131F4172 Danfoss VLT FC-102 HVAC Drive 90 kW / 125 HP, 380 - 480 VAC, IP55

131F4172 Danfoss VLT FC-102 HVAC Drive 90 kW / 125 HP, 380 – 480 VAC, IP55

Danfoss 131F4172 VLT HVAC Drive FC 102, a 90 kW three-phase AC variable frequency drive with IP55 enclosure, RFI filter, graphical local control panel and BACnet MCA 109 for HVAC motor control applications.

SKU: 131F4172Alt SKU: FC-102P90KT4E55H2XGXXXXSXXXXAJBXCXXXXDXMPN: 131F4172
Price
List Price £9,374.00 ex VAT
Your Price (ex VAT) Save 45%
£5,155.70 45% OFF
You save £4,218.30 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £5,155.70
Trade pricing is personalised to your account

Manufacturer Lead Time

£5,155.70

Danfoss 131F4172 at a glance

The Danfoss 131F4172 is a 90 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame C2, IP55 / UL Type 12 unit, built for wall mounting in plant rooms without a separate enclosure.

This configuration has RFI class A2 (C3), no brake chopper, a graphical LCP 102 control panel, and a BACnet MCA 109 fieldbus card. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP55 / UL Type 12 — built for wall mounting in plant rooms without a separate enclosure.
  • EMC: RFI class A2 (C3). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Smaller1.1 kWDanfoss 131F4157IP55 / UL Type 12 · frame A5View drive →
This drive90 kWDanfoss 131F4172IP55 / UL Type 12 · frame C2

Same 90 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 90 kW
Voltage 480 V
Phase Three Phase
IP Rating IP55
Series VLT HVAC Drive FC 102
SKU / MPN 131F4172
Product type HVAC frequency converter / variable speed drive
Rated output power 90 kW
Horsepower rating 125 HP
Input voltage 380–480 V AC
Input phases 3-phase
Output phases 3-phase
Protection rating IP55 / Type 12
RFI filter RFI filter fitted
Brake chopper No brake chopper
Local control panel Graphical local control panel
Mains option No mains option
A option BACnet MCA 109
B option No B option
C1 option No C1 option
D option No D option
PCB coating Not coated PCB
Cable entries Standard cable entries
Software release Latest release standard software
Frame size C2
Net weight approx. 60.2 kg
Gross weight approx. 61.3 kg
Volume approx. 228.095 litres
EAN 5710107119448

Frequently asked questions

Which communication protocols does it support?

This unit is fitted with a BACnet MCA 109 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.

Can this drive be wall mounted without a panel?

Yes. The IP55 / UL Type 12 enclosure is designed for direct mounting.

Type code decoded

FC-102P90KT4E55H2XGXXXXSXXXXAJBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
90 kWP90K
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP55 / UL Type 12E55
RFI filter
Position 16–17
RFI class A2 (C3)H2
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
BACnet MCA 109AJ
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX