A1/B (C1) with reduced motor cable lengthH3
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
BACnet MCA 109AJ
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX