131B7911 Danfoss VLT FC-102 HVAC Drive 3.0 kW / 4.0 HP, 380 - 480 VAC, IP20

131B7911 Danfoss VLT FC-102 HVAC Drive 3.0 kW / 4.0 HP, 380 – 480 VAC, IP20

Danfoss 131B7911 VLT HVAC Drive FC 102, a 3.0 kW three phase AC variable frequency drive designed for HVAC motor control, fans, pumps and building automation systems.

SKU: 131B7911Alt SKU: FC-102P3K0T4E20H2XNXXXXSXXXXAXBXCXXXXDXMPN: 131B7911
Price
List Price £938.00 ex VAT
Your Price (ex VAT) Save 45%
£515.90 45% OFF
You save £422.10 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £515.90
Trade pricing is personalised to your account

Manufacturer Lead Time

£515.90

Danfoss 131B7911 at a glance

The Danfoss 131B7911 is a 3.0 kW / 4.0 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame A2, IP20 / chassis unit, built for mounting inside a control panel or enclosure.

This configuration has RFI class A2 (C3), no brake chopper, and a numeric LCP 101 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP20 / chassis — built for mounting inside a control panel or enclosure.
  • EMC: RFI class A2 (C3). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

Same 3 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 3 kW
Voltage 480 V
Phase Three Phase
IP Rating IP20
EMC Filter Industrial
Series VLT HVAC Drive FC 102
Model code FC-102P3K0T4E20H2XNXXXXSXXXXAXBXCXXXXDX
Product type AC variable frequency drive
Rated output power 3.0 kW / 4.0 HP
Output current 6.3 A
Input voltage 380–480 V AC
Input phases 3-phase
Protection rating IP20 / chassis
RFI filter Class A2 (C3)
Control panel Numerical Local Control Panel
Brake chopper No brake chopper
PCB coating Not coated PCB
Mains option No mains option
Frame size A2
Installation type Panel / cabinet mounting
Weight approx. 5.0 kg

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

Does this drive need to go in an enclosure?

Yes. IP20 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.

Type code decoded

FC-102P3K0T4E20H2XNXXXXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
3.0 kW / 4.0 HPP3K0
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP20 / chassisE20
RFI filter
Position 16–17
RFI class A2 (C3)H2
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Numeric LCP 101N
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX