Danfoss 131F0030 VLT HVAC Drive FC 102: 11 kW / 15 HP, 3 × 380–480 V AC supply, IP21 / UL Type 1. Configured with RFI class A2 (C3), no brake chopper, graphical local control panel (LCP 102).
£1,162.70
The Danfoss 131F0030 is an 11 kW / 15 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is an IP21 / UL Type 1 unit, suitable for mounting in clean, dry indoor plant rooms.
This configuration has RFI class A2 (C3), no brake chopper, a graphical LCP 102 control panel, and a LonWorks MCA 108 fieldbus card. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 11 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 11 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP21 | |
| Manufacturer | Danfoss | |
| Series | VLT HVAC Drive FC 102 | |
| Type code | FC-102P11KT4E21H2XGXXXXSXXXXAGBXCXXXXDX | |
| Rated output power | 11 kW / 15 HP | |
| Input voltage | 3 × 380–480 V AC | |
| Input phases | Three phase | |
| Protection rating | IP21 / UL Type 1 | |
| RFI filter | RFI class A2 (C3) | |
| Brake / Safe Stop | No brake chopper | |
| Control panel | Graphical local control panel (LCP 102) | |
| PCB coating | Standard (uncoated) PCBs | |
| Mains option | No mains option | |
| Product type | Frequency converter / variable frequency drive | |
| Frequency | 50 / 60 Hz | |
| Mounting type | Wall / panel mounting | |
| Application | HVAC systems | |
| Brake chopper | No brake chopper | |
| Cooling | Integrated cooling system | |
| Series functionality | Pump, fan and compressor control |
This unit is fitted with a LonWorks MCA 108 card, in addition to the built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee.
Yes. The IP21 / UL Type 1 enclosure is designed for direct mounting.
FC-102P11KT4E21H2XGXXXXSXXXXAGBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 11 kW / 15 HP | P11K |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP21 / UL Type 1 | E21 |
| RFI filter Position 16–17 | RFI class A2 (C3) | H2 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | LonWorks MCA 108 | AG |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |