Finder 7S.14.8.120.4220 is a DIN rail-mounted modular safety relay with forcibly guided 2 NO and 2 NC contacts, a 120 V AC coil, 6 A contact rating, spring-loaded terminals and an integrated LED status indicator.
£92.00
The Finder 7S.14.8.120.4220 is a modular safety relay featuring forcibly guided contacts, a 120 V AC coil and four contacts arranged as 2 normally open (NO) and 2 normally closed (NC). Part of the Finder 7S Series, this industrial relay is designed for applications requiring reliable switching and mechanically linked contact operation in safety-related control circuits.
With a 6 A contact current rating and a nominal switching voltage of 250 V AC, the Finder 7S.14.8.120.4220 provides dependable control and feedback switching. Its forcibly guided contact mechanism helps support contact-state monitoring and fault detection when incorporated into an appropriately designed safety control system.
The relay combines spring-loaded push-in terminals, 35 mm DIN rail mounting and an integrated LED status indicator in a compact 22.5 mm-wide enclosure. This makes it suitable for industrial automation panels, machinery control systems, safety interface circuits and electrical installations where space-efficient relay mounting and dependable contact operation are important.
The Finder 7S.14.8.120.4220 uses a forcibly guided contact mechanism in which the normally open and normally closed contacts are mechanically linked. This arrangement is particularly useful in safety-related control systems because it supports monitoring of contact states and the detection of certain contact faults when the relay is incorporated into a suitably designed diagnostic circuit.
When the 120 V AC coil is energised, the relay changes the state of its two normally open and two normally closed contacts. The integrated LED provides visual indication of coil energisation, while the four-pole contact arrangement allows separate switching and feedback functions within the applicable electrical ratings.
The relay's silver tin oxide contacts provide a rated switching current of 6 A at a nominal contact switching voltage of 250 V AC. Its 12 ms operate time and 10 ms release time support responsive operation in industrial control circuits.
For installation, the Finder 7S.14.8.120.4220 features a compact DIN rail-mounted housing and spring-loaded push-in terminals. These features simplify panel wiring and allow the relay to be incorporated into machinery control cabinets, automation panels and electrical distribution enclosures.
Safety consideration: Although this relay features forcibly guided contacts, it is not a complete safety controller or standalone safety monitoring system. The achievable safety performance level or category depends on the complete circuit architecture, diagnostics, component selection and validation. A suitably qualified engineer should assess the application against the relevant machinery safety standards.
Tick the specs you need, then view products that match.
| Device Type | Positively Guided Relay | |
|---|---|---|
| Terminal Type | Push-in | |
| Mounting Type | DIN rail | |
| Switching Current (A) | 6 A | |
| Manufacturer | Finder | |
| Series | 7S Series | |
| Model | 7S.14.8.120.4220 | |
| Manufacturer part number | 7S.14.8.120.4220 | |
| Product type | Modular relay with forcibly guided contacts | |
| Product category | Safety relays | |
| Contact arrangement | 4PST, 2 NO + 2 NC | |
| Number of contacts | 4 | |
| Normally open contacts | 2 | |
| Normally closed contacts | 2 | |
| Contact mechanism | Forcibly guided | |
| Rated contact current | 6 A | |
| Nominal switching voltage | 250 V AC | |
| Rated switching capacity | 1,500 VA | |
| Contact material | Silver tin oxide (AgSnO) | |
| Nominal coil voltage | 120 V AC | |
| Coil current | 10.2 mA | |
| Coil resistance | 11.8 kΩ | |
| Minimum operate voltage | 93 V AC | |
| Release voltage | 12 V AC | |
| Operate time | 12 ms | |
| Release time | 10 ms | |
| Terminal type | Spring-loaded push-in terminals | |
| Mounting method | DIN rail | |
| Housing width | 22.5 mm | |
| Housing height | 86.2 mm | |
| Housing depth | 100.3 mm | |
| Status indication | Integrated LED | |
| Mechanical durability | 10,000,000 operations | |
| Electrical durability | 100,000 operations | |
| Rated insulation voltage | 250 V | |
| Pollution degree | 2 | |
| Operating ambient temperature | −40 to +70 °C | |
| Ingress protection | IP20 | |
| EAN | 8012823420455 |
The Finder 7S.14.8.120.4220 is a modular relay with forcibly guided contacts, designed for industrial control and safety-related monitoring circuits requiring a 120 V AC coil and 2 normally open plus 2 normally closed contacts.
Forcibly guided contacts are mechanically linked so that the normally open and normally closed contacts cannot simultaneously assume certain contradictory states. This construction supports contact-state monitoring and fault detection within appropriately designed safety circuits.
The relay has four contacts, comprising 2 normally open (NO) and 2 normally closed (NC) contacts.
The Finder 7S.14.8.120.4220 has a 120 V AC nominal coil voltage.
The relay has a 6 A contact current rating, with a nominal switching voltage of 250 V AC.
The Finder 7S.14.8.120.4220 uses silver tin oxide (AgSnO) contacts.
Yes. The relay includes an integrated LED indicator for visual indication of relay energisation.
The relay uses spring-loaded push-in terminals, providing a screwless wiring connection for installation in electrical control panels.
The relay is designed for DIN rail mounting and has a compact housing measuring approximately 22.5 mm wide, 86.2 mm high and 100.3 mm deep.
The Finder 7S.14.8.120.4220 has a specified 12 ms operate time and 10 ms release time.
The relay is specified for operation between −40 and +70 °C.
The Finder 7S.14.8.120.4220 has a specified mechanical durability of 10 million operations.
No. The Finder 7S.14.8.120.4220 is a relay with forcibly guided contacts, not a complete safety controller. It must be incorporated into a properly designed and validated safety-related control system where required.
It can be used as a component within an appropriately designed emergency-stop control system. The complete safety circuit must be assessed and validated against the applicable machinery safety requirements.
The Finder 7S.14.8.120.4220 has an IP20 ingress protection rating and should be installed within an appropriately rated electrical enclosure. It is not intended for unprotected outdoor mounting.
Finder 7S Series modular relays provide dependable switching solutions for industrial control and safety-related applications. Combining forcibly guided contacts, a 2 NO + 2 NC contact arrangement, 120 V AC coil, 6 A contact rating, silver tin oxide contacts, integrated LED indication and spring-loaded push-in terminals, the Finder 7S.14.8.120.4220 is suited to industrial automation engineers, machine builders, electrical panel manufacturers and maintenance professionals requiring reliable relay switching and contact monitoring.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.