Why Choose the WAGO 704-5004 16-Channel Relay Output Interface Module?

The WAGO 704-5004 is a 16-channel relay output interface module designed to connect industrial PLC output signals to electrically isolated switching contacts. Part of WAGO's 704 Series system wiring range, it features a 20-pole male connector according to DIN 41651, 16 miniature switching relays, individual channel status indicators and double-deck PCB terminal blocks in a DIN-rail mounting carrier.

Each relay channel provides one changeover contact (SPDT), allowing compatible loads to be switched through normally open or normally closed contact arrangements. The module operates from a nominal 24 V DC control supply and supports a maximum continuous current of 5 A per channel, subject to the relay and installation ratings. With a maximum switching voltage of 250 V AC or 48 V DC, it provides a practical interface between low-voltage PLC control signals and industrial switching circuits.

The WAGO 704-5004 incorporates green LED indicators for individual relay channels and a yellow power supply LED, making it easier to monitor output activity and diagnose control system operation. Its standardised DIN 41651 ribbon cable connection, replaceable relay arrangement and accessible field-side terminals help simplify industrial panel wiring, commissioning and maintenance.

Key Advantages

  • 16-channel relay output module consolidates multiple switching circuits into one interface assembly.
  • One changeover contact per channel provides flexible normally open and normally closed switching arrangements.
  • 24 V DC nominal operating voltage supports common industrial PLC control systems.
  • 5 A maximum continuous current per channel accommodates appropriately rated industrial loads.
  • 250 V AC maximum switching voltage supports compatible AC switching applications.
  • 48 V DC maximum switching voltage provides an option for suitable DC load circuits.
  • 20-pole DIN 41651 male connector supports organised PLC-to-interface ribbon cable connections.
  • 16 miniature switching relays provide electrically isolated relay contact outputs.
  • Green channel LEDs provide visual indication of individual relay activation.
  • Yellow power supply LED provides convenient supply status indication.
  • Integrated 1 A supply fuse provides protection within the module's control supply circuit.
  • Double-deck PCB terminal blocks provide accessible field-side load connections.
  • DIN-35 rail mounting simplifies integration into industrial electrical cabinets.
  • Compatible with selected GE Fanuc PLC modules, supporting suitable system wiring applications.

Key Features

  • WAGO 704 Series system wiring interface module.
  • 16 relay output channels.
  • One changeover contact per relay.
  • 20-pole male DIN 41651 system-side connector.
  • Double-deck PCB terminal blocks for field-side wiring.
  • Nominal operating voltage: 24 V DC.
  • Operating voltage tolerance: ±10%.
  • Maximum continuous current: 5 A per channel.
  • Maximum switching voltage: 250 V AC / 48 V DC.
  • Maximum resistive switching power: 1,250 VA AC / 50 W DC.
  • Short-duration making capacity: 16 A for 2 ms.
  • Mechanical relay life: 30 million switching operations.
  • Green LED for each output channel.
  • Yellow LED for power supply indication.
  • Internal supply fuse: 1 A.
  • WAGO 788-154 basic relay specified for the module.
  • DIN-35 rail mounting carrier.

16-Channel Relay Output Switching for Industrial PLC Systems

The WAGO 704-5004 converts control signals from a compatible PLC output interface into 16 independent relay contact outputs. Each channel provides a changeover contact, allowing the connected load to be switched using normally open or normally closed contacts as required by the application. This configuration is useful for controlling indicator devices, auxiliary relays, signalling circuits and other appropriately rated industrial electrical loads.

The module's 5 A maximum continuous current per channel applies regardless of the relay fitted, so replacement relay ratings must not be used to justify a higher module current. The maximum resistive switching capacities are 1,250 VA for AC circuits and 50 W for DC circuits. Actual permissible switching loads depend on the load type, voltage, power factor, switching frequency and relay contact characteristics.

Integrated LED Status Indication and Simplified Troubleshooting

The WAGO 704-5004 includes green LEDs for the individual relay channels, allowing technicians to observe relay activation during commissioning and fault finding. A separate yellow LED indicates the power supply status, helping distinguish control supply issues from individual output channel conditions.

The module also incorporates a 1 A internal supply fuse. This protects the module's supply circuit but does not replace suitable external protection for the switched load circuits. The standardised DIN 41651 connector helps organise PLC wiring, while the field-side terminal blocks allow load conductors to be accessed for inspection and maintenance.

Installation and Electrical Safety Considerations

The WAGO 704-5004 is designed for mounting on a standard 35 mm DIN rail inside an appropriate industrial electrical enclosure. Its 20-pole DIN 41651 connector must be connected using a compatible cable assembly with the correct pin assignment and orientation. The nominal 24 V DC control supply must remain within the specified ±10% operating range.

When connecting loads, observe the 5 A per-channel continuous current limit and the specified maximum AC and DC switching capacities. Inductive loads, such as contactor coils and solenoids, may require suitable suppression devices and additional switching derating. Appropriate circuit protection, conductor sizing, insulation separation and protection against accidental contact must be provided in accordance with the installation requirements.

Typical Applications

  • PLC relay output interfacing.
  • Industrial automation and electrical control cabinets.
  • 16-channel digital output switching.
  • GE Fanuc PLC system wiring applications.
  • Machinery control and auxiliary switching circuits.
  • Industrial signalling and alarm systems.
  • Control panel indicator and annunciator switching.
  • Interfacing low-voltage PLC outputs with suitable AC or DC loads.
  • Industrial equipment monitoring and control.
  • OEM machinery and control panel manufacturing.
  • Maintenance and replacement of industrial relay interface assemblies.

Technical Specifications

Type of electrical connection, field-sided Spring clamp connection
Type of electrical connection, control sided Other
Height 105 mm
Number of poles 64
Rated voltage 50 V
Width 180 mm
Rated current 5 A
Pollution degree 2
Depth 105 mm
Mounting method DIN rail (top hat rail) 35 mm
Manufacturer WAGO
Series 704 Series
Part number 704-5004
Product type Relay output interface module for system wiring
Number of output channels 16
Output technology Electromechanical miniature switching relays
Relay contact configuration 1 changeover contact (SPDT) per channel
Nominal operating voltage 24 V DC
Operating voltage range ±10%
Calculated operating voltage range 21.6–26.4 V DC
Maximum continuous current 5 A per channel
Short-duration making capacity 16 A for 2 ms
Maximum AC switching voltage 250 V AC
Maximum DC switching voltage 48 V DC
Maximum resistive AC switching power 1,250 VA
Maximum resistive DC switching power 50 W
Mechanical relay life 30 × 106 switching operations
Relay contact material AgNi 90/10
Basic relay reference WAGO 788-154
System-side connector DIN 41651 male
System-side number of poles 20
Field-side connection Double-deck PCB terminal blocks
Maximum conductor cross-section 2.5 mm²
Channel status indication Green LED
Power supply status indication Yellow LED
Internal supply fuse 1 A
Individual relay output fuses Not integrated
Rated insulation voltage 50 V
Rated surge voltage 0.8 kV
Dielectric strength between control and load circuits 2.5 kV AC RMS for 1 minute
Dielectric strength between load circuits 1 kV AC RMS for 1 minute
Net weight Approximately 550 g
Compatible PLC family Selected GE Fanuc Series 90-30 and RX3i modules
GE Fanuc Series 90-30 references IC693MDL740, IC693MDL742, IC693MDL753
GE Fanuc RX3i reference IC694MDL753

Frequently Asked Questions

What is the WAGO 704-5004 used for?

The WAGO 704-5004 is a 16-channel relay output interface module designed to connect compatible PLC output signals to individually accessible relay switching contacts. It uses a 20-pole DIN 41651 male connector and provides one changeover contact per channel for industrial control applications.

What is the operating voltage of the WAGO 704-5004?

The WAGO 704-5004 operates from a nominal 24 V DC supply with a tolerance of ±10%, corresponding to an operating range of 21.6–26.4 V DC. A yellow LED provides visual indication of the module's power supply status.

What is the maximum switching current and voltage of the WAGO 704-5004?

The module supports a maximum continuous current of 5 A per channel. Its maximum switching voltages are 250 V AC and 48 V DC, with maximum resistive switching powers of 1,250 VA AC and 50 W DC. The actual load must remain within all applicable relay and module ratings.

Does the WAGO 704-5004 include relay status LEDs and a fuse?

Yes. The WAGO 704-5004 features green LEDs for individual relay channels, a yellow power supply LED and an internal 1 A supply fuse. Individual relay output fuses are not integrated, so appropriate external load circuit protection must be provided.

How is the WAGO 704-5004 connected and mounted?

The WAGO 704-5004 uses a 20-pole DIN 41651 male connector for system-side wiring and double-deck PCB terminal blocks for field-side load connections, accepting conductors up to 2.5 mm². It mounts on a 35 mm DIN rail and measures approximately 180 mm wide, 105 mm high and 105 mm deep.

Trusted WAGO Relay Interface Technology for Industrial Automation

WAGO system wiring modules provide practical solutions for connecting industrial PLC control signals to field-side electrical circuits. The WAGO 704-5004 combines 16 relay output channels, individual changeover contacts, integrated LED status indication, a 20-pole DIN 41651 connector and DIN-rail mounting in an organised interface assembly for industrial automation and electrical control systems.