Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 7S.12.9.012.5110 is a 12 V DC DIN rail-mounted safety relay module with Class A forcibly guided contacts, 1 NO + 1 NC configuration, 6 A contact rating, 250 V AC switching voltage, screwless spring-clamp terminals, LED coil indication and compact 22.5 mm housing for industrial safety-related control systems.
£34.40
The Finder 7S.12.9.012.5110 is a professional 12 V DC safety relay module with forcibly guided contacts, designed for industrial machinery, automation systems and safety-related electrical control applications. Part of the Finder Series 7S, this compact DIN rail-mounted relay module features a 1 normally open (NO) + 1 normally closed (NC) contact configuration, a 6 A contact rating and spring-clamp terminals for reliable electrical connections.
Engineered for applications where contact reliability and predictable switching behaviour are essential, the Finder 7S.12.9.012.5110 incorporates Class A forcibly guided contacts in accordance with EN 61810-3. This mechanically linked contact arrangement helps prevent the normally open and normally closed contacts from simultaneously assuming their closed positions in the event of a contact welding fault, supporting fault detection within an appropriately designed safety-related control system.
The module features a 12 V DC operating coil, LED coil status indication, gold-plated silver-nickel contacts and a compact 22.5 mm-wide housing. Designed for installation on a standard 35 mm DIN rail, it is suitable for machinery safety circuits, industrial automation panels and control systems requiring dependable relay switching with mechanically linked contacts.
With an operating temperature range of −40 to +70 °C, IP20 protection and a mechanical endurance of 10 million operations, the Finder 7S.12.9.012.5110 offers a practical solution for safety-related industrial control applications.
The defining feature of the Finder 7S.12.9.012.5110 is its use of Class A forcibly guided contacts. Unlike ordinary relay contacts, the normally open and normally closed contacts are mechanically linked so that a specified minimum separation is maintained between opposing contacts if one contact becomes welded.
This mechanical arrangement helps a correctly designed monitoring circuit detect certain relay contact faults. For example, if a normally open contact becomes welded closed, the associated normally closed contact cannot return to its normal closed state. A suitable safety controller or monitoring circuit can use this behaviour to identify a fault and prevent an unsafe restart.
The relay provides one normally open contact for a controlled switching function and one normally closed contact that can be incorporated into a feedback or monitoring circuit. The precise allocation of these contacts depends on the application and the safety circuit design.
The Finder 7S Series uses forcibly guided relay technology in accordance with EN 61810-3, supporting its integration into machinery safety systems designed according to relevant functional safety standards.
Important: The Finder 7S.12.9.012.5110 is a relay module with forcibly guided contacts, not a complete safety controller. The relay alone does not establish a safety category, Performance Level or Safety Integrity Level for an installation. The complete safety function must be designed, assessed and validated using the applicable standards.
The Finder 7S.12.9.012.5110 operates from a 12 V DC nominal coil supply, with a specified operating voltage range of 9.6 to 14.4 V DC. Its coil draws approximately 55 mA at nominal voltage, corresponding to a rated power consumption of approximately 0.7 W.
The module offers a 6 A rated contact current and a 250 V AC rated switching voltage, allowing it to interface with a variety of suitable industrial control loads. Contact loading must always remain within the applicable ratings for the load type and switching conditions.
The silver-nickel contacts with gold plating are designed to provide reliable electrical contact performance. The gold-plated contact surfaces are particularly useful in applications where dependable contact operation is important, including suitably specified low-energy monitoring circuits.
With an operating time of approximately 7 ms and a release time of approximately 11 ms, the module provides defined switching characteristics for control circuit design. These relay timings should not be treated as the total stopping time of a machine or complete safety system.
The Finder 7S.12.9.012.5110 safety relay module is housed in a compact enclosure measuring approximately 22.5 mm wide, 86.2 mm high and 100.3 mm deep. Its slim construction makes it suitable for installation in industrial automation cabinets where DIN rail space is limited.
The relay uses screwless spring-clamp terminals, allowing conductors to be connected without conventional screw terminals. When installed using the manufacturer's recommended conductor sizes and wiring procedure, spring-clamp connections provide a secure and maintenance-friendly termination method.
An integrated LED coil status indicator provides immediate visual confirmation of coil energisation, helping technicians during commissioning and fault diagnosis. The LED indicates the coil's electrical status; it does not independently verify the state of every relay contact or the safety of the connected machinery.
The module has an IP20 protection rating and should be installed inside a suitable electrical enclosure. Its wide −40 to +70 °C operating temperature range supports applications in demanding industrial environments, subject to the manufacturer's installation requirements.
Finder Series 7S relay modules are designed for integration into safety-related electrical control systems. Their forcibly guided contacts make them suitable components for applications involving contact monitoring and fault detection.
The Series 7S is associated with applications up to SIL 2 according to IEC 61508, subject to the architecture, diagnostic coverage, reliability calculations and validation of the complete system. Machinery safety applications may also be assessed under EN ISO 13849-1.
The Finder 7S.12.9.012.5110 has a single-channel architecture. Its use in a safety function must therefore be assessed against the required Performance Level, Safety Integrity Level and fault tolerance of the complete installation.
For emergency-stop circuits, guard monitoring, machine interlocks and other safety-related applications, the relay should be integrated with appropriate safety monitoring and control equipment. A qualified functional safety professional should verify the circuit architecture, contact ratings, diagnostic measures and required safety performance before commissioning.
Tick the specs you need, then view products that match.
| Device Type | Positively Guided Relay | |
|---|---|---|
| Mounting Type | DIN rail | |
| Switching Current (A) | 6 A | |
| Load Voltage | 250 V AC | |
| Manufacturer | Finder | |
| Series | 7S | |
| Model | 7S.12.9.012.5110 | |
| Product type | Safety relay module with forcibly guided contacts | |
| Relay architecture | Single-channel | |
| Contact configuration | 1 NO + 1 NC | |
| Number of poles | 2 | |
| Contact guidance | Class A forcibly guided contacts | |
| Contact guidance standard | EN 61810-3 | |
| Nominal coil voltage | 12 V DC | |
| Coil operating voltage range | 9.6 to 14.4 V DC | |
| Rated coil current | 55 mA | |
| Rated coil power | 0.7 W | |
| Approximate coil resistance | 218.2 Ω | |
| Rated contact current | 6 A | |
| Rated switching voltage | 250 V AC | |
| Rated switching capacity | 1,500 VA | |
| Contact material | Silver-nickel (AgNi) with gold plating | |
| Operate time | 7 ms | |
| Release time | 11 ms | |
| Mechanical endurance | 10,000,000 operations | |
| Electrical endurance | 100,000 operations under specified test conditions | |
| Rated insulation voltage | 250 V | |
| Pollution degree | 2 | |
| Electrical connection | Screwless spring-clamp terminals | |
| Coil status indication | Integrated LED | |
| Mounting method | DIN rail | |
| DIN rail size | 35 mm | |
| Housing width | 22.5 mm | |
| Housing height | 86.2 mm | |
| Housing depth | 100.3 mm | |
| Ingress protection | IP20 | |
| Operating temperature | −40 to +70 °C | |
| Safety-related applications | Up to SIL 2, subject to complete system design and assessment | |
| Machine safety framework | EN ISO 13849-1, subject to system-level validation | |
| EAN / GTIN | 8012823368153 |
The Finder 7S.12.9.012.5110 is a 12 V DC relay module with forcibly guided contacts, designed for integration into industrial machinery safety-related control circuits, automation systems and applications requiring reliable contact switching and fault monitoring.
Forcibly guided contacts are mechanically linked normally open and normally closed contacts designed so that they cannot both be closed simultaneously under specified contact fault conditions. This allows appropriately designed monitoring circuits to detect certain relay failures, such as welded contacts.
The relay has a 1 normally open (NO) + 1 normally closed (NC) contact configuration, providing two mechanically linked contacts for switching and monitoring functions.
The Finder 7S.12.9.012.5110 uses a 12 V DC nominal coil, with an operating voltage range of approximately 9.6 to 14.4 V DC.
The Finder 7S.12.9.012.5110 has a 6 A rated contact current and a 250 V AC rated switching voltage. The permitted load must be checked against the relevant contact ratings and application conditions.
Yes. The module includes an integrated LED coil status indicator, providing visual confirmation when the relay coil is energised.
The Finder 7S.12.9.012.5110 uses screwless spring-clamp terminals, providing secure electrical connections without conventional screw terminals.
Yes. The module is designed for installation on a standard 35 mm DIN rail and has a compact housing width of approximately 22.5 mm.
The Finder 7S.12.9.012.5110 is designed for operation in ambient temperatures from −40 to +70 °C, making it suitable for a wide range of industrial electrical environments.
The relay has a specified mechanical endurance of 10 million operations. Actual service life depends on electrical loading, switching frequency, environmental conditions and installation practices.
No. The Finder 7S.12.9.012.5110 is a relay module with forcibly guided contacts, not a standalone safety controller. It must be integrated into a correctly designed and validated safety-related control system where required.
Finder Series 7S relay modules are intended for integration into applications up to SIL 2 according to IEC 61508, subject to the design, architecture, reliability calculations and validation of the complete safety function. The relay alone does not provide a SIL 2 rating for an entire system.
Unlike a conventional relay, the Finder 7S.12.9.012.5110 uses Class A forcibly guided contacts. This mechanical linkage supports detection of certain contact faults in appropriately designed safety-related monitoring circuits.
The module measures approximately 22.5 mm wide, 86.2 mm high and 100.3 mm deep, making it suitable for compact DIN rail-mounted industrial control installations.
Finder Series 7S relay modules combine Class A forcibly guided contact technology, dependable industrial switching performance and compact DIN rail construction. With a 12 V DC coil, 1 NO + 1 NC contact configuration, 6 A contact rating, screwless spring-clamp terminals and LED coil indication, the Finder 7S.12.9.012.5110 provides a reliable relay component for appropriately designed industrial safety-related control systems.