Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 7S.12.9.024.5110T Series 7S safety-related relay module with forcibly guided contacts. The documented 7S.12.9.024.5110 base model features a 24 V DC coil, 1 NO + 1 NC contacts, 6 A contact rating, screwless spring-clamp terminals and DIN rail mounting. T-suffix-specific characteristics require manufacturer confirmation.
£49.08
The Finder 7S.12.9.024.5110T is a 24 V DC safety relay module with forcibly guided contacts, designed for integration into industrial machinery and safety-related electrical control systems. Part of the Finder Series 7S, this compact relay module is intended for applications requiring reliable switching, contact monitoring and fault detection within an appropriately designed safety circuit.
The module belongs to Finder's family of Class A forcibly guided contact relays. This technology mechanically links normally open and normally closed contacts, allowing a suitable monitoring circuit to detect certain contact faults, including welded contacts. It is particularly valuable in machinery control applications where feedback from switching devices forms part of the safety system.
The 7S.12 family features a 1 normally open (NO) + 1 normally closed (NC) contact arrangement, a 6 A contact rating, a 24 V DC coil and screwless spring-clamp connections. Its slim DIN rail-mounted construction makes it suitable for installation in industrial automation cabinets and machinery control panels.
Product identification note: Published technical information is available for the closely related Finder 7S.12.9.024.5110. The exact additional T suffix on 7S.12.9.024.5110T has not been independently confirmed. The specifications below describe the documented base model and Series 7S characteristics; any suffix-specific differences should be checked against the manufacturer's documentation before ordering or installation.
Reference: The following electrical and mechanical characteristics are documented for the Finder 7S.12.9.024.5110 base model. Confirmation is required that they also apply unchanged to the 7S.12.9.024.5110T variant.
The principal benefit of the Finder Series 7S is its forcibly guided relay contact construction. In a conventional relay, normally open and normally closed contacts may not provide the same mechanically constrained fault behaviour. With forcibly guided contacts, the contact sets are linked so that they cannot simultaneously reach their closed positions under specified fault conditions.
For example, if a normally open contact becomes welded closed, the mechanically linked normally closed contact is prevented from closing normally. An appropriately designed monitoring circuit can detect this discrepancy and use it to inhibit a machine restart or initiate another defined safety response.
The 1 NO + 1 NC configuration provides a straightforward arrangement for switching and feedback functions. The normally open contact may be used as part of the controlled circuit, while the normally closed contact can provide feedback to suitable monitoring equipment, subject to the requirements of the overall safety design.
Forcibly guided contact construction does not make the relay a complete safety controller. The complete safety function must incorporate appropriate monitoring, fault detection, redundancy where necessary and system-level validation.
The documented Finder 7S.12.9.024.5110 base model operates with a 24 V DC nominal coil, making it suitable for integration into industrial control systems using this common control voltage.
Its 6 A rated contact current and 250 V AC nominal switching voltage support a range of appropriately rated electrical loads. The permitted switching duty depends on the type of load, operating conditions and the relevant manufacturer contact ratings.
The relay's gold-plated silver-nickel contacts combine established industrial relay contact materials with a plated surface. This construction supports dependable switching performance when used within the specified electrical limits.
Documented operating characteristics for the base model include an approximate 7 ms operate time and 11 ms release time. These values describe the relay itself and must not be confused with the overall response or stopping time of a complete machinery safety system.
The Finder 7S.12 family is designed for installation in electrical control cabinets using a standard 35 mm DIN rail. Its compact 22.5 mm nominal width makes it a practical choice for panels containing multiple relays, safety monitoring devices and industrial automation components.
Spring-clamp terminals provide a convenient alternative to traditional screw terminals. These connections help simplify wiring and support secure conductor retention when installed using the manufacturer's approved conductor types and preparation requirements.
The documented base model has an IP20 protection rating and should be installed inside an appropriate electrical enclosure. Its operating temperature range of −40 to +70 °C supports a wide variety of industrial applications.
Before installation, verify the exact terminal arrangement, wiring diagram, coil polarity requirements and any characteristics associated with the T suffix against the product marking and Finder documentation.
Forcibly guided relays are frequently used in machinery safety circuits because their mechanically linked contacts can support diagnostic monitoring. However, the safety performance of an installation depends on the complete circuit architecture rather than the relay alone.
When designing a safety-related control system, engineers should consider the required Performance Level or Safety Integrity Level, diagnostic coverage, common-cause failures, contact loading and the behaviour of the system when a fault occurs.
The relay should be integrated with suitable safety controllers, monitoring circuits or other protective equipment where required. Emergency-stop systems, guard interlocks and machine safety functions must be assessed and validated against the relevant application standards.
Important: The Finder 7S.12.9.024.5110T should not be treated as a standalone emergency-stop controller or as independently providing a particular SIL or Performance Level.
Tick the specs you need, then view products that match.
| Device Type | Positively Guided Relay | |
|---|---|---|
| Switching Current (A) | 6 A | |
| Mounting Type | DIN rail |
The Finder 7S.12.9.024.5110T is a Series 7S relay module intended for safety-related industrial control applications requiring forcibly guided contacts. The precise characteristics of the T-suffix version should be confirmed with Finder.
The documented Finder 7S.12.9.024.5110 base model uses a 24 V DC coil. The exact T-suffix variant should be checked against the manufacturer's product documentation before connection.
The Finder 7S.12 base model features 1 normally open (NO) and 1 normally closed (NC) contact, with the contacts mechanically linked through a forcibly guided arrangement.
Forcibly guided contacts are mechanically linked normally open and normally closed contacts designed to prevent both contact sets from closing simultaneously under specified fault conditions. This helps suitable monitoring circuits detect faults such as welded contacts.
The documented 7S.12.9.024.5110 base model has a 6 A rated contact current. Actual permissible loads depend on the electrical switching conditions and manufacturer ratings.
The Finder 7S.12 base model is designed for 35 mm DIN rail mounting and has a nominal width of 22.5 mm. Confirm that these characteristics also apply to the T-suffix version.
Yes. The documented Finder 7S.12.9.024.5110 base model uses screwless spring-clamp terminals for its electrical connections.
The documented base model has an operating temperature range of −40 to +70 °C. The exact T-suffix version should be checked for any different environmental ratings.
No. A relay with forcibly guided contacts is a component used within a safety-related control system. It does not independently provide all the monitoring, diagnostics and system functions required of a complete safety controller.
It may be suitable as a component within an appropriately designed emergency-stop control circuit. The complete safety function must be assessed and validated to ensure it meets the required safety performance.
The Finder 7S.12.9.024.5110 is a documented 24 V DC, 1 NO + 1 NC forcibly guided relay module. The exact meaning of the additional T suffix in 7S.12.9.024.5110T has not been independently verified, so any differences should be confirmed with Finder before treating the products as interchangeable.
They help safety monitoring circuits detect certain contact faults, including welded contacts. This supports fault detection and controlled system behaviour when combined with a properly designed safety architecture.
Finder Series 7S relay modules combine forcibly guided contact technology with compact DIN rail construction and industrial relay switching performance. The 7S.12 family provides a practical relay interface for applications requiring monitored switching and contact feedback, subject to confirmation of the exact product variant and validation of the complete safety system.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.