Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 66.82.9.012.1600 is a flange-mounted 30 A electromagnetic power relay featuring a 12 V DC coil, two normally open contacts, a minimum 1.5 mm contact gap and Faston 250 terminals for industrial power switching and renewable energy control applications.
The Finder 66.82.9.012.1600 is a high-current 30 A electromagnetic power relay designed for reliable electrical switching in industrial automation, power management and electrical control equipment. Featuring a 12 V DC operating coil, two normally open contacts (2 NO / DPST-NO) and a contact gap of at least 1.5 mm, this relay provides dependable two-pole switching for applications requiring defined contact separation.
As part of the established Finder Series 66 power relay range, the 66.82.9.012.1600 combines substantial contact current capacity with a robust flange-mounted design and Faston 250 quick-connect terminals. Its two normally open contacts operate together when the DC coil is energised, allowing two independent circuits or conductors to be switched through a common control signal.
The 66.82.9.012.1600 belongs to the Series 66 special contact-gap family, developed for switching applications where increased separation between open contacts is important. With a 12 V DC coil, 30 A nominal contact rating and 250 V AC nominal switching voltage, it is suitable for industrial machinery, electrical power control assemblies and appropriately designed renewable energy equipment.
The Finder 66.82.9.012.1600 uses an electromagnetic mechanism to control two normally open power contacts. When the 12 V DC coil is energised, the relay closes both contact circuits, allowing electrical loads to operate. When the coil supply is removed, the contacts return to their normally open positions.
A distinguishing characteristic of the Finder 66.82 x60x range is its minimum 1.5 mm open-contact gap. This design provides greater contact separation than conventional relay configurations and is particularly relevant to applications where defined switching isolation is required. The Series 66 x60x family has been developed with reference to switching requirements encountered in solar inverter and renewable energy equipment.
The relay's flange-mounted construction and Faston 250 terminals support installation into industrial electrical assemblies, while reinforced coil-to-contact insulation helps maintain separation between the control supply and switched circuits. For renewable energy, motor or other demanding applications, the complete system must be assessed for the required isolation function, switching duty, fault protection, electrical endurance and applicable standards.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Terminal Type | Faston / flat-pin | |
| Load Voltage | 440 V AC | |
| Mounting Type | Panel | |
| Manufacturer | Finder | |
| Series | 66 Series Power Relays | |
| Model | 66.82.9.012.1600 | |
| Relay type | 66.82 | |
| Product type | Electromagnetic power relay | |
| Contact configuration | 2 NO / DPST-NO | |
| Number of poles | 2 | |
| Contact arrangement | Normally open | |
| Minimum contact gap | 1.5 mm | |
| Nominal coil voltage | 12 V DC | |
| Coil supply type | Direct current (DC) | |
| Nominal DC coil consumption | 1.7 W | |
| Nominal contact current | 30 A | |
| Maximum peak contact current | 120 A for 5 ms, subject to contact material | |
| Nominal switching voltage | 250 V AC | |
| Maximum switching voltage | 440 V AC | |
| Rated AC-1 resistive load | 7,500 VA | |
| Rated AC-15 load at 230 V AC | 1,200 VA | |
| Single-phase motor rating at 230 V AC | 1.5 kW | |
| DC-1 breaking capacity at 24 V DC | 25 A | |
| DC-1 breaking capacity at 110 V DC | 1.2 A | |
| DC-1 breaking capacity at 220 V DC | 0.5 A | |
| Minimum switching load | 1,000 mW (10 V / 10 mA) | |
| Standard contact material | Silver tin oxide (AgSnO₂) | |
| Coil-to-contact insulation | Reinforced | |
| Coil-to-contact impulse withstand voltage | 6 kV | |
| Coil-to-contact creepage and clearance | 8 mm | |
| Operating temperature range | −40 to +70 °C | |
| Mounting type | Flange / panel mounting | |
| Terminal type | Faston 250 quick-connect terminals | |
| Terminal dimensions | 6.3 × 0.8 mm | |
| Contact-gap version | Series 66 x60x configuration | |
| Applicable relay standard | EN 61810-1 |
The Finder 66.82.9.012.1600 is a high-current electromagnetic power relay used for electrical load switching in industrial machinery, automation equipment and power control systems. Its two normally open contacts and increased contact gap also make it relevant to suitably designed renewable energy switching applications.
The relay uses a 12 V DC nominal operating coil. It is intended for compatible direct-current control supplies and has a nominal DC coil consumption of 1.7 W.
2 NO means two normally open contacts. DPST-NO stands for Double Pole Single Throw – Normally Open, indicating that the relay has two separate switching circuits which close together when the coil is energised.
The Finder 66.82.9.012.1600 belongs to the 30 A Series 66 power relay range. Its rated AC-1 resistive switching load is 7,500 VA. Actual switching capacity depends on the load category, voltage and operating conditions.
The relay uses a two normally open contact configuration with a minimum 1.5 mm contact gap. This increased contact separation distinguishes the x60x relay family from standard contact-gap variants.
The Finder Series 66 x60x relay family is designed with an increased contact gap for applications including solar inverter switching. Suitability for a particular inverter depends on the required isolation arrangement, electrical ratings and compliance of the complete equipment.
The relay is designed for flange mounting and uses Faston 250 quick-connect terminals measuring 6.3 × 0.8 mm. Compatible connectors and appropriately rated wiring should be used.
Both products belong to the Finder Series 66.82 family and use a 12 V DC coil. The 66.82.9.012.1600 is an x60x normally open contact-gap version with a minimum 1.5 mm gap, while the 66.82.9.012.1303 has a different contact and special-version configuration. Their exact contact materials, approvals and installation requirements should be compared before substitution.
Yes. The Series 66 x60x design supports appropriately rated DC switching. Published DC-1 breaking capacities include 25 A at 24 V DC, 1.2 A at 110 V DC and 0.5 A at 220 V DC. These ratings apply to the specified resistive load conditions.
The Series 66 provides reinforced insulation between the coil and contacts, with 8 mm creepage and clearance distances and a 6 kV coil-to-contact impulse withstand voltage. These are separate characteristics from the minimum 1.5 mm open-contact gap.
Finder Series 66 power relays provide dependable electromagnetic switching solutions for industrial machinery, power management systems and renewable energy equipment. Their high-current contact designs, reinforced insulation and specialised increased-contact-gap configurations make them a practical choice for engineers and OEM manufacturers developing reliable electrical control assemblies.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.