Finder 7S.14.8.120.4310 is a DIN rail-mounted modular safety relay with forcibly guided 3 NO and 1 NC contacts, a 120 V AC coil, 6 A contact rating, spring-loaded push-in terminals and an integrated LED status indicator.
£86.80
The Finder 7S.14.8.120.4310 is a modular industrial safety relay featuring forcibly guided contacts, a 120 V AC coil and four contacts arranged as 3 normally open (NO) and 1 normally closed (NC). Part of the Finder 7S Series, this relay is designed for safety-related control circuits requiring mechanically linked contacts and dependable switching performance.
With a 6 A contact current rating and a 250 V AC nominal switching voltage, the Finder 7S.14.8.120.4310 is suitable for industrial automation, machinery control and safety interface applications. Its forcibly guided contact construction supports the detection of certain contact faults when used within a correctly designed monitoring circuit.
The relay combines spring-loaded push-in terminals, an integrated LED indicator and a compact 22.5 mm-wide DIN rail-mounted housing. These features simplify electrical panel installation, provide visual indication of relay energisation and support efficient use of control cabinet space.
The Finder 7S.14.8.120.4310 incorporates forcibly guided contacts, a mechanical arrangement that prevents normally open and normally closed contacts from simultaneously occupying certain contradictory states. This feature supports contact monitoring and the detection of specific contact faults when the relay is integrated into an appropriately designed safety-related control circuit.
When the 120 V AC coil is energised, the relay operates its three normally open contacts and one normally closed contact. The three NO contacts can be used for appropriately rated switching functions, while the NC contact can provide feedback to a compatible monitoring circuit. The exact arrangement and achievable diagnostic coverage depend on the complete system design.
The relay features 6 A silver tin oxide contacts with a nominal switching voltage of 250 V AC. Its specified 12 ms operate time and 10 ms release time support responsive control circuit operation.
For installation, the Finder 7S.14.8.120.4310 uses spring-loaded push-in terminals and a 22.5 mm-wide DIN rail-mounted housing. The integrated LED indicator allows operators and maintenance engineers to check the relay's energisation state without additional test equipment.
Safety consideration: The Finder 7S.14.8.120.4310 is a relay with forcibly guided contacts, not a complete safety controller. The safety category, performance level or safety integrity level achieved by an installation depends on the complete circuit architecture, diagnostic measures, component selection and validation. The relay must be incorporated into a suitably engineered safety system where required.
Tick the specs you need, then view products that match.
| Device Type | Positively Guided Relay | |
|---|---|---|
| Terminal Type | Push-in | |
| Mounting Type | DIN rail | |
| Switching Current (A) | 6 A | |
| Manufacturer | Finder | |
| Series | 7S Series | |
| Model | 7S.14.8.120.4310 | |
| Manufacturer part number | 7S.14.8.120.4310 | |
| Product type | Modular relay with forcibly guided contacts | |
| Product category | Safety Relays | |
| Contact arrangement | 4PST, 3 NO + 1 NC | |
| Number of contacts | 4 | |
| Normally open contacts | 3 | |
| Normally closed contacts | 1 | |
| Contact mechanism | Forcibly guided | |
| Rated contact current | 6 A | |
| Nominal switching voltage | 250 V AC | |
| Rated switching capacity | 1,500 VA | |
| Contact material | Silver tin oxide (AgSnO) | |
| Nominal coil voltage | 120 V AC | |
| Coil current | 10.2 mA | |
| Coil resistance | 11.8 kΩ | |
| Minimum operate voltage | 93 V AC | |
| Must-release voltage | 12 V AC | |
| Operate time | 12 ms | |
| Release time | 10 ms | |
| Terminal type | Spring-loaded push-in terminals | |
| Mounting method | DIN rail | |
| Housing width | 22.5 mm | |
| Housing height | 86.2 mm | |
| Housing depth | 100.3 mm | |
| Status indication | Integrated LED | |
| Mechanical durability | 10,000,000 operations | |
| Electrical durability | 100,000 operations | |
| Rated insulation voltage | 250 V | |
| Pollution degree | 2 | |
| Operating ambient temperature | −40 to +70 °C | |
| Ingress protection | IP20 | |
| Country of origin | Italy |
The Finder 7S.14.8.120.4310 is a modular relay with forcibly guided contacts, designed for industrial control and safety-related monitoring circuits requiring a 120 V AC coil and a 3 NO + 1 NC contact configuration.
Forcibly guided contacts are mechanically linked so that the normally open and normally closed contacts cannot simultaneously assume certain contradictory states. This construction supports contact-state monitoring and fault detection within appropriately designed safety circuits.
The relay has four contacts, comprising three normally open (NO) contacts and one normally closed (NC) contact.
The Finder 7S.14.8.120.4310 has a 120 V AC nominal coil voltage.
The relay has a 6 A rated contact current and a nominal switching voltage of 250 V AC.
The relay uses silver tin oxide (AgSnO) contacts for industrial switching applications.
Yes. The relay includes an integrated LED indicator that provides visual indication of coil energisation.
The relay uses spring-loaded push-in terminals, providing screwless electrical connections for installation in control panels.
The relay is designed for DIN rail mounting and has a compact housing measuring approximately 22.5 mm wide, 86.2 mm high and 100.3 mm deep.
The Finder 7S.14.8.120.4310 has a specified 12 ms operate time and 10 ms release time.
Both relays belong to the Finder 7S Series and use a 120 V AC coil with forcibly guided contacts. The 7S.14.8.120.4310 has a 3 NO + 1 NC contact arrangement, while the 7S.14.8.120.4220 has a 2 NO + 2 NC arrangement.
The Finder 7S.14.8.120.4310 is specified for operation between −40 and +70 °C.
The relay has a specified mechanical durability of 10 million operations.
No. The Finder 7S.14.8.120.4310 is a relay with forcibly guided contacts, not a complete safety controller. It must be incorporated into a properly designed and validated safety-related control system where required.
It can be used as a component within an appropriately designed emergency-stop control system. The complete safety circuit must be assessed and validated against the applicable machinery safety requirements.
The relay has an IP20 ingress protection rating and should be installed within an appropriately rated electrical enclosure. It is not intended for unprotected outdoor mounting.
Finder 7S Series relays provide practical switching solutions for industrial automation and safety-related control systems. Combining forcibly guided contacts, a 3 NO + 1 NC contact arrangement, 120 V AC coil, 6 A contact rating, silver tin oxide contacts, integrated LED indication and spring-loaded push-in terminals, the Finder 7S.14.8.120.4310 supports industrial automation engineers, machinery manufacturers, electrical panel builders and maintenance professionals requiring dependable relay switching and contact monitoring.