Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131F3134 VLT HVAC Drive FC 102, a 4.0 kW three-phase AC variable frequency drive with IP20 chassis enclosure, Safe Stop, graphical local control panel and RFI Class A1/B C1 filter for HVAC motor control applications.
£710.60
The Danfoss 131F3134 is a 4.0 kW VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame A2, IP20 / chassis unit, built for mounting inside a control panel or enclosure.
This configuration has RFI class A1/B (C1), safe Stop, no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 4 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 4 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP20 | |
| EMC Filter | Commercial | |
| Series | VLT® HVAC Drive FC 102 | |
| Part Number | 131F3134 | |
| Model Code | FC-102P4K0T4E20H1TGXXXXSXXXXAXBXCXXXXDX | |
| Product type | AC variable frequency drive | |
| Rated output power | 4.0 kW | |
| Horsepower rating | 5.5 HP | |
| Continuous output current | 10 A | |
| Intermittent output current | 11 A | |
| Input voltage | 380-480 V AC | |
| Input phases | Three-phase | |
| Protection rating | IP20 / Chassis | |
| RFI filter | Class A1/B (C1) | |
| Safety function | Safe Stop | |
| Control panel | Graphical Local Control Panel | |
| PCB coating | Not coated PCB | |
| Mains option | No mains option | |
| Frame size | A2 | |
| Dimensions (H × W × D) | approx. 268 × 90 × 205 mm | |
| Net weight | approx. 4.59 kg | |
| EAN | 5702427427662 |
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Yes. IP20 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.
FC-102P4K0T4E20H1TGXXXXSXXXXAXBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 4.0 kW | P4K0 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP20 / chassis | E20 |
| RFI filter Position 16–17 | RFI class A1/B (C1) | H1 |
| Brake / Safe Stop Position 18 | Safe Stop, no brake chopper | T |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.