Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 48P681201060SPA (48.P6.8.120.1060SPA) industrial interface relay module with a 120 V AC coil, 16 A single changeover contact, push-in terminals, integrated supply indication, EMC coil suppression and SPA plastic retaining clip for DIN rail-mounted industrial automation and electrical control applications.
The Finder 48P681201060SPA, also written as 48.P6.8.120.1060SPA, is a compact 16 A industrial electromechanical interface relay module designed for reliable electrical switching in industrial automation, control panels and PLC interface applications. Part of the Finder 48 Series, this module combines a 120 V AC operating coil, a single changeover contact and convenient push-in terminals in a slimline DIN rail-mounted assembly.
The Finder 48.P6 interface relay features a single-pole double-throw (SPDT / 1 CO) contact configuration, allowing one control signal to switch between normally open and normally closed electrical connections. Its 16 A rated contact current and silver-nickel (AgNi) contacts make it suitable for a range of industrial switching applications, subject to the manufacturer's load ratings and wiring requirements.
With a compact 15.8 mm module width, push-in terminal technology, integrated supply status indication and EMC coil suppression, the Finder 48.P6.8.120.1060SPA offers a practical solution for control panel builders and industrial maintenance engineers. The SPA configuration includes a plastic retaining clip with an instant relay-ejection feature, helping simplify relay replacement and servicing.
The Finder 48.P6.8.120.1060SPA is designed to provide an electrically isolated switching interface between a 120 V AC control circuit and a separate electrical load. When the relay coil is energised, the internal electromagnetic mechanism transfers the common contact from the normally closed position to the normally open position. Removing the control voltage allows the relay to return to its original state.
The module's push-in terminal system helps streamline wiring during electrical panel manufacture and maintenance. Its 15.8 mm width allows multiple interface relays to be installed efficiently on a standard DIN rail, while the integrated supply indication helps technicians identify when the control circuit is energised.
The SPA plastic retaining clip provides an instant relay-ejection function, allowing the plug-in relay to be removed more conveniently during servicing. The module also incorporates an EMC coil suppression arrangement to help limit electrical disturbances associated with switching. For load currents exceeding 10 A, the specified contact terminals must be connected in parallel as directed by Finder.
Tick the specs you need, then view products that match.
| Device Type | Interface Relay | |
|---|---|---|
| Terminal Type | Push-in | |
| Switching Current (A) | 16 A | |
| Load Voltage | 400 V AC | |
| Mounting Type | DIN rail | |
| Manufacturer | Finder | |
| Manufacturer part number | 48.P6.8.120.1060SPA | |
| Alternative part number | 48P681201060SPA | |
| Series | 48 Series | |
| Interface type | 48.P6 | |
| Product type | Electromechanical interface relay module | |
| Nominal coil voltage | 120 V AC | |
| Coil frequency | 50/60 Hz | |
| Coil type | AC electromagnetic | |
| Rated AC coil consumption | 1.2 VA at 50 Hz | |
| Nominal coil current | 11.8 mA at 50 Hz | |
| Minimum specified coil operating voltage | 96 V AC | |
| Maximum specified coil operating voltage | 132 V AC | |
| Coil operating range | 0.8–1.1 × nominal voltage | |
| AC holding voltage | 0.8 × nominal voltage | |
| AC must drop-out voltage | 0.2 × nominal voltage | |
| Relay operating principle | Monostable electromagnetic switching | |
| Contact configuration | Single-pole double-throw (SPDT / 1 CO) | |
| Number of poles | 1 | |
| Number of changeover contacts | 1 | |
| Contact material | Silver nickel (AgNi) | |
| Rated contact current | 16 A | |
| Maximum peak contact current | 30 A | |
| Rated contact voltage | 250 V AC | |
| Maximum switching voltage | 400 V AC | |
| Rated resistive switching load (AC1) | 4,000 VA | |
| Rated switching load (AC15 at 230 V AC) | 1,000 VA | |
| Single-phase motor rating at 230 V AC | 0.55 kW | |
| DC1 breaking capacity at 24 V DC | 16 A | |
| DC1 breaking capacity at 110 V DC | 0.6 A | |
| DC1 breaking capacity at 220 V DC | 0.25 A | |
| Minimum switching load | 500 mW (10 V / 5 mA) | |
| Mechanical life | 10 million cycles | |
| Electrical life at rated AC1 load | 100,000 cycles | |
| Nominal operate time | 7 ms for AC coil versions | |
| Nominal release time | 14 ms for AC coil versions | |
| Coil-to-contact impulse withstand voltage | 6 kV (1.2/50 µs) | |
| Coil-to-contact insulation distance | 8 mm | |
| Dielectric strength between open contacts | 1,000 V AC | |
| Operating temperature | −40 to +70 °C | |
| Protection category | IP20 | |
| Mounting type | DIN rail | |
| DIN rail standard | EN 60715, 35 mm | |
| Terminal type | Push-in | |
| Module width | 15.8 mm | |
| Supply indication | Integrated status indicator | |
| Coil protection | Integrated EMC suppression module | |
| Retaining clip | SPA plastic clip with instant relay ejection | |
| Relay construction | Replaceable plug-in relay and socket assembly | |
| High-current wiring requirement | For currents above 10 A, contact terminals 21 and 11, 24 and 14, and 22 and 12 must be connected in parallel according to Finder's wiring instructions. | |
| Application category | Industrial automation, PLC interfacing and electrical control |
The Finder 48P681201060SPA is an industrial interface relay module used to switch electrical loads through a separate control circuit. Typical applications include PLC interfacing, industrial automation, electrical control panels, machinery control and auxiliary electrical switching.
The Finder 48.P6.8.120.1060SPA uses a 120 V AC coil rated for 50/60 Hz operation. The specified operating voltage range is 96–132 V AC, and the nominal coil consumption is 1.2 VA at 50 Hz.
The relay has a 16 A rated contact current and a 250 V AC rated contact voltage, with a rated AC1 resistive switching capacity of 4,000 VA. For currents above 10 A, Finder requires the relevant contact terminals to be connected in parallel according to the manufacturer's wiring instructions.
The SPA suffix identifies the version supplied with a plastic retaining clip featuring instant relay ejection. This helps technicians remove and replace the plug-in relay during maintenance. Finder also offers SMA variants with a metal retaining clip.
The main difference is the nominal coil voltage. The 48.P6.8.120.1060SPA uses a 120 V AC coil, while the 48.P6.8.024.1060SPA uses a 24 V AC coil. Both belong to the Finder 48.P6 interface relay family and offer a 16 A single changeover contact, push-in terminals and DIN rail mounting. The coil voltages are not interchangeable.
Finder 48 Series interface relays provide dependable electrical switching for automation engineers, control panel builders and industrial maintenance teams. The Finder 48.P6.8.120.1060SPA combines a 120 V AC operating coil, 16 A changeover contact, push-in terminal technology and a convenient SPA relay-ejection clip for efficient integration into industrial control systems.