131B1272 Danfoss VLT FC-102 HVAC Drive 11 kW / 15 HP, 380 - 480 VAC, IP21

131B1272 Danfoss VLT FC-102 HVAC Drive 11 kW / 15 HP, 380 – 480 VAC, IP21

Danfoss 131B1272 VLT HVAC Drive FC 102 variable frequency drive featuring 11 kW output power, three-phase 380–480 V AC input, IP21 / Type 1 enclosure, graphical local control panel and RFI Class A1/B filter.

SKU: 131B1272Alt SKU: FC-102P11KT4E21H3XGXXXXSXXXXAXBXCXXXXDXMPN: 131B1272
Price
List Price £2,137.00 ex VAT
Your Price (ex VAT) Save 45%
£1,175.35 45% OFF
You save £961.65 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £1,175.35
Trade pricing is personalised to your account

Manufacturer Lead Time

£1,175.35

Danfoss 131B1272 at a glance

The Danfoss 131B1272 is an 11 kW (15 HP) VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame B1, IP21 / UL Type 1 unit, suitable for mounting in clean, dry indoor plant rooms.

This configuration has RFI class A1/B (C1) with reduced motor cable length, no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP21 / UL Type 1 — suitable for mounting in clean, dry indoor plant rooms.
  • EMC: RFI class A1/B (C1) is met only with a reduced screened motor cable length. Check the maximum length for this frame in the Danfoss FC 102 Design Guide (Technical Documents tab); for longer runs, ask us about an H2 (A2/C3) variant.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

This drive11 kWDanfoss 131B1272IP21 / UL Type 1 · frame B1
Larger15 kWDanfoss 131B5475IP21 / UL Type 1 · frame B1View drive →

Same 11 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 11 kW
Voltage 480 V
Phase Three Phase
IP Rating IP21
EMC Filter Commercial
Series VLT® HVAC Drive FC 102
Part Number 131B1272
Model Code FC-102P11KT4E21H3XGXXXXSXXXXAXBXCXXXXDX
Product type AC variable frequency drive
Rated output power 11 kW (15 HP)
Input voltage 380–480 V AC
Input phases 3-phase
Frequency 50 / 60 Hz
Protection rating IP21 / Type 1
Enclosure type Protected enclosure
Frame size B1
RFI filter Class A1/B (C1)
Brake chopper Not included
Local control panel Graphical LCP
Mounting type Wall / cabinet mounting
Typical gross weight approx. 24.51 kg

Frequently asked questions

What is the maximum motor cable length with this RFI filter?

The 131B1272 has the H3 filter: RFI class A1/B (C1) with a reduced motor cable length. The exact limit for this frame is in the Danfoss VLT HVAC Drive FC 102 Design Guide (see Technical Documents). If your screened cable run is longer, contact us and we will suggest an alternative.

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

Can this drive be wall mounted without a panel?

Yes. The IP21 / UL Type 1 enclosure is designed for direct mounting.

Type code decoded

FC-102P11KT4E21H3XGXXXXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
11 kW (15 HP)P11K
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP21 / UL Type 1E21
RFI filter
Position 16–17
RFI class A1/B (C1) with reduced motor cable lengthH3
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX