Finder 62.82.9.048.0040 is a 16 A electromagnetic power relay with a 48 V DC coil, two changeover contacts, a lockable test button, mechanical indicator and rear flange-mounted Faston 250 connections.
The Finder 62.82.9.048.0040 is a robust 16 A electromagnetic power relay designed for switching electrical loads in industrial control, automation and power management applications. Part of the Finder 62 Series, it combines a 48 V DC coil with two changeover contacts for flexible control of industrial equipment.
This model incorporates a lockable test button and mechanical indicator, allowing engineers to test relay operation manually and check its switching state during commissioning, maintenance and fault diagnosis. Its 2 CO contact configuration supports changeover control, interlocking and simultaneous switching across two independent circuits.
With a rated contact current of 16 A, an AC1 load rating of 4,000 VA and 6.3 × 0.8 mm Faston 250 terminals, the 62.82.9.048.0040 is suitable for demanding industrial installations. Its rear flange provides secure mounting within machinery, control panels and electrical equipment.
Electromagnetic power relays allow a relatively low-power control signal to operate higher-current electrical loads. Applying 48 V DC to the coil of the Finder 62.82.9.048.0040 transfers both changeover contacts, enabling two circuits to be switched simultaneously.
The lockable test button enables manual operation during installation and maintenance, while the mechanical indicator makes the relay’s switching state easier to identify. Rear flange mounting and Faston terminals support secure installation and efficient wiring in industrial machinery and control systems.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Terminal Type | Faston / flat-pin | |
| Load Voltage | 400 V AC | |
| Mounting Type | Panel | |
| Switching Current (A) | 16 A | |
| Contacts | 2 C/O | |
| HS Code | 85364900 | |
| Manufacturer | Finder | |
| Series | 62 Series | |
| Model | 62.82.9.048.0040 | |
| Product type | Electromagnetic power relay | |
| Contact configuration | 2 CO (DPDT) | |
| Rated contact current | 16 A | |
| Rated contact voltage | 250 V AC | |
| Maximum switching voltage | 400 V AC | |
| Rated load AC1 | 4,000 VA | |
| Rated load AC15 at 230 V AC | 750 VA | |
| Motor rating at 230 V AC | 0.8 kW | |
| DC1 breaking capacity at 24 / 110 / 220 V DC | 16 / 0.6 / 0.4 A | |
| Minimum switching load | 1,000 mW (10 V / 10 mA) | |
| Contact material | AgCdO | |
| Nominal coil voltage | 48 V DC | |
| Coil current | 27 mA | |
| Coil resistance | 1.77 kΩ | |
| Rated coil power | 1.3 W | |
| DC operating range | 0.8–1.1 UN | |
| Operate / release time | 11 / 4 ms | |
| Mechanical life | 30 million cycles | |
| Electrical life at rated AC1 load | 100,000 cycles | |
| Coil-to-contact impulse withstand voltage | 6 kV | |
| Dielectric strength between open contacts | 1,500 V AC | |
| Ambient operating temperature | −40 to +70 °C | |
| Environmental protection | RT I | |
| Mounting type | Rear flange panel mounting | |
| Terminal type | Faston 250, 6.3 × 0.8 mm | |
| Dimensions | 35.8 × 38.2 × 49.1 mm |
This power relay is used to switch motors, lighting, heating equipment and other electrical loads in industrial control and automation systems.
The Finder 62.82.9.048.0040 has a nominal 48 V DC coil.
The relay provides two changeover contacts, also described as a 2 CO or DPDT contact configuration.
Yes. The relay includes a lockable test button and mechanical indicator for manual testing and visual status checking.
The relay is secured using its rear mounting flange and connected with 6.3 × 0.8 mm Faston 250 terminals.