Finder 7S.14.9.048.4220 is a modular forcibly guided safety relay with a 48 V DC coil, four contacts arranged as 2 normally open and 2 normally closed, 6 A rated contact current, 250 V AC nominal switching voltage, silver tin oxide contacts, spring-loaded screwless terminals, LED coil status indication, IP20 protection and compact 22.5 mm DIN rail housing. Designed for industrial automation and appropriately engineered safety-related control systems.
£77.12
The Finder 7S.14.9.048.4220 is a professional 48 V DC modular safety relay with forcibly guided contacts, designed for industrial machinery, automation systems and safety-related control applications. Part of the Finder 7S Series, this four-pole relay combines a 2 normally open (NO) + 2 normally closed (NC) contact arrangement, a 6 A contact rating and screwless spring terminals in a compact DIN rail-mounted housing.
Forcibly guided contacts are particularly important in safety-related control circuits because they provide a defined mechanical relationship between normally open and normally closed contacts. This arrangement helps external monitoring circuits detect certain relay contact faults, including welded contacts, when the relay is incorporated into an appropriately designed safety system.
The Finder 7S.14.9.048.4220 operates from a 48 V DC coil supply, making it suitable for industrial control installations using this voltage. Its four-contact configuration provides two normally open switching paths and two normally closed paths that may be used for monitoring, feedback or other appropriately engineered control functions.
With silver tin oxide (AgSnO) contacts, a 250 V AC nominal switching voltage, an IP20 protection rating and a compact 22.5 mm housing width, this relay is designed for integration into industrial control panels and machine safety electrical assemblies.
The spring-loaded, screwless terminals simplify wiring, while the integrated LED coil status indicator supports commissioning and fault diagnosis. Its forcibly guided contact construction makes it a useful component for machine builders, automation engineers and industrial maintenance professionals working with safety-related relay circuits.
The key feature of the Finder 7S.14.9.048.4220 is its forcibly guided contact mechanism. This design provides a mechanical relationship between normally open and normally closed contacts that can be used to support diagnostic monitoring in safety-related control systems.
In a conventional relay, the behaviour of individual contacts during certain faults may not provide the mechanical relationship required for safety monitoring. A forcibly guided relay is designed so that normally open and normally closed contacts cannot simultaneously assume specified contradictory closed positions.
For example, if a normally open contact becomes welded closed, the mechanically linked normally closed contact is prevented from returning to its normal closed position under the defined fault condition. A correctly designed feedback circuit can detect this condition and prevent an unsafe restart or indicate a fault, depending on the complete safety system design.
The Finder 7S.14.9.048.4220 has a 2 NO + 2 NC contact arrangement, making it suitable for circuits requiring both normally open switching contacts and normally closed feedback contacts.
The relay is intended for applications using the Class A forcibly guided contact principle according to EN 61810-3. Its integration into a complete safety-related control system must be assessed according to the relevant machinery safety requirements.
Importantly, the Finder 7S.14.9.048.4220 is a safety-related relay component, not a complete standalone safety controller. The safety performance of the complete system depends on the circuit architecture, diagnostics, monitoring, fault handling and validation.
The four-contact arrangement of the Finder 7S.14.9.048.4220 consists of two normally open contacts and two normally closed contacts.
The normally open contacts can be used for appropriately rated switching functions, such as enabling control circuits or interfacing with external equipment. The normally closed contacts may be used for monitoring and feedback functions where the mechanical contact guidance is required.
For the 7S.14...4220 configuration, the contact terminal pairs are:
The relay has a 6 A rated contact current and a 250 V AC nominal switching voltage. Actual permissible switching loads depend on the load type, electrical characteristics and operating duty specified by Finder.
The use of silver tin oxide contacts supports switching performance in industrial control applications. Contact wear and electrical service life depend on switching current, voltage, load characteristics and the number of operating cycles.
The Finder 7S.14.9.048.4220 is designed for a 48 V DC nominal coil supply. This makes it suitable for compatible industrial control systems that use 48 V DC power distribution.
Finder's 7S.14 coil data specifies an operating voltage range of 38.4 to 57.6 V DC for the 48 V DC coil option. The nominal coil current is approximately 13.5 mA, with a rated coil power of approximately 0.7 W.
Correct coil voltage is essential for reliable relay operation. An undersupplied coil may not operate as intended, while excessive voltage can cause overheating or damage.
The integrated LED status indicator provides a convenient visual indication of coil energisation, helping engineers identify whether the control circuit is applying power to the relay.
The coil must be connected with the polarity and electrical arrangement specified in Finder's installation documentation, including any relevant suppression or protection requirements.
The Finder 7S.14.9.048.4220 is designed for installation on a standard 35 mm DIN rail within a suitable electrical control enclosure.
Its 22.5 mm housing width allows efficient use of panel space, making it suitable for compact industrial control cabinets and machine electrical assemblies.
The spring-loaded screwless terminals allow conductors to be connected without conventional screw-clamp terminals. This can simplify assembly and maintenance when the manufacturer's specified wiring procedures are followed.
During installation, the relay coil and all four contact circuits must be connected according to the appropriate Finder wiring diagram. The normally closed and normally open contact arrangements must be identified correctly, particularly where the relay is used for monitored safety-related functions.
Where the relay is part of a safety-related control circuit, commissioning should include verification of the intended switching sequence, feedback monitoring, fault response and restart behaviour.
The relay has an IP20 protection rating and is intended for installation inside an appropriately rated electrical enclosure. It is not suitable for unprotected exposure to water, dust or outdoor environmental conditions.
Installation and maintenance should be performed by a competent electrical professional, with the complete safety system designed and validated according to the applicable machinery safety requirements.
Tick the specs you need, then view products that match.
| Device Type | Positively Guided Relay | |
|---|---|---|
| Terminal Type | Spring clamp | |
| Mounting Type | DIN rail | |
| Switching Current (A) | 6 A | |
| Manufacturer | Finder | |
| Series | 7S Series | |
| Product family | 7S.14 | |
| Manufacturer part number | 7S.14.9.048.4220 | |
| Alternative code | 7S1490484220 | |
| EAN / GTIN | 8012823420417 | |
| Product type | Modular forcibly guided safety relay | |
| Coil voltage | 48 V DC | |
| Coil supply type | DC | |
| Coil operating voltage range | 38.4 to 57.6 V DC | |
| Rated coil input current | Approximately 13.5 mA | |
| Rated coil power | Approximately 0.7 W | |
| Contact configuration | 2 NO + 2 NC | |
| Number of poles | 4 | |
| Rated contact current | 6 A | |
| Nominal contact switching voltage | 250 V AC | |
| Contact material | Silver tin oxide (AgSnO) | |
| Contact guidance | Forcibly guided | |
| Contact terminal arrangement | 11-12, 21-22, 33-34, 43-44 | |
| Coil terminal identification | A1 and A2 | |
| Terminal type | Spring-loaded / screwless | |
| Mounting method | DIN rail | |
| Nominal housing width | 22.5 mm | |
| Approximate housing height | 86.2 mm | |
| Ingress protection | IP20 | |
| Operating temperature range | -40 °C to +70 °C | |
| Coil status indication | LED | |
| Contact guidance standard | EN 61810-3 | |
| Country of origin | Italy | |
| Typical applications | Machinery safety-related control, industrial automation and relay monitoring circuits |
The Finder 7S.14.9.048.4220 is a modular relay with forcibly guided contacts, designed for industrial automation and safety-related control applications. It can be used in appropriately engineered circuits requiring mechanically linked switching and feedback contacts.
The relay has a 48 V DC coil, with a specified operating voltage range of approximately 38.4 to 57.6 V DC.
The relay has four contacts, arranged as 2 normally open (NO) and 2 normally closed (NC).
The Finder 7S.14.9.048.4220 has a 6 A rated contact current and a 250 V AC nominal switching voltage, subject to the manufacturer's specified load conditions.
Forcibly guided contacts are mechanically linked so that normally open and normally closed contacts cannot simultaneously assume specified contradictory closed states. This behaviour allows appropriately designed monitoring circuits to detect certain contact failures, including welded contacts.
Yes. The relay uses spring-loaded, screwless terminals for electrical connections.
Yes. The relay includes an LED coil status indicator, providing a visible indication of relay energisation.
No. The Finder 7S.14.9.048.4220 is a forcibly guided relay component. A complete safety function requires appropriate control architecture, monitoring, diagnostics and validation.
The 7S.14.9.048.4220 has a 2 NO + 2 NC contact configuration, whereas the 7S.14.9.048.4310 uses a 3 NO + 1 NC arrangement. Both belong to the Finder 7S.14 family, but their contact arrangements are different and they should not be treated as interchangeable without checking the circuit requirements.
The relay is designed for 35 mm DIN rail mounting and has a compact 22.5 mm housing width.
The relay is specified for operation between -40 °C and +70 °C, subject to correct installation conditions.
The product's listed EAN / GTIN is 8012823420417.
The Finder 7S.14.9.048.4220 provides forcibly guided relay technology for industrial automation and safety-related control systems. Combining a 48 V DC coil, 2 NO + 2 NC contacts, 6 A switching capability, screwless spring terminals, LED indication and compact DIN rail mounting, it is a practical component for appropriately designed switching and feedback circuits.
Manufacturer technical reference: Finder 7S Series Modular Relays with Forcibly Guided Contacts – Technical Datasheet.