Finder 66.82.8.120.4301 is a 120 V AC electromechanical power relay from the Series 66.82 range, featuring double-pole high-current switching, reinforced coil-to-contact insulation, flange mounting and Faston 250 terminals for industrial automation and electrical control applications.
£15.98
The Finder 66.82.8.120.4301 is a robust electromechanical power relay designed for high-current electrical switching in industrial automation, machinery control and power management systems. As part of the established Finder Series 66 power relay range, it combines dependable electromagnetic operation, high-current contacts and reinforced electrical insulation in a practical flange-mounted construction.
The Finder 66.82 family features double-pole switching technology and is designed for applications requiring reliable control of electrical loads. The 66.82.8.120.4301 incorporates a 120 V AC operating coil, allowing compatible AC control circuits to operate the relay contacts. Its Faston 250 quick-connect terminals and flange-mounted housing support convenient installation within industrial electrical equipment and control assemblies.
The Finder 66.82 series provides 30 A rated normally open contacts for resistive AC loads, with a 250 V AC rated contact voltage. The 66.82.8.120.4301 is suitable for industrial heating equipment, HVAC systems, electrical machinery and power switching applications where robust construction and dependable electrical isolation are important.
Electromechanical power relays such as the Finder 66.82.8.120.4301 provide an effective method of controlling electrical loads using a separate low-power electromagnetic control circuit. When the 120 V AC coil is energised, the internal relay mechanism operates the switching contacts, allowing connected equipment to be controlled without passing the full load current through the control device.
The Finder Series 66.82 is designed for industrial applications requiring high-current switching, reinforced electrical insulation and secure mechanical installation. Its flange-mounted housing and Faston 250 terminals simplify integration into electrical equipment, while its double-pole construction supports control of separate electrical circuits. Correct relay selection should consider the contact configuration, load characteristics, switching frequency and applicable manufacturer ratings.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Terminal Type | Faston / flat-pin | |
| Load Voltage | 440 V AC | |
| Manufacturer | Finder | |
| Series | 66 Series Power Relays | |
| Model | 66.82.8.120.4301 | |
| Product type | Electromechanical power relay | |
| Relay family | 66.82 | |
| Number of poles | 2 | |
| Nominal coil voltage | 120 V AC | |
| Coil frequency | 50/60 Hz | |
| Coil type | AC electromagnetic coil | |
| Nominal coil consumption | 3.6 VA | |
| Nominal coil current | 30 mA at 50 Hz | |
| Nominal coil resistance | approx. 1.05 kΩ | |
| AC coil operating range | 0.8–1.1 × nominal voltage (Series 66) | |
| Rated normally open contact current | 30 A (Series 66.82) | |
| Rated normally closed contact current | 10 A (changeover variants) | |
| Rated contact voltage | 250 V AC | |
| Maximum switching voltage | 440 V AC | |
| Rated AC1 switching load | 7,500 VA (NO) / 2,500 VA (NC, where fitted) | |
| Rated AC15 switching load at 230 V AC | 1,200 VA (NO) | |
| Single-phase motor rating at 230 V AC | 1.5 kW (NO) | |
| DC1 breaking capacity at 24 V DC | 25 A (NO) | |
| Minimum switching load | 1,000 mW (10 V / 10 mA) | |
| Operating mechanism | Non-latching / monostable | |
| Mounting type | Flange / chassis mounting | |
| Terminal type | Faston 250 quick-connect terminals | |
| Terminal dimensions | 6.3 × 0.8 mm | |
| Insulation | Reinforced insulation between coil and contacts | |
| Creepage and clearance | 8 mm | |
| Coil-to-contact impulse withstand | 6 kV | |
| Dielectric strength between open contacts | 1,500 V AC | |
| Operating temperature | −40 to +70 °C | |
| Environmental protection category | RT II (standard Series 66 construction) | |
| Dimensions (L × W × H) | approx. 68.5 × 33.5 × 31 mm |
The Finder 66.82.8.120.4301 is an electromechanical power relay intended for switching electrical loads in industrial automation, machinery, heating equipment and electrical control systems. It belongs to the Finder Series 66.82 flange-mounted relay family.
The relay operates with a 120 V AC nominal coil voltage at 50/60 Hz. The Series 66 AC coil has a nominal consumption of approximately 3.6 VA.
The Finder 66.82 series provides 30 A rated normally open contacts for resistive AC loads at a rated voltage of 250 V AC. Changeover variants also have normally closed contacts with a lower current rating. The permissible load depends on the exact contact configuration and operating conditions.
The Finder 66.82 relay family uses a flange-mounted housing with Faston 250 quick-connect terminals. This construction supports installation within electrical control panels, machinery and industrial equipment rather than direct PCB mounting.
The Series 66 combines high-current switching capability, reinforced electrical insulation and dependable electromechanical operation. Its flange-mounted variants provide secure installation and convenient electrical connections for industrial control and power switching applications.
Finder Series 66 power relays are designed to deliver dependable high-current switching in industrial automation, electrical control and power management equipment. Their robust construction, reinforced insulation and practical mounting arrangements make them a valuable choice for engineers and OEM manufacturers developing reliable industrial electrical systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.