Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
EMAS HJ12X09UL enclosed DOL starter with 9 A contactor, 3.60-5.40 A thermal overload relay, start and reset buttons, 220-230 V AC control voltage and IP65 enclosure for industrial motor control.
£76.20
The EMAS HJ12X09UL is an HJ Series enclosed contactor with integrated thermal overload protection, designed for reliable motor starting, switching, and overload protection applications. This compact motor starter combines a 9A contactor, thermal overload relay, enclosure, start button, and reset button into a complete ready-to-install motor control solution.
Featuring a 220-230V AC 50/60Hz control voltage, a 9A contactor rating, and an adjustable thermal overload range of 3.60A to 5.40A, the EMAS HJ12X09UL provides dependable motor protection for industrial machinery, pumps, fans, compressors, and automation equipment.
The EMAS HJ12X09UL enclosed contactor is suitable for motor control applications including industrial machinery, pumps, fans, compressors, conveyors, HVAC systems, and automation equipment requiring integrated switching and thermal protection.
The EMAS HJ12X09UL provides a complete motor starter solution by combining contactor switching, thermal overload protection, and local operator controls in a compact enclosure. Its integrated design helps simplify installation while delivering dependable motor control performance.
Tick the specs you need, then view products that match.
| Current | 5.40 A | |
|---|---|---|
| Voltage | 230 V | |
| Phase | Three Phase | |
| IP Rating | IP65 | |
| Coil / Supply Voltage | 220 V AC, 230 V AC | |
| Series | HJ Series | |
| Product type | Enclosed DOL starter / contactor with thermal relay | |
| Contactor rating | 9 A | |
| Thermal relay range | 3.60-5.40 A | |
| Control voltage | 220-230 V AC | |
| Frequency | 50 / 60 Hz | |
| Usage category | AC-3 | |
| Insulation voltage | 690 V AC | |
| Impulse withstand voltage | 6 kV | |
| Dielectric strength | 1890 V AC | |
| Isolation resistance | 10 MΩ at 500 V DC | |
| Short-circuit breaking capacity | Ics 50 kA | |
| Mechanical life | minimum 100,000 operations | |
| Electrical life | minimum 100,000 operations | |
| Operating frequency | 600 mechanical / 600 electrical operations per hour | |
| Protection rating | IP65 | |
| Operating temperature | -5 to +40 °C | |
| Pollution degree | 3 | |
| Cable section | 1.5 mm² | |
| Screw torque | 1.8 Nm | |
| Enclosure | With start and reset button |
The EMAS HJ12X09UL is used for starting, switching, and protecting electric motors with an integrated contactor and thermal overload relay.
The thermal overload relay adjustment range is 3.60A to 5.40A.
The EMAS HJ12X09UL operates with a 220-230V AC 50/60Hz control supply.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.