Emas HJ12S09UI enclosed contactor with thermal overload relay, 9 A AC-3 current rating, 220-230 V 50/60 Hz voltage, start and reset buttons, pilot indicator and 2.50-3.70 A overload range for small motor control applications.
£76.20
The EMAS HJ12S09UI is an HJ Series enclosed contactor with integrated thermal overload protection, designed for reliable motor switching, control, and protection applications. This compact motor starter solution combines a 9A contactor, thermal overload relay, enclosure, start button, reset button, and pilot indicator into a single ready-to-install unit.
Featuring a 220-230V AC 50/60Hz coil voltage, a 9A AC-3 rated operational current, and a thermal overload adjustment range of 2.50A to 3.70A, the EMAS HJ12S09UI provides dependable motor protection for industrial machinery, pumps, fans, compressors, and automation systems.
The EMAS HJ12S09UI enclosed contactor is suitable for motor control applications including industrial machinery, HVAC systems, pumps, conveyors, compressors, and automation equipment where reliable switching and overload protection are required.
The EMAS HJ12S09UI provides a complete motor starter solution by combining contactor switching, thermal overload protection, and local operator controls in one compact enclosure. Its integrated design simplifies installation while providing reliable protection for low-voltage motor applications.
Tick the specs you need, then view products that match.
| Current | 9 A | |
|---|---|---|
| Phase | Three Phase | |
| IP Rating | IP30 | |
| Series | HJ Series | |
| Product type | Enclosed contactor with thermal overload relay | |
| Rated operational current Ie | 9 A | |
| Usage category | AC-3 | |
| Operational frequency | 50 / 60 Hz | |
| Thermal overload calibration interval | 2.50-3.70 A | |
| Enclosure controls | Start button, reset button and pilot indicator | |
| Protection rating | IP30 | |
| Rated insulation voltage Ui | 690 V AC | |
| Rated impulse withstand voltage Uimp | 6 kV | |
| Pollution degree | 3 | |
| Operating temperature | -5°C to +40°C | |
| Cable section | 1.5 mm² | |
| Screw torque | 1.8 Nm | |
| Short-circuit breaking capacity Ics | 50 kA | |
| Mechanical life | minimum 100,000 operations | |
| Electrical life | minimum 100,000 operations | |
| Operating frequency | 600 operations/hour mechanical and electrical |
The EMAS HJ12S09UI is used for controlling, switching, and protecting low-voltage motors with an integrated contactor and thermal overload relay.
The thermal overload relay adjustment range is 2.50A to 3.70A.
The EMAS HJ12S09UI operates with a 220-230V AC 50/60Hz coil supply.