Finder 77.F1.9.024.8650 - 77 Series Modular solid state relays

Finder 77.F1.9.024.8650 – 77 Series Modular solid state relays

Finder 77.F1.9.024.8650 is an 80 A single-phase solid state relay with a 3–32 V DC control input, 24–660 V AC load switching range, zero-crossing operation, screw terminals and panel or heat-sink mounting for industrial AC load control.

SKU: 77.F1.9.024.8650Alt SKU: 77F190248650MPN: 77.F1.9.024.8650
Price
List Price £52.94 ex VAT
Your Price (ex VAT) Save 30%
£37.06 30% OFF
You save £15.88 per unit
Manufacturer Lead Time Standard Manufacturer Lead Time 6-8 Weeks, Call For Express Delivery Options
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £37.06
Trade pricing is personalised to your account

Manufacturer Lead Time

£37.06

Why Choose the Finder 77.F1.9.024.8650 Solid State Relay?

The Finder 77.F1.9.024.8650 is an industrial 80 A single-phase solid state relay (SSR) designed for high-current, contactless switching of AC electrical loads. Part of the Finder 77 Series, this relay provides a robust electronic switching solution for industrial heating, process control, automated machinery and electrical control systems.

Featuring a 3–32 V DC control input and a 24–660 V AC load switching range, the Finder 77.F1.9.024.8650 enables compatible low-voltage electronic controllers to operate higher-voltage AC equipment. Its single normally open semiconductor output (SPST-NO) is rated at 80 A when installed with appropriate thermal management, making it suitable for demanding applications requiring frequent switching.

The relay incorporates zero-crossing switching, which initiates conduction near an AC voltage zero crossing to help reduce electrical switching interference. Its hockey-puck-style housing, protective folding screw cover, screw terminals and panel or heat-sink mounting arrangement provide a practical installation format for industrial electrical assemblies.

Key Advantages

  • 80 A rated load current for suitably rated single-phase AC applications.
  • 3–32 V DC control input for integration with compatible PLCs and electronic controllers.
  • 24–660 V AC switching range for a broad selection of industrial AC loads.
  • 600 V AC rated output voltage for appropriate electrical installations.
  • Zero-crossing switching helps reduce electrical interference during turn-on.
  • Contactless semiconductor operation eliminates mechanical contact bounce.
  • Silent switching for machinery and equipment requiring frequent operation.
  • High switching endurance without mechanical output contact wear.
  • 800 A maximum peak current for 10 ms under specified conditions.
  • Hockey-puck-style housing with a folding protective screw cover.
  • Relay-style terminal arrangement with input and output terminals on opposite sides.
  • Panel or heat-sink mounting for flexible installation and thermal management.
  • IP20 protection rating for use within suitable electrical enclosures.

Key Features

  • Finder 77 Series industrial solid state relay.
  • Model: 77.F1.9.024.8650.
  • Single-phase AC load switching.
  • Output configuration: 1 normally open equivalent (SPST-NO).
  • Rated output current: 80 A.
  • Rated output voltage: 600 V AC.
  • Load switching voltage range: 24–660 V AC.
  • Nominal control voltage: 24 V DC.
  • Control input voltage range: 3–32 V DC.
  • Switching mode: Zero-crossing turn-on.
  • Maximum peak current: 800 A for 10 ms.
  • Operating frequency range: 47–400 Hz.
  • Ambient operating temperature: −30 to +80 °C.
  • Hockey-puck-style housing with folding screw cover.
  • Relay-style terminal layout with input and output connections on opposite sides.
  • Screw terminal connections.
  • Mounting: Control cabinet panel or suitable heat sink.
  • Protection classification: IP20.
  • RoHS-compliant construction.

High-Current Zero-Crossing Switching for Industrial AC Loads

The Finder 77.F1.9.024.8650 uses an electronic semiconductor output rather than conventional mechanical relay contacts. When a suitable 3–32 V DC control signal is applied, the relay initiates conduction near an AC voltage zero crossing, allowing current to flow through the connected load. When the control signal is removed, conduction ceases according to the semiconductor output's operating characteristics.

This zero-crossing switching method is particularly useful for suitable resistive loads, including industrial heating elements, where reduced switching interference and frequent operation are desirable. The relay's 80 A rating requires an appropriately selected heat sink and suitable installation conditions. Load characteristics, ambient temperature, ventilation, wiring and protective devices must be considered during design. As a semiconductor switching device, the relay may exhibit off-state leakage current and must not be used as a substitute for a mechanical isolating switch.

Typical Applications

  • Industrial electric heating and temperature control systems.
  • High-current resistive heating elements.
  • Industrial ovens, furnaces and drying equipment.
  • PLC-controlled AC load switching.
  • Manufacturing and process automation equipment.
  • Industrial lighting control applications.
  • Solenoid and contactor driver circuits.
  • Packaging and production machinery.
  • OEM industrial electrical control assemblies.
  • Applications requiring frequent, silent and contactless AC switching.

Technical Specifications

Tick the specs you need, then view products that match.

Device Type Solid State Relay
Terminal Type Screw
Mounting Type Panel
Manufacturer Finder
Series 77 Series
Manufacturer part number 77.F1.9.024.8650
Product type Single-phase solid state relay
Housing style Hockey puck
Number of switched phases 1
Output configuration 1 NO / SPST-NO
Rated output current 80 A
Rated output voltage 600 V AC
Load switching voltage range 24–660 V AC
Nominal control voltage 24 V DC
Control voltage range 3–32 V DC
Control input type DC
Switching characteristic Zero-crossing
Maximum peak current 800 A for 10 ms
Operating frequency 47–400 Hz
Ambient operating temperature −30 to +80 °C
Mounting method Panel or heat-sink mounting
Terminal type Screw terminals
Terminal arrangement Relay style, input and output on opposite sides
Protection rating IP20
Compliance RoHS
EAN / GTIN-13 8012823450735
Product category Solid State Relays

Frequently Asked Questions

What is the Finder 77.F1.9.024.8650 used for?

The Finder 77.F1.9.024.8650 is an 80 A single-phase solid state relay designed for contactless switching of suitable AC loads in industrial heating, automation and electrical control applications.

What control voltage does the Finder 77.F1.9.024.8650 require?

The relay accepts a 3–32 V DC control input, making it suitable for compatible low-voltage electronic controllers and PLC outputs.

What is the rated output current of this solid state relay?

The Finder 77.F1.9.024.8650 has an 80 A rated output current. This rating requires suitable heat-sink selection and compliance with the specified operating and thermal conditions.

What AC voltage range can the Finder 77.F1.9.024.8650 switch?

The relay is designed for a 24–660 V AC load switching range, with a rated output voltage of 600 V AC.

Does the Finder 77.F1.9.024.8650 use zero-crossing switching?

Yes. The relay uses zero-crossing turn-on switching, initiating conduction near the AC voltage zero crossing to help reduce electrical switching interference.

How many output poles does the Finder 77.F1.9.024.8650 have?

The relay provides one normally open semiconductor output path, equivalent to an SPST-NO contact arrangement, for single-phase AC load switching.

Can this solid state relay be controlled by a PLC?

Yes. Its 3–32 V DC input can be operated by a compatible PLC output or electronic controller, provided the controller meets the relay's electrical input requirements.

Does the Finder 77.F1.9.024.8650 require a heat sink?

Yes. A suitably rated heat sink is necessary for high-current operation. The allowable load current depends on the thermal resistance of the mounting arrangement and the installation's ambient temperature.

What is the maximum peak current rating of the Finder 77.F1.9.024.8650?

The relay has a specified maximum peak current of 800 A for 10 ms under the applicable test conditions. This is a short-duration peak rating, not a continuous operating current.

Can the Finder 77.F1.9.024.8650 be mounted on a control cabinet panel?

Yes. Its hockey-puck-style housing is suitable for mounting on control cabinet sheet metal or an appropriate heat sink, provided the installation meets the necessary thermal requirements.

Can the Finder 77.F1.9.024.8650 switch DC loads?

No. The Finder 77.F1.9.024.8650 has a DC control input but an AC semiconductor load output. It is intended for AC load switching rather than DC load switching.

Does this solid state relay provide safe electrical isolation when switched off?

No. Semiconductor outputs can exhibit off-state leakage current and do not provide the same isolation as a mechanical disconnecting device. Suitable electrical isolation and circuit protection must be provided separately.

Trusted by Industrial Automation and Electrical Engineering Professionals

Finder 77 Series solid state relays are designed for electrical engineers, industrial automation specialists, panel builders and machinery manufacturers requiring reliable high-current semiconductor switching, silent operation and practical integration into industrial heating, process control and automated production systems.