Finder 65.31.8.230.4309 is a 30 A industrial power relay with a 230 V AC coil, one normally open contact, silver tin oxide contact material, a minimum 3 mm contact gap, Faston 250 terminals and rear flange mounting for industrial automation and high-current electrical load switching.
The Finder 65.31.8.230.4309 is a heavy-duty 30 A industrial electromechanical power relay designed for reliable switching of high-current electrical loads. Part of the established Finder 65 Series, this relay features a 230 V AC operating coil, a single normally open contact (SPST-NO / 1 Form A) and a robust panel-mounting design.
Featuring silver tin oxide (AgSnO₂) contact material, the Finder 65.31.8.230.4309 is suitable for demanding industrial switching applications. Its 30 A rated contact current, 250 V AC rated contact voltage and 7,500 VA resistive switching capacity make it a practical choice for industrial machinery, heating equipment, lighting control and electrical automation systems.
A key feature of this relay is its normally open contact with a minimum 3 mm contact gap, providing increased contact separation when the relay is de-energised. Combined with Faston 250 quick-connect terminals and rear flange mounting, the Finder 65.31.8.230.4309 offers a dependable solution for installing or replacing high-current relays in compatible electrical control panels.
The Finder 65.31.8.230.4309 operates as an electrically controlled power switch. When its 230 V AC coil is energised, the relay closes its normally open contact, allowing current to flow through the connected load circuit. When coil power is removed, the contact returns to its open position, interrupting the electrical connection.
Unlike multi-pole changeover relays, the 65.31.8.230.4309 is specifically designed around a single high-current normally open contact. This makes it particularly useful where a control circuit needs to energise or disconnect one substantial electrical load. Its 30 A contact rating and 7,500 VA AC1 switching capacity provide considerable flexibility for appropriately rated resistive loads.
The relay's silver tin oxide contacts support dependable switching in industrial applications, while the minimum 3 mm contact gap provides increased separation when the contact is open. This feature is useful in equipment designed to meet relevant contact-separation requirements, although the relay should not be treated as a substitute for a dedicated safety isolator unless the complete installation meets the applicable standards.
For installation, the rear flange mounting arrangement allows secure attachment to a suitable panel or chassis. The Faston 250 quick-connect terminals provide a convenient connection method using compatible receptacles. Its 230 V AC coil is suitable for control systems operating from the appropriate AC supply, with suitable protection, wiring and switching arrangements.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Terminal Type | Faston / flat-pin | |
| Switching Current (A) | 30 A | |
| Load Voltage | 400 V AC | |
| Mounting Type | Panel | |
| Manufacturer | Finder | |
| Series | 65 Series Power Relays | |
| Model | 65.31.8.230.4309 | |
| Product type | Industrial electromechanical power relay | |
| Contact configuration | SPST-NO / 1 Form A | |
| Number of poles | 1 | |
| Number of normally open contacts | 1 | |
| Normally closed contacts | None | |
| Rated contact current | 30 A | |
| Maximum peak contact current | 120 A for 5 ms | |
| Rated contact voltage | 250 V AC | |
| Maximum switching voltage | 400 V AC | |
| Maximum DC switching voltage | 220 V DC, subject to breaking-capacity limits | |
| Rated resistive load (AC1) | 7,500 VA | |
| Rated inductive load (AC15 at 230 V AC) | 1,250 VA | |
| Single-phase motor rating at 230 V AC | 1.5 kW | |
| DC1 breaking capacity at 24 V DC | 30 A | |
| DC1 breaking capacity at 110 V DC | 1.1 A | |
| DC1 breaking capacity at 220 V DC | 0.7 A | |
| Minimum switching load | 1,000 mW (10 V / 10 mA) | |
| Nominal coil voltage | 230 V AC | |
| Coil frequency | 50/60 Hz | |
| Coil type | AC, non-latching | |
| Nominal coil consumption | 2.2 VA | |
| Nominal coil current | Approximately 10.5 mA | |
| Nominal coil resistance | 7,250 Ω | |
| Coil operating voltage range | 184 to 253 V AC | |
| Contact material | Silver tin oxide (AgSnO₂) | |
| Open-contact gap | At least 3 mm | |
| Mounting type | Chassis / panel mounting | |
| Mounting arrangement | Rear flange | |
| Terminal type | Faston 250 quick-connect | |
| Terminal dimensions | 6.3 × 0.8 mm | |
| Number of electrical terminals | 4 | |
| Overall dimensions | Approximately 36.5 × 32.2 × 59.2 mm, including mounting arrangement | |
| Operating temperature | −40 to +75 °C | |
| Mechanical endurance | 10 million operations | |
| Electrical endurance at rated AC1 load | 30,000 operations | |
| Operating time | Approximately 15 ms | |
| Release time | Approximately 4 ms | |
| Coil-to-contact impulse withstand voltage | 4 kV | |
| Dielectric strength between open contacts | 2,500 V AC | |
| Environmental protection category | RT I | |
| Application | Industrial automation, high-current switching and electrical control systems |
The Finder 65.31.8.230.4309 is a 30 A industrial power relay used for switching electrical loads in machinery, automation systems and electrical control panels. It operates a single normally open contact using a 230 V AC coil.
The relay has a 230 V AC nominal coil voltage at 50/60 Hz. Its nominal coil consumption is 2.2 VA, with a coil resistance of approximately 7.25 kΩ.
The Finder 65.31.8.230.4309 has a 30 A rated contact current at 250 V AC, with a rated resistive switching capacity of 7,500 VA. Its maximum switching voltage is 400 V AC. The permissible load depends on its electrical characteristics and switching category.
The relay has one normally open contact (SPST-NO / 1 Form A). This contact closes when the coil is energised and opens when the coil is de-energised. It does not provide a normally closed or changeover contact.
The Finder 65.31.8.230.4309 features a minimum 3 mm gap between its open contacts. This provides increased physical separation when the relay is de-energised and supports applications requiring this contact-gap characteristic. The overall equipment design must still meet the relevant electrical safety requirements.
The relay uses a rear flange mounting arrangement for installation on a suitable chassis or panel. Electrical connections are made using Faston 250 quick-connect terminals measuring 6.3 × 0.8 mm.
The Finder 65.31.8.230.4309 uses silver tin oxide (AgSnO₂) contacts. This cadmium-free contact material is suitable for reliable switching of compatible industrial electrical loads.
The relay's 230 V AC coil has a specified operating range of approximately 184 to 253 V AC under the manufacturer's reference conditions. Actual operating behaviour can depend on the ambient temperature and installation conditions.
The relay has a specified mechanical endurance of 10 million operations and an electrical endurance of approximately 30,000 operations at the rated AC1 resistive load. Actual service life depends on switching frequency, electrical loading and environmental conditions.
The principal difference is the contact configuration and current rating. The 65.31.8.230.4309 has one normally open contact rated at 30 A, while the 65.31.8.230.4000 has one normally open and one normally closed contact, rated at 20 A. Both use a 230 V AC coil, but their contact arrangements and electrical ratings are different.
Yes. The relay can switch compatible DC loads, but its 30 A rating does not apply at every DC voltage. The manufacturer's DC1 ratings include 30 A at 24 V DC, 1.1 A at 110 V DC and 0.7 A at 220 V DC. Inductive DC loads require additional assessment of switching capacity and suitable protection.
Finder 65 Series power relays are designed for demanding industrial automation, electrical control and power management applications. The Finder 65.31.8.230.4309 combines a 30 A contact rating, 230 V AC coil, silver tin oxide contacts, 3 mm contact gap and Faston 250 terminals to deliver a dependable high-current switching solution for compatible industrial equipment.