Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 66.82.9.012.1303 is a flange-mounted 30 A electromagnetic power relay featuring a 12 V DC coil, two normally open silver-nickel contacts, Faston 250 terminals and an ATEX / HazLoc special-version configuration for industrial electrical switching applications.
The Finder 66.82.9.012.1303 is a 30 A electromagnetic power relay designed for industrial electrical load switching, automation and power control applications. Featuring a 12 V DC operating coil, two normally open contacts (2 NO / DPST-NO) and silver-nickel (AgNi) contact material, this relay combines dependable switching performance with a robust industrial construction.
As part of the established Finder Series 66 power relay range, the 66.82.9.012.1303 features flange mounting and Faston 250 quick-connect terminals for installation into compatible electrical equipment. Its two normally open contact circuits operate together when the coil is energised, making it suitable for switching electrical loads through a common low-voltage control signal.
A distinguishing feature of the 66.82.9.012.1303 is its ATEX and HazLoc special-version designation, intended for suitably designed equipment used in specified hazardous-location environments. Its combination of 12 V DC control, 30 A nominal contact capability, reinforced coil-to-contact insulation and industrial mounting arrangement makes it a practical choice for OEM manufacturers and control system engineers requiring a specialised power relay.
The Finder 66.82.9.012.1303 uses an electromagnetic coil to operate two normally open power contacts. When the specified 12 V DC supply is applied to the coil, the relay closes both switching circuits. Removing the coil supply allows the contacts to return to their normally open positions, disconnecting the controlled loads.
The relay's silver-nickel contact material provides a cadmium-free contact option within the Finder Series 66 range. Its flange-mounted design and Faston 250 terminals allow integration into industrial electrical equipment without requiring the relay itself to be soldered onto a PCB. Reinforced insulation between the coil and contacts helps maintain electrical separation between the control supply and switched circuits.
The ATEX / HazLoc special version is intended for equipment designed to satisfy the relevant hazardous-location requirements. The relay must be installed within an appropriate protective enclosure, and the complete assembly must comply with the applicable electrical, thermal and explosion-protection conditions. Its hazardous-location designation does not make the bare relay suitable for unrestricted installation in an explosive atmosphere.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Terminal Type | Faston / flat-pin | |
| Load Voltage | 440 V AC | |
| Mounting Type | Panel | |
| Manufacturer | Finder | |
| Series | 66 Series Power Relays | |
| Model | 66.82.9.012.1303 | |
| Relay type | 66.82 | |
| Product type | Electromagnetic power relay | |
| Contact configuration | 2 NO / DPST-NO | |
| Number of poles | 2 | |
| Contact arrangement | Normally open | |
| Contact material | Silver-nickel (AgNi) | |
| Nominal coil voltage | 12 V DC | |
| Coil supply type | Direct current (DC) | |
| Nominal DC coil consumption | 1.7 W | |
| Coil resistance | 85 Ω | |
| Nominal coil current | 141 mA | |
| DC coil operating range | 9.6–13.2 V DC | |
| DC coil holding voltage | 0.5 × nominal voltage | |
| DC coil must-drop-out voltage | 0.1 × nominal voltage | |
| Nominal contact current | 30 A | |
| Maximum peak contact current | 50 A for the AgNi contact option | |
| Nominal switching voltage | 250 V AC | |
| Maximum switching voltage | 440 V AC under applicable general relay ratings | |
| Rated AC-1 resistive load | 7,500 VA | |
| Rated AC-15 load at 230 V AC | 1,200 VA | |
| Single-phase motor rating at 230 V AC | 1.5 kW | |
| DC-1 breaking capacity at 24 V DC | 25 A | |
| DC-1 breaking capacity at 110 V DC | 0.7 A | |
| DC-1 breaking capacity at 220 V DC | 0.3 A | |
| Minimum switching load | 1,000 mW (10 V / 10 mA) | |
| Mechanical endurance | 10,000,000 cycles | |
| Electrical endurance at rated AC-1 load | 100,000 cycles | |
| Typical operate time | 8 ms | |
| Typical release time | 10 ms | |
| Coil-to-contact insulation | Reinforced | |
| Coil-to-contact impulse withstand voltage | 6 kV | |
| Coil-to-contact creepage and clearance | 8 mm | |
| Dielectric strength between open contacts | 1,500 V AC | |
| General ambient temperature range | −40 to +70 °C | |
| Mounting type | Flange / panel mounting | |
| Terminal type | Faston 250 quick-connect terminals | |
| Terminal dimensions | 6.3 × 0.8 mm | |
| Special version | ATEX / HazLoc | |
| ATEX marking | II 3G Ex ec nC IIC Gc | |
| HazLoc classification | Class I, Division 2, Groups A, B, C and D, subject to applicable temperature classification and installation requirements | |
| Hazardous-location enclosure requirement | IP54 or higher, with applicable Ex protection requirements | |
| Minimum conductor cross-section for ATEX installation | 4 mm² | |
| Applicable relay standard | EN 61810-1 |
The Finder 66.82.9.012.1303 is an electromagnetic power relay used to switch electrical loads in industrial machinery, automation equipment and power control systems. It is an ATEX / HazLoc special version intended for suitably designed electrical equipment operating under the relevant hazardous-location conditions.
The relay features a 12 V DC nominal operating coil with a standard operating range of 9.6–13.2 V DC and nominal coil consumption of 1.7 W.
2 NO means two normally open contacts, while DPST-NO stands for Double Pole Single Throw – Normally Open. The relay contains two separate switching circuits that close together when the coil is energised.
The Finder 66.82.9.012.1303 belongs to the 30 A Series 66 power relay range. The AgNi contact option has a 50 A maximum peak contact current. Actual permissible switching loads depend on the application, utilisation category and applicable hazardous-location limits.
The relay uses silver-nickel (AgNi) contacts. This is a cadmium-free contact material option within the Finder Series 66 range.
The configuration code identifies AgNi contact material, a normally open contact arrangement and an ATEX / HazLoc special version. These characteristics distinguish the relay from standard Series 66 configurations.
The relay is an ATEX / HazLoc special version intended for integration into equipment meeting the relevant hazardous-location requirements. Its ATEX designation is II 3G Ex ec nC IIC Gc. Appropriate enclosure protection, wiring, temperature classification and equipment-level compliance are required.
The relay features flange mounting and Faston 250 terminals measuring 6.3 × 0.8 mm. For ATEX applications, Finder specifies an appropriate enclosure with at least IP54 protection and a minimum conductor cross-section of 4 mm², together with the applicable explosion-protection installation requirements.
Yes. The relay can be controlled through a suitable PLC output or interposing driver capable of supplying its 12 V DC coil. The output must accommodate the nominal coil current of approximately 141 mA, and appropriate suppression and installation measures should be considered.
The Finder Series 66 relay has a general ambient operating temperature range of −40 to +70 °C. For hazardous-location applications, the permissible ambient temperature and load depend on the required temperature classification and the manufacturer's specific installation conditions.
Finder Series 66 power relays provide robust electromagnetic switching solutions for industrial machinery, electrical control equipment and power management systems. The availability of cadmium-free contacts, DC operating coils and specialised ATEX / HazLoc versions makes the range suitable for engineers and OEM manufacturers designing reliable industrial control assemblies with clearly defined electrical and environmental requirements.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.