Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 7S.32.9.024.5110 is a 24 V DC DIN rail-mounted safety relay module featuring Class A forcibly guided contacts, 1 NO + 1 NC contact configuration, 6 A rated contact current, 250 V AC nominal switching voltage, gold-plated silver-nickel contacts, screw terminals and integrated LED indication for industrial safety-related control applications.
£32.45
The Finder 7S.32.9.024.5110 is a professional 24 V DC safety relay module with Class A forcibly guided contacts, designed for industrial machinery, automation systems and safety-related electrical control applications. Part of the Finder Series 7S, this compact DIN rail-mounted relay features a 1 normally open (NO) + 1 normally closed (NC) contact configuration, a 6 A contact rating and conventional screw terminals.
Engineered for applications where dependable switching and contact monitoring are essential, the Finder 7S.32.9.024.5110 incorporates mechanically linked contacts that help external monitoring circuits detect certain relay faults, including welded contacts. Its forcibly guided contact arrangement is designed in accordance with EN 61810-3, making it suitable for integration into appropriately designed safety-related control systems.
The relay operates from a 24 V DC nominal coil supply and offers a 250 V AC nominal switching voltage. It features gold-plated silver-nickel contacts, an integrated LED coil status indicator and a compact 22.5 mm-wide housing suitable for installation on a standard 35 mm DIN rail.
With an operating temperature range of −40 to +70 °C, an IP20 protection rating and a mechanical endurance of 10 million operations, the Finder 7S.32.9.024.5110 provides a reliable relay interface for industrial safety monitoring, machine control and automation applications.
The defining feature of the Finder 7S.32.9.024.5110 is its use of Class A forcibly guided contacts. This technology mechanically links the normally open and normally closed contacts so that they cannot simultaneously assume their closed positions under specified contact fault conditions.
In a conventional relay, a welded contact may not always be detectable through the state of another contact. Forcibly guided contact technology provides a mechanical relationship between the contacts that supports the detection of certain failures.
For example, if the normally open contact becomes welded closed, the mechanically linked normally closed contact is prevented from returning to its normal closed position. An appropriately designed safety monitoring circuit can detect this discrepancy and respond according to the requirements of the safety function.
The Finder 7S.32.9.024.5110 provides one normally open contact for a controlled switching function and one normally closed contact that may be incorporated into a feedback or monitoring circuit.
Its contact arrangement makes the module particularly useful in machinery control systems where relay switching must be monitored and where reliable fault detection forms part of the overall safety design.
Important: The Finder 7S.32.9.024.5110 is a relay module with forcibly guided contacts, not a complete safety controller. It must be integrated into an appropriately designed and validated safety-related control system.
The Finder 7S.32.9.024.5110 operates from a 24 V DC nominal coil supply, making it suitable for a wide variety of industrial automation and machinery control systems.
The relay has a specified must-operate voltage of 16.8 V DC and a must-release voltage of 2.4 V DC. These are defined switching thresholds rather than the full permissible continuous operating voltage range.
At nominal voltage, the coil draws approximately 38.2 mA, with a rated power consumption of 0.9 W and an approximate coil resistance of 628.3 Ω.
These characteristics should be considered when selecting a suitable DC power supply, PLC output or other control device. The supply must meet the relay's electrical requirements and account for voltage tolerances and switching conditions.
The relay offers a specified 7 ms operate time and 11 ms release time, providing predictable relay switching behaviour for industrial control applications.
These timing figures describe the relay itself and must not be treated as the total response time or stopping time of a complete machinery safety system.
The Finder 7S.32.9.024.5110 features two mechanically linked contacts arranged as one normally open and one normally closed.
The normally open contact can be used to switch an appropriately rated electrical load, while the normally closed contact can provide feedback to a suitable monitoring circuit. This arrangement is useful where a controlled switching function must be accompanied by contact status monitoring.
The relay has a 6 A rated contact current and a 250 V AC nominal switching voltage, with a rated switching capacity of 1,500 VA under specified conditions.
Its silver-nickel contacts with gold plating are designed to provide dependable electrical contact performance.
The permissible switching load depends on the application, particularly where inductive loads, high inrush currents or frequent switching are involved. The manufacturer's load-specific ratings should always be checked before installation.
A key feature of the Finder 7S.32.9.024.5110 is its use of conventional screw terminals.
This distinguishes the Finder 7S.32 from the closely related 7S.12 family, which uses screwless terminals. The 7S.32 version is particularly suitable for electrical installations where screw terminal connections are preferred or specified.
Screw terminals provide a familiar wiring method for industrial control cabinets and electrical panels. Conductors should be prepared and tightened in accordance with the manufacturer's instructions, including the applicable conductor sizes and tightening torque.
The relay is designed for mounting on a standard 35 mm DIN rail and has a compact housing measuring 22.5 mm wide, 86.2 mm high and 100.3 mm deep.
An integrated LED coil status indicator provides visual confirmation when the relay coil is energised, helping technicians during commissioning, inspection and fault diagnosis.
The LED indicates coil energisation and does not independently verify the physical condition of every relay contact.
The Finder 7S.32.9.024.5110 is designed for industrial environments where reliable electrical switching and mechanical durability are important.
The relay has a specified mechanical endurance of 10 million operations and an electrical endurance of 100,000 operations under defined test conditions.
Actual service life depends on factors including contact loading, switching frequency, environmental conditions and installation practices.
With an ambient operating temperature range of −40 to +70 °C, the relay can be used in a wide variety of industrial electrical environments.
The module has an IP20 protection rating and should be installed within a suitable electrical enclosure that provides the protection required by the application.
Finder Series 7S relays are designed for safety-related applications requiring forcibly guided contacts. Their mechanically linked contact construction supports diagnostic monitoring within correctly designed electrical control systems.
The Series 7S range is associated with functional safety applications up to SIL 2 according to IEC 61508 and PL d according to EN ISO 13849-1, subject to the relevant product documentation and complete system design.
The safety performance of an installation depends on the overall circuit architecture, diagnostic coverage, reliability calculations and the response to detected faults.
The Finder 7S.32.9.024.5110 may be incorporated into emergency-stop circuits, machine guard interlocks and other monitored control functions where its electrical and safety characteristics meet the system requirements.
Important: The relay alone does not establish a particular Safety Integrity Level, Performance Level or safety category for the complete installation. The safety function must be designed, assessed and validated by a competent professional.
Tick the specs you need, then view products that match.
| Device Type | Positively Guided Relay | |
|---|---|---|
| Terminal Type | Screw | |
| Switching Current (A) | 6 A | |
| Mounting Type | DIN rail | |
| Manufacturer | Finder | |
| Series | 7S | |
| Product code | 7S.32.9.024.5110 | |
| Product type | Relay module with forcibly guided contacts | |
| Contact configuration | 1 NO + 1 NC | |
| Number of contacts | 2 | |
| Contact form | DPST-NO/NC, 1 Form A + 1 Form B | |
| Contact guidance | Class A forcibly guided | |
| Contact guidance standard | EN 61810-3 | |
| Nominal coil voltage | 24 V DC | |
| Must-operate voltage | 16.8 V DC | |
| Must-release voltage | 2.4 V DC | |
| Rated coil current | 38.2 mA | |
| Rated coil power | 0.9 W | |
| Coil resistance | Approximately 628.3 Ω | |
| Rated contact current | 6 A | |
| Nominal switching voltage | 250 V AC | |
| Rated switching capacity | 1,500 VA | |
| Contact material | Silver-nickel (AgNi) with gold (Au) plating | |
| Operate time | 7 ms | |
| Release time | 11 ms | |
| Mechanical endurance | 10,000,000 operations | |
| Electrical endurance | 100,000 operations under specified test conditions | |
| Rated insulation voltage | 250 V | |
| Pollution degree | 2 | |
| Terminal type | Screw terminals | |
| Coil status indication | Integrated LED | |
| Mounting method | DIN rail | |
| DIN rail size | 35 mm | |
| Housing dimensions | 22.5 × 86.2 × 100.3 mm | |
| Ingress protection | IP20 | |
| Operating temperature | −40 to +70 °C | |
| RoHS compliance | Yes | |
| Country of origin | Italy | |
| EAN / GTIN | 8012823420271 | |
| Farnell UK order code | 4068527 |
The Finder 7S.32.9.024.5110 is a 24 V DC relay module with forcibly guided contacts, designed for industrial safety-related control systems, machinery automation and monitored switching applications.
The relay features a 1 normally open (NO) + 1 normally closed (NC) contact configuration, providing two mechanically linked contacts.
The Finder 7S.32.9.024.5110 uses a 24 V DC nominal coil. Its specified must-operate voltage is 16.8 V DC, and its must-release voltage is 2.4 V DC.
Class A forcibly guided contacts are mechanically linked normally open and normally closed contacts designed so that they cannot simultaneously assume their closed positions under specified fault conditions. This supports the detection of certain relay failures, including welded contacts.
The Finder 7S.32.9.024.5110 has a 6 A rated contact current. The permissible switching load depends on the load type and the manufacturer's specified operating conditions.
The relay has a 250 V AC nominal switching voltage, making it suitable for appropriately rated AC control circuits.
The relay uses silver-nickel (AgNi) contacts with gold (Au) plating, designed for dependable electrical contact performance.
Yes. The relay includes an integrated LED coil status indicator, allowing technicians to identify when the coil is energised.
The Finder 7S.32.9.024.5110 uses screw terminals. The closely related Finder 7S.12 family uses screwless terminals.
Yes. The relay is designed for mounting on a standard 35 mm DIN rail and has a compact housing width of 22.5 mm.
The relay is designed for ambient operating temperatures from −40 to +70 °C, supporting installation in a range of industrial electrical environments.
The Finder 7S.32.9.024.5110 has a specified 7 ms operate time and 11 ms release time. These values describe the relay itself rather than the total response time of a complete machinery safety system.
No. The Finder 7S.32.9.024.5110 is a relay module with forcibly guided contacts, not a standalone safety controller. It must be integrated into an appropriately designed and validated safety-related control system.
The main difference is the terminal connection type. The Finder 7S.12.9.024.5110 uses screwless terminals, while the Finder 7S.32.9.024.5110 uses screw terminals. Both are 24 V DC Series 7S relays with 1 NO + 1 NC forcibly guided contacts.
Finder Series 7S relay modules combine Class A forcibly guided contact technology with compact DIN rail construction and dependable industrial switching performance. Featuring a 24 V DC coil, 1 NO + 1 NC contacts, 6 A contact rating, gold-plated silver-nickel contacts and screw terminal connections, the Finder 7S.32.9.024.5110 provides a practical relay component for appropriately designed industrial safety-related control systems.
Technical references: Farnell UK – Finder 7S.32.9.024.5110, DigiKey – Finder 7S.32.9.024.5110 specifications and TME UK – Finder 7S.32.9.024.5110 technical data. Verify the current manufacturer's datasheet and installation instructions before selecting the relay for a safety-related function.