131G1399 Danfoss VLT FC-102 HVAC Drive 132 kW, 380 - 480 VAC, IP54

131G1399 Danfoss VLT FC-102 HVAC Drive 132 kW, 380 – 480 VAC, IP54

Danfoss 131G1399 VLT HVAC Drive FC 102, rated at 132 kW / 200 HP for 380-480 V AC three-phase HVAC motor control applications, supplied in an IP54 / Type 12 enclosure with Commercial C2 RFI filter, Safe Stop, coated PCB, no mains option, no A option and no B option.

SKU: 131G1399Alt SKU: FC-102P132T4E54H4TGCXXXSXXXXAXBXCXXXXDXMPN: 131G1399
This product has been discontinued A direct replacement is available below.
134F9734 Danfoss VLT HVAC Drive 132 kW/200HP 380-480VAC IP54 Replacement product Danfoss VLT HVAC Drive 132KW/200HP 380-480VAC IP54 SKU: 134F9734 £8,008.55 ex VAT View

Danfoss 131G1399 at a glance

The Danfoss 131G1399 is a 132 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is an IP54 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A1 (C2), safe Stop, no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP54 / UL Type 12 — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A1 (C2). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

This drive132 kWDanfoss 131G1399IP54 / UL Type 12
Larger160 kWDanfoss 134G9585IP54 / UL Type 12 · frame D1HView drive →

Same 132 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 132 kW
Voltage 480 V
Phase Three Phase
IP Rating IP54
EMC Filter Commercial
Model code FC-102P132T4E54H4TGCXXXSXXXXAXBXCXXXXDX
Drive series VLT HVAC Drive FC 102
Product type Variable frequency drive / HVAC inverter drive
Power rating 132 kW / 200 HP
Supply voltage 380–480 V AC
Input phase Three-phase
Enclosure rating IP54 / Type 12
RFI filter Commercial C2
Safety function Safe Stop
Brake chopper No brake chopper
Mains option No mains option
A option No A option
B option No B option
PCB coating Coated PCB

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

Can this drive be wall mounted without a panel?

Yes. The IP54 / UL Type 12 enclosure is designed for direct mounting.

Type code decoded

FC-102P132T4E54H4TGCXXXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
132 kWP132
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP54 / UL Type 12E54
RFI filter
Position 16–17
RFI class A1 (C2)H4
Brake / Safe Stop
Position 18
Safe Stop, no brake chopperT
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Conformal-coated PCBsC
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX