Finder 62.33.8.125.0040 – 62 Series Power relays.
The Finder 62.33.8.125.0040 is a 125 V AC electromagnetic power relay from the Finder 62 Series, designed for industrial automation, electrical control panels and power switching applications. Featuring three changeover contacts (3PDT / 3 CO) rated at 16 A, it provides flexible switching of multiple circuits through a single relay coil.
Designed for practical installation and maintenance, the Finder 62.33.8.125.0040 incorporates a lockable test button and mechanical status indicator. These features support manual functional testing and visual confirmation of the relay mechanism's operating position during commissioning, inspection and troubleshooting.
The relay combines a 125 V AC operating coil with a plug-in/Faston 187 connection arrangement. Its three independent changeover contacts make it suitable for electrical interlocking, machinery control, industrial signalling and auxiliary power switching. The relay can be installed using an appropriately selected Finder 92 Series socket or a compatible direct connection arrangement.
The Finder 62.33.8.125.0040 uses an electromagnetic coil to operate three independent changeover contact sets. When the 125 V AC coil is energised, the relay transfers its contacts from their normal positions to their operated positions. When the coil supply is removed, the spring-return mechanism restores the contacts to their normal state.
The 3PDT configuration enables three separate circuits to be controlled using one electrical signal, making the relay useful for interlocking, signalling and auxiliary equipment control. Its lockable test button allows manual operation during functional testing, while the mechanical indicator provides a visual reference for the relay mechanism's position.
With 16 A rated contacts, the relay supports a range of industrial switching duties. The connected load must remain within the manufacturer's ratings for the relevant voltage and utilisation category. Inductive, motor and DC loads may require different switching limits from resistive AC loads.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Terminal Type | Faston / flat-pin | |
| Switching Current (A) | 16 A | |
| Load Voltage | 400 V AC | |
| Manufacturer | Finder | |
| Series | 62 Series | |
| Model | 62.33.8.125.0040 | |
| Product type | Electromagnetic power relay | |
| Contact configuration | 3PDT / 3 CO | |
| Number of poles | 3 | |
| Number of changeover contacts | 3 | |
| Rated contact current | 16 A | |
| Rated contact voltage | 250 V AC | |
| Maximum switching voltage | 400 V AC | |
| Rated switching capacity (AC1) | 4000 VA | |
| Nominal coil voltage | 125 V AC | |
| Coil supply type | AC | |
| Operating principle | Electromagnetic, monostable | |
| Connection type | Plug-in / Faston 187 | |
| Faston terminal dimensions | 4.8 × 0.5 mm | |
| Compatible socket family | Finder 92 Series, subject to socket model | |
| Test function | Lockable test button | |
| Status indication | Mechanical indicator | |
| Contact arrangement | Three independent changeover contact sets | |
| Application | Industrial electrical control and power switching |
The Finder 62.33.8.125.0040 is an electromagnetic power relay used to switch multiple electrical circuits in industrial automation, machinery control, electrical panels and auxiliary power applications.
This model is identified by a 125 V AC nominal coil voltage. The coil supply must match the relay's specified AC operating requirements.
The relay features three changeover contacts (3 CO), also known as a 3PDT configuration. The three contact sets operate together when the relay coil is energised.
The Finder 62.33.8.125.0040 has a 16 A rated contact current. Actual load suitability depends on the switching voltage, load characteristics and applicable manufacturer ratings.
Yes. The relay includes a lockable test button for manually operating its contacts during commissioning, inspection and maintenance. Testing should only be performed under appropriate electrical safety conditions.
Yes. The .0040 configuration includes a mechanical status indicator that provides visual confirmation of the relay mechanism's operating position.
The .0040 configuration is specified with a lockable test button and mechanical indication. An integrated LED should not be assumed for this version.
The relay supports plug-in mounting with appropriately selected Finder 92 Series sockets and has Faston 187 terminals measuring 4.8 × 0.5 mm for compatible connection arrangements.
No. The Finder 62.33.8.125.0040 is identified as an AC-coil version. A suitable DC-coil relay should be selected where the control supply is DC.
The relay can switch suitable DC loads when the contact voltage, current and load characteristics remain within the manufacturer's specified DC switching limits. The 16 A AC contact rating must not automatically be applied to DC loads.
Finder 62 Series power relays are designed for industrial electrical control and power switching applications. The Finder 62.33.8.125.0040 combines three 16 A changeover contacts, a 125 V AC coil, a lockable test button and a mechanical indicator in a practical plug-in/Faston design for industrial switching and maintenance.