Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 50.14.9.024.4220 – 50 Series Relays with forcibly guided contacts.
£19.04
The Finder 50.14.9.024.4220 is a compact and reliable 8 A, four-pole safety relay with a 24 V DC coil, designed for safety-related switching and monitoring circuits in industrial automation and machinery control systems. As part of the Finder Series 50 forcibly guided contact relay range, it incorporates mechanically linked contacts that support contact-state monitoring in appropriately designed safety circuits.
Featuring two normally open (NO) and two normally closed (NC) contacts, the Finder 50.14.9.024.4220 uses forcibly guided contact technology conforming to EN 61810-3 Type A. This arrangement prevents normally open and normally closed contacts from being closed simultaneously, including under specified contact fault conditions, supporting fault detection through external monitoring circuitry.
With an 8 A rated contact current, 24 V DC operating coil and through-hole PCB mounting, this relay is well suited to safety interface boards, industrial control equipment and machinery safety systems. Its RT III wash-tight construction, silver tin oxide contacts and compact dimensions make it suitable for integration into electronic safety control assemblies.
The Finder 50.14.9.024.4220 uses a mechanically linked contact mechanism to provide coordinated switching between its two normally open and two normally closed contacts. When the 24 V DC coil is energised, the normally open contacts close while the normally closed contacts open. When the coil supply is removed, the contacts return to their normal positions.
Unlike conventional electromechanical relays, forcibly guided contact relays are constructed so that normally open and normally closed contacts cannot occupy their closed positions simultaneously under the fault conditions defined by the applicable standard. This characteristic enables external safety monitoring circuits to detect certain contact failures, including welded contacts. The Finder Series 50 is therefore suitable for integration into appropriately engineered machinery safety systems, emergency-stop monitoring interfaces and safety-related control assemblies. The relay itself is a component and must be incorporated into a correctly designed and validated safety circuit to achieve the required safety performance.
Tick the specs you need, then view products that match.
| Device Type | Positively Guided Relay | |
|---|---|---|
| Timing Function | None (instantaneous) | |
| Load Voltage | 400 V AC | |
| Mounting Type | PCB | |
| Terminal Type | PCB / pins | |
| Switching Current (A) | 8 A | |
| Manufacturer | Finder | |
| Series | 50 Series | |
| Model | 50.14.9.024.4220 | |
| Product type | Forcibly guided contact safety relay | |
| Relay technology | Electromechanical | |
| Relay operation | Monostable, non-latching | |
| Contact arrangement | 2 NO + 2 NC | |
| Number of poles | 4 | |
| Rated contact current | 8 A | |
| Maximum peak contact current | 15 A | |
| Nominal contact voltage | 250 V AC | |
| Maximum switching voltage | 400 V AC | |
| Rated resistive switching load (AC1) | 2000 VA | |
| Nominal coil voltage | 24 V DC | |
| Coil supply type | DC | |
| Nominal coil consumption | 0.8 W | |
| Nominal coil resistance | 720 Ω | |
| Nominal coil current | 33.3 mA | |
| Coil operating voltage range | 18–28.8 V DC | |
| Contact material | Silver tin oxide (AgSnO₂) | |
| Mechanical endurance | 10 million operations | |
| Electrical endurance | 100,000 operations at rated resistive load | |
| Impulse withstand voltage between coil and contacts | 6 kV (1.2/50 µs) | |
| Clearance and creepage between coil and contacts | 8 mm | |
| Dielectric strength between coil and contacts | 1500 V AC | |
| Operating temperature | −40 to +70 °C | |
| Protection category | RT III, wash-tight | |
| Mounting type | Through-hole PCB mounting | |
| Terminal type | PCB pins | |
| Terminal pitch | 5 mm | |
| Dimensions (L × W × H) | 40 × 13 × 16.5 mm | |
| Contact standard | EN 61810-3 Type A (formerly EN 50205) | |
| Contact materials | Cadmium-free |
The Finder 50.14.9.024.4220 is a four-pole forcibly guided contact relay designed for safety-related switching and monitoring applications in industrial automation, machinery control and electronic safety interface equipment.
This relay operates using a 24 V DC nominal coil supply, with a nominal coil consumption of 0.8 W and a nominal coil resistance of 720 Ω.
The Finder 50.14.9.024.4220 has four forcibly guided contacts arranged as 2 normally open (NO) and 2 normally closed (NC). This arrangement supports switching and external contact-state monitoring.
The relay has an 8 A rated contact current and a nominal contact voltage of 250 V AC. The permissible switching load depends on the connected equipment and applicable operating conditions.
Forcibly guided contacts are mechanically linked normally open and normally closed contacts designed so that they cannot be closed simultaneously, including under specified contact fault conditions. This enables suitable external monitoring circuitry to detect certain contact failures.
Yes. The Finder Series 50 forcibly guided contact relay is designed according to EN 61810-3 Type A, the standard previously referenced as EN 50205.
Yes. The relay is designed for through-hole PCB mounting, making it suitable for integration into electronic safety controllers, industrial monitoring equipment and OEM control assemblies.
Yes. The relay can be incorporated into appropriately designed emergency-stop monitoring and safety control circuits. However, the relay alone does not constitute a complete certified emergency-stop system, and the overall safety function must be designed and validated according to the applicable safety requirements.
The RT III wash-tight construction provides protection suitable for specified PCB assembly and washing processes. Manufacturing and cleaning procedures should follow Finder's applicable processing instructions.
Finder Series 50 forcibly guided contact relays are designed for dependable switching and contact monitoring in industrial machinery, electronic safety interfaces and automation control equipment. With EN 61810-3 Type A contact construction, compact PCB mounting and reliable electromechanical operation, the Finder 50.14.9.024.4220 provides a practical component for safety engineers, control panel designers and OEM equipment manufacturers developing safety-related electrical systems.