131F1454 Danfoss VLT FC-102 HVAC Drive 45 kW / 60 HP, 380 - 480 VAC, IP21

131F1454 Danfoss VLT FC-102 HVAC Drive 45 kW / 60 HP, 380 – 480 VAC, IP21

Danfoss 131F1454 VLT HVAC Drive FC-102, a 45 kW three phase variable speed drive designed for HVAC motor control, ventilation, heating, refrigeration and building automation systems.

SKU: 131F1454Alt SKU: FC-102P45KT4E21H2XNXXXXSXXXXAXBXCXXXXDXMPN: 131F1454
Price
List Price £5,439.00 ex VAT
Your Price (ex VAT) Save 45%
£2,991.45 45% OFF
You save £2,447.55 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £2,991.45
Trade pricing is personalised to your account

Manufacturer Lead Time

£2,991.45

Danfoss 131F1454 at a glance

The Danfoss 131F1454 is a 45 kW / 60 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame C1, IP21 / UL Type 1 unit, suitable for mounting in clean, dry indoor plant rooms.

This configuration has RFI class A2 (C3), no brake chopper, and a numeric LCP 101 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP21 / UL Type 1 — suitable for mounting in clean, dry indoor plant rooms.
  • EMC: RFI class A2 (C3). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Smaller37 kWDanfoss 131F1453IP21 / UL Type 1 · frame C1View drive →
This drive45 kWDanfoss 131F1454IP21 / UL Type 1 · frame C1

Same 45 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 45 kW
Voltage 480 V
Phase Three Phase
IP Rating IP21
EMC Filter Industrial
Series VLT® HVAC Drive FC-102
Model code FC-102P45KT4E21H2XNXXXXSXXXXAXBXCXXXXDX
Product type Frequency converter / variable speed drive
Rated output power 45 kW / 60 HP
Continuous output current 90 A / 80 A depending on supply voltage
Intermittent output current 99 A / 88 A depending on supply voltage
Input voltage 380–480 V AC
Input phases 3-phase
Frequency 50 / 60 Hz
Protection rating IP21 / Type 1
RFI filter Class A2 (C3)
Brake chopper Not fitted
Local control panel Numerical local control panel
PCB coating Not coated
A option None
B option None
Mains option None
Frame size C1
Weight approx. 41.07 kg

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

Can this drive be wall mounted without a panel?

Yes. The IP21 / UL Type 1 enclosure is designed for direct mounting.

Type code decoded

FC-102P45KT4E21H2XNXXXXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
45 kW / 60 HPP45K
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP21 / UL Type 1E21
RFI filter
Position 16–17
RFI class A2 (C3)H2
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Numeric LCP 101N
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX