131F8303 Danfoss VLT FC-102 HVAC Drive 22 kW / 30 HP, 380 - 480 VAC, IP55

131F8303 Danfoss VLT FC-102 HVAC Drive 22 kW / 30 HP, 380 – 480 VAC, IP55

Danfoss 131F8303 VLT HVAC Drive FC 102, a 22 kW three phase AC variable frequency drive designed for HVAC fans, pumps, air handling units, ventilation systems and building automation applications.

SKU: 131F8303Alt SKU: FC-102P22KT4E55H2XGXXXXSXXXXAXB0CXXXXDXMPN: 131F8303
Price
List Price £3,436.00 ex VAT
Your Price (ex VAT) Save 45%
£1,889.80 45% OFF
You save £1,546.20 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,889.80
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,889.80

Danfoss 131F8303 at a glance

The Danfoss 131F8303 is a 22 kW / 30 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame B2, IP55 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A2 (C3), no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Continuous output current: 44 A. Size the drive on the motor nameplate current at your actual supply voltage.
  • Intermittent (overload) current: 48.4 A — the normal-overload rating that suits variable-torque fan and pump loads.
  • Enclosure: IP55 / UL Type 12 — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A2 (C3). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same 22 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 22 kW
Voltage 480 V
Phase Three Phase
IP Rating IP55
EMC Filter Industrial
Series VLT® HVAC Drive FC 102
SKU / MPN 131F8303
Product type AC variable frequency drive / frequency converter
Rated output power 22 kW / 30 HP
Continuous current 44 A
Intermittent current 48.4 A
kVA rating 30.5 kVA
Power loss 525 W
Input voltage 380–480 V AC
Input phases 3-phase
Protection rating IP55 / Type 12
RFI filter Class A2 (C3)
Communication / I/O MCB 109 analogue I/O with RTC back-up
Brake chopper No brake chopper
Control panel Graphical local control panel
PCB coating Not coated PCB
Mains option No mains option
Frame size B2
Dimensions (H × W × D) approx. 664 × 243 × 261 mm
Net weight approx. 26.97 kg

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

What output current does it deliver at 400 V and at 480 V?

Continuous output current is 44 A; intermittent current is 48.4 A. Always size on the motor nameplate current at your supply voltage.

Can this drive be wall mounted without a panel?

Yes. The IP55 / UL Type 12 enclosure is designed for direct mounting.

Type code decoded

FC-102P22KT4E55H2XGXXXXSXXXXAXB0CXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
22 kW / 30 HPP22K
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP55 / UL Type 12E55
RFI filter
Position 16–17
RFI class A2 (C3)H2
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
MCB 109 analogue I/O with real-time-clock back-upB0
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX