Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131F8478 VLT HVAC Drive FC-102, a 5.5 kW three phase variable frequency drive for HVAC fans, pumps, ventilation and refrigeration applications.
£985.05
The Danfoss 131F8478 is a 5.5 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame A5, IP55 / UL Type 12 with backplate unit, built for wall mounting in plant rooms without a separate enclosure.
This configuration has RFI class A1/B (C1), no brake chopper, a graphical LCP 102 control panel, and a BACnet MCA 109 fieldbus card. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same 5.5 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 5.5 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP55 | |
| Series | VLT® HVAC Drive FC-102 | |
| Part number | 131F8478 | |
| Product type | Variable frequency drive | |
| Rated output power | 5.5 kW | |
| Horsepower rating | 7.5 HP | |
| Input voltage | 380-480 V AC | |
| Input phases | Three phase | |
| Application type | HVAC drive | |
| Protection rating | IP55 / Type 12 | |
| Frame size | A5 | |
| RFI filter | Class A1/B | |
| Brake chopper | No | |
| Communication option | BACnet MCA 109 | |
| Control panel | Graphical local control panel | |
| PCB coating | Not coated | |
| Mains option | No mains option |
This unit is fitted with a BACnet MCA 109 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.
Yes. The IP55 / UL Type 12 with backplate enclosure is designed for direct mounting.
FC-102P5K5T4P55H1XGXXXXSXXXXAJBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 5.5 kW | P5K5 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP55 / UL Type 12 with backplate | P55 |
| RFI filter Position 16–17 | RFI class A1/B (C1) | H1 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | BACnet MCA 109 | AJ |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.