Finder 62.33.8.208.4006 – 62 Series Power relays.
The Finder 62.33.8.208.4006 is a 16 A industrial electromechanical power relay from the Finder 62 Series, designed for machinery control, industrial automation and electrical switching applications. Combining a three-pole changeover contact arrangement with a 208 V AC operating coil, this relay provides a practical solution for controlling multiple electrical circuits from a single control signal.
Featuring three changeover contacts (3 CO / 3PDT) and a plug-in connection arrangement, the Finder 62.33 is particularly suited to electrical control panels and industrial equipment where serviceability, flexible circuit switching and reliable electromagnetic operation are important.
The Finder 62.33 relay family offers a 16 A rated contact current, 250 V AC rated switching voltage and 4,000 VA AC1 resistive switching capacity. The .4006 variant belongs to the silver tin oxide (AgSnO₂) contact family, providing a contact material suited to appropriately rated industrial switching applications.
Product selection note: The exact 62.33.8.208.4006 suffix combination should be confirmed against Finder's variant-specific documentation before ordering. The principal electrical ratings below are based on the Finder 62.33 relay family and documented related configurations; special-option details are not assumed where they cannot be confirmed.
The Finder 62.33.8.208.4006 uses an electromagnetic operating mechanism to switch three mechanically linked changeover contacts. When the appropriate 208 V AC control voltage is applied to the coil, each common contact transfers from its normally closed terminal to its normally open terminal.
When the coil is de-energised, the relay automatically returns to its normal position. This monostable operation makes the relay suitable for electrical control applications where the switching state must follow the presence or absence of a control signal.
The 3 CO / 3PDT configuration allows three separate circuits to be switched simultaneously. This is useful for applications such as auxiliary machinery control, multiple control outputs, signal changeover and status indication.
Although all three contact sets operate together, they provide separate switching paths. Each connected circuit must remain within the applicable contact ratings, and the relay must not be used as a substitute for a safety-rated contactor or isolation device unless the complete application has been appropriately assessed.
The .4 contact material designation identifies a silver tin oxide (AgSnO₂) contact configuration. AgSnO₂ contacts are commonly used where resistance to contact welding and performance under demanding switching conditions are important.
These characteristics can make the relay suitable for appropriately rated industrial loads with challenging switching behaviour. However, contact material alone does not determine whether a relay can safely switch a particular motor, transformer, solenoid or electronic load.
For loads with high starting or inrush currents, the installer should consider the actual current waveform, switching frequency, power factor and required service life. The relay's 16 A nominal contact rating must not be confused with its short-duration peak-current capability.
The Finder 62.33 relay features Faston 187 terminals and can be installed using an appropriate Finder 92 Series relay socket. Socket mounting provides a convenient interface for panel wiring and can simplify relay replacement during maintenance.
Where a compatible DIN rail socket is selected, the relay can be incorporated into a standard industrial control cabinet. The relay itself does not clip directly onto the DIN rail.
The 208 V AC coil voltage is an important selection characteristic. It must be matched to the control circuit and should not be confused with the relay's 250 V AC rated contact switching voltage. A 208 V AC coil version should not be assumed interchangeable with 120 V or 230 V versions.
The exact .4006 special configuration, including any optional mechanical features, should be checked against the original Finder part marking or variant-specific datasheet before replacing an existing relay.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Terminal Type | Faston / flat-pin | |
| Switching Current (A) | 16 A | |
| Load Voltage | 400 V AC | |
| Mounting Type | Plug-in socket | |
| Manufacturer | Finder | |
| Series | 62 Series | |
| Manufacturer part number | 62.33.8.208.4006 | |
| Product type | Industrial electromechanical power relay | |
| Relay operation | Monostable / non-latching | |
| Number of poles | 3 | |
| Contact configuration | 3 CO (3PDT) | |
| Contact material | Silver tin oxide (AgSnO₂) | |
| Rated contact current | 16 A | |
| Maximum peak contact current | 30 A, standard 62.33 family rating | |
| Rated switching voltage | 250 V AC | |
| Maximum switching voltage | 400 V AC | |
| Rated resistive load (AC1) | 4,000 VA | |
| Rated inductive load (AC15) | 750 VA at 230 V AC | |
| Single-phase motor rating | 0.8 kW at 230 V AC, standard 62.33 family rating | |
| Minimum switching load | 1,000 mW (10 V / 10 mA), standard family rating | |
| Nominal coil voltage | 208 V AC | |
| Coil supply type | AC | |
| Nominal coil frequency | 50/60 Hz | |
| Standard AC coil consumption | 2.2 VA at 50 Hz | |
| Standard AC coil operating range | 80–110% of nominal voltage | |
| Approximate coil operating range | 166.4–228.8 V AC, subject to variant confirmation | |
| Coil-to-contact impulse withstand voltage | 6 kV (1.2/50 µs) | |
| Dielectric strength between open contacts | 1,500 V AC, standard changeover configuration | |
| Standard mechanical life | 10 million operations with AC coil | |
| Electrical life at rated AC1 load | 100,000 operations | |
| Operating temperature | −40 to +70 °C, standard relay family | |
| Terminal type | Faston 187 quick-connect | |
| Terminal dimensions | 4.8 × 0.5 mm | |
| Mounting type | Plug-in / compatible socket | |
| Compatible socket family | Finder 92 Series | |
| Approximate relay body dimensions | 35.8 × 38.2 × 49.1 mm | |
| Typical application | Industrial automation and three-pole electrical switching |
The Finder 62.33.8.208.4006 is an industrial electromechanical power relay used for machinery control, industrial automation and multi-circuit electrical switching. It features three changeover contacts and a 208 V AC coil.
The part number specifies a 208 V AC nominal coil. The control circuit must provide a compatible AC supply. The standard 62.33 AC coil operating range is 80–110% of nominal voltage, but the exact variant should be checked before installation.
3 CO means three changeover contacts, also described as 3PDT. Each pole has a common, normally open and normally closed terminal. All three poles change state together when the relay coil is energised.
The .4 contact material designation indicates silver tin oxide (AgSnO₂). This contact material is commonly selected for industrial switching applications where demanding load characteristics and contact-welding resistance are important.
The relay uses a plug-in mounting arrangement. It can be installed on a DIN rail when fitted into a compatible Finder 92 Series DIN rail socket. The socket must be selected to match the relay's terminal arrangement and electrical ratings.
Finder 62 Series power relays provide versatile electromechanical switching solutions for industrial machinery, automation equipment and electrical control panels. With three-pole changeover operation, robust contact ratings and convenient plug-in mounting, the range supports electrical engineers, machine builders, panel manufacturers and maintenance professionals.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.