Finder 7S.34.9.012.4310 is a four-contact force-guided safety relay module featuring a 12 V DC coil, 3 normally open and 1 normally closed contacts, a 6 A contact rating, 250 V AC nominal switching voltage, screw terminals, illuminated status indication and DIN rail mounting for industrial safety-related control applications.
£63.28
The Finder 7S.34.9.012.4310 is a professional 12 V DC force-guided safety relay module designed for industrial automation, machinery safety and monitored electrical control applications. Part of the Finder 7S Series, this four-contact relay features 3 normally open (NO) contacts and 1 normally closed (NC) contact, providing multiple switching outputs together with a mechanically linked feedback contact for use in appropriately engineered safety-related control systems.
Featuring a 6 A rated contact current, 250 V AC nominal switching voltage and 12 V DC operating coil, the Finder 7S.34.9.012.4310 combines electromagnetic switching with force-guided contact technology. Its mechanically linked contacts are designed to prevent normally open and normally closed contacts from being simultaneously closed under specified fault conditions, allowing suitable external monitoring circuits to detect certain relay failures, including welded contacts.
The module incorporates screw terminals, an integrated illuminated status indicator and standard DIN rail mounting. With IP20 ingress protection and an operating temperature range of −40 to +70 °C, it provides a practical solution for industrial control cabinets, machine safety assemblies and automation equipment requiring reliable switching and contact-state monitoring.
Industrial machinery and automated equipment often require electrical switching devices that operate predictably while providing reliable information about their contact states. In safety-related systems, faults such as welded relay contacts can prevent equipment from returning to its intended condition. The Finder 7S.34.9.012.4310 supports monitored control applications through its force-guided contact arrangement.
The relay provides three normally open contacts for switching suitable electrical circuits and one normally closed contact that can be incorporated into an external feedback monitoring circuit. Because the contacts are mechanically linked, the relay is designed to prevent normally open and normally closed contacts from being simultaneously closed under specified fault conditions. This characteristic allows appropriately designed monitoring equipment to detect certain contact failures.
Its 12 V DC coil is suitable for compatible low-voltage control supplies. With a nominal coil power consumption of 800 mW, the relay provides efficient electromagnetic operation. The 6 A rated contacts and 250 V AC nominal switching voltage support a variety of appropriately rated control applications, provided the connected loads comply with the manufacturer's switching limits.
The relay has a typical 12 ms operate time and 10 ms release time, supporting predictable switching behaviour. These values describe relay operation under specified conditions; the total response time of a safety-related control system must account for all associated controllers, monitoring devices and output equipment.
The screw-terminal construction provides a familiar wiring method for industrial panel builders and maintenance engineers. An integrated illuminated indicator gives local confirmation of relay energisation, while DIN rail mounting allows convenient installation alongside safety controllers, contactors, PLCs and other automation components.
Important: A force-guided relay is a component used within a safety-related control system, not a complete safety controller. The achieved Performance Level or Safety Integrity Level depends on the complete system architecture, diagnostic coverage, component reliability, fault monitoring and validation against applicable machinery safety standards.
Tick the specs you need, then view products that match.
| Device Type | Positively Guided Relay | |
|---|---|---|
| SIL (up to) | SIL 2 | |
| Timing Function | None (instantaneous) | |
| Mounting Type | DIN rail | |
| Terminal Type | Screw | |
| Auxiliary Contacts | 1 NC | |
| Switching Current (A) | 6 A | |
| Manufacturer | Finder | |
| Series | 7S Series | |
| Product family | 7S.34 | |
| Model | 7S.34.9.012.4310 | |
| Manufacturer part number | 7S.34.9.012.4310 | |
| Alternative reference | 7S3490124310 | |
| Product type | Modular force-guided safety relay | |
| Relay technology | Electromagnetic | |
| Contact configuration | 3 NO + 1 NC | |
| Number of contacts | 4 | |
| Normally open contacts | 3 | |
| Normally closed contacts | 1 | |
| Contact technology | Force-guided, mechanically linked | |
| Contact material | Silver tin oxide (AgSnO) | |
| Rated contact current | 6 A | |
| Nominal switching voltage | 250 V AC | |
| Nominal coil voltage | 12 V DC | |
| Nominal coil power | 800 mW | |
| Nominal coil current | 64.7 mA | |
| Coil resistance | 185.5 Ω | |
| Must-operate voltage | 9.6 V DC | |
| Must-release voltage | 1.2 V DC | |
| Typical operate time | 12 ms | |
| Typical release time | 10 ms | |
| Terminal type | Screw terminals | |
| Mounting | DIN rail | |
| Ingress protection | IP20 | |
| Operating temperature | −40 to +70 °C | |
| Status indication | Integrated illuminated indicator | |
| Relevant contact standard | EN 61810-3 | |
| RoHS compliance | RoHS compliant | |
| Country of origin | Italy | |
| Application | Industrial automation and safety-related control systems |
The Finder 7S.34.9.012.4310 is a four-contact force-guided relay module designed for industrial automation and safety-related control applications requiring mechanically linked contacts, dependable switching and contact-state feedback.
The relay has a 12 V DC coil with a nominal power consumption of 800 mW.
The Finder 7S.34.9.012.4310 has four contacts, arranged as 3 normally open (NO) and 1 normally closed (NC).
Force-guided contacts are mechanically linked normally open and normally closed contacts designed to prevent simultaneous closure under specified fault conditions. This allows suitable external monitoring circuits to detect certain relay contact failures.
The relay has a 6 A rated contact current. The permissible switching load depends on the electrical load type, operating voltage and applicable manufacturer ratings.
The Finder 7S.34.9.012.4310 has a 250 V AC nominal switching voltage, subject to the specified contact current and switching duty limits.
The relay uses screw terminals, providing secure electrical connections for industrial control panel wiring.
The 7S.34.9.012.4310 provides 3 NO + 1 NC contacts, whereas the 7S.34.9.012.4220 provides 2 NO + 2 NC contacts. Both use a 12 V DC coil and belong to the Finder 7S.34 family, but their contact arrangements differ and must be considered before substitution.
The Finder 7S.34 family uses screw-terminal connections, whereas the 7S.14 family uses screwless terminals. Both families include four-contact force-guided relay configurations, but the complete part number must be checked before substitution.
Yes. The Finder 7S.34.9.012.4310 includes an integrated illuminated indicator that provides visual confirmation of relay energisation.
The nominal coil current is approximately 64.7 mA at a 12 V DC supply, with a coil resistance of approximately 185.5 Ω.
The relay has a typical 12 ms operate time and 10 ms release time under specified operating conditions.
The device is designed for DIN rail mounting inside a suitable electrical control enclosure.
The relay has an operating temperature range of −40 to +70 °C, making it suitable for a wide range of protected industrial control environments.
Yes. The relay can form part of a properly designed emergency-stop control system where its contact arrangement, electrical ratings and monitoring characteristics meet the application requirements. It is not a complete emergency-stop controller on its own.
No. The Finder 7S.34.9.012.4310 is a component within a safety-related control system. The achieved Performance Level or Safety Integrity Level depends on the complete architecture, diagnostic coverage, reliability calculations and system validation.
Check the 12 V DC coil supply, 3 NO + 1 NC contact arrangement, switching current, load voltage, safety monitoring requirements, screw-terminal wiring, environmental conditions and Finder's installation instructions.
Finder 7S Series force-guided relays provide dependable switching and contact-state monitoring capabilities for industrial automation and safety-related electrical control systems. Combining a 12 V DC coil, 3 NO + 1 NC mechanically linked contacts, a 6 A contact rating, screw terminals, illuminated status indication and DIN rail construction, the Finder 7S.34.9.012.4310 offers a practical solution for professionally engineered machinery control and monitoring applications.