Finder 62.82.9.024.4500 is a 16 A double-pole changeover industrial power relay with a 24 V DC coil, silver tin oxide contacts, additional coil-to-contact separation, rear flange mounting and Faston 250 terminals for reliable electrical switching in industrial automation and control panels.
£12.92
The Finder 62.82.9.024.4500 is a robust and reliable 16 A industrial power relay with a 24 V DC coil and two changeover contacts, designed for dependable electrical switching in industrial automation, machinery and electrical control systems. As part of the established Finder 62 Series power relay range, this model combines durable electromechanical switching with a practical flange-mounted construction, making it suitable for machine builders, electrical engineers and industrial maintenance professionals.
Featuring a double-pole double-throw (DPDT / 2 CO) contact configuration, the relay enables two independent electrical circuits to be switched simultaneously using a single DC control signal. Its silver tin oxide (AgSnO2) contacts provide durable switching characteristics, while the additional contact-to-coil separation associated with the 62 Series 4500 configuration makes it suitable for applications requiring enhanced segregation between control and switching circuits.
With a 16 A rated contact current, 24 V DC nominal coil voltage and 250 V AC rated contact voltage, the Finder 62.82.9.024.4500 is suitable for industrial switching duties involving control circuits, electrical loads and automation equipment. Its rear flange mounting arrangement and Faston 250 quick-connect terminals support secure installation and straightforward electrical connections within industrial control panels.
Industrial power relays such as the Finder 62.82.9.024.4500 provide a dependable method of controlling electrical loads using a separate DC control signal. When the relay's 24 V DC coil is energised, an electromagnetic mechanism operates the internal changeover contacts, transferring each circuit between its normally closed and normally open connections. This enables two independent electrical circuits to be switched simultaneously while maintaining galvanic isolation between the control coil and connected loads.
The Finder 62 Series is designed for industrial switching applications where dependable contact operation, robust construction and straightforward installation are essential. The 62.82.9.024.4500 combines durable AgSnO2 contacts with an additional physical separator between the coil and contact circuits. This arrangement supports applications where increased physical segregation is important, including appropriately designed control systems requiring separation between low-voltage control electronics and switched electrical loads.
Its rear flange mounting arrangement and Faston 250 quick-connect terminals support secure installation and convenient wiring within industrial machinery and electrical control cabinets. With a 16 A rated contact current and 24 V DC operating coil, the relay is suitable for auxiliary switching, electrical interlocking, equipment signalling and automation control applications. The permissible switching current must always be selected according to the load type, operating voltage and manufacturer's specified ratings.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Terminal Type | Faston / flat-pin | |
| Switching Current (A) | 16 A | |
| Load Voltage | 400 V AC | |
| Mounting Type | Panel | |
| Manufacturer | Finder | |
| Series | 62 Series Power Relays | |
| Model | 62.82.9.024.4500 | |
| Product type | Electromechanical industrial power relay | |
| Contact configuration | DPDT / 2 CO (two changeover contacts) | |
| Number of poles | 2 | |
| Number of changeover contacts | 2 | |
| Rated contact current | 16 A | |
| Rated contact voltage | 250 V AC | |
| Maximum switching voltage | 400 V AC | |
| Rated resistive load (AC1) | 4,000 VA | |
| Contact material | Silver tin oxide (AgSnO2) | |
| Nominal coil voltage | 24 V DC | |
| Coil supply type | DC | |
| Nominal coil power | 1.3 W | |
| Nominal coil resistance | 445 Ω | |
| Nominal coil current | 54 mA | |
| Coil operating voltage range | 20.4–26.4 V DC | |
| Coil operating principle | Electromagnetic, non-latching | |
| Contact switching action | Electromechanical changeover | |
| Contact-to-coil separation | Additional physical separator | |
| Coil-to-contact insulation | Reinforced insulation | |
| Coil-to-contact clearance | 6 mm | |
| Coil-to-contact creepage distance | 8 mm | |
| Coil-to-contact impulse withstand voltage | 6 kV | |
| Typical operate time | 11 ms | |
| Typical release time | 4 ms | |
| Mechanical durability | 30,000,000 operations | |
| Electrical life at rated AC1 load | 100,000 operations | |
| Mounting type | Rear flange / panel mounting | |
| Terminal type | Faston 250 quick-connect | |
| Terminal dimensions | 6.3 × 0.8 mm | |
| Environmental protection category | RT I | |
| Operating temperature range | −40 to +70 °C |
The Finder 62.82.9.024.4500 is a 16 A industrial power relay used for switching electrical circuits in industrial automation, machinery and electrical control panels. Its two changeover contacts allow two independent circuits to be controlled simultaneously using a single 24 V DC coil.
The relay operates using a 24 V DC nominal coil with approximately 1.3 W nominal coil consumption. The standard Finder 62 Series 24 V DC coil has a nominal resistance of 445 Ω and an operating voltage range of approximately 20.4–26.4 V DC.
The relay features two changeover contacts (DPDT / 2 CO). Each contact provides a common terminal, a normally closed terminal and a normally open terminal, allowing two independent electrical circuits to change switching state when the relay coil is energised.
The 4500 configuration incorporates an additional physical separator between the coil and contact circuits. This complements the Finder 62 Series reinforced insulation design and makes the relay suitable for applications requiring enhanced physical separation between control and switched circuits, subject to the complete equipment's insulation and safety requirements.
The Finder 62.82.9.024.4500 is a rear flange-mounted industrial power relay with Faston 250 quick-connect terminals measuring 6.3 × 0.8 mm. It is designed for secure installation on suitable panels or equipment mounting surfaces, rather than conventional plug-in relay socket mounting.
Finder 62 Series power relays are widely used by automation engineers, electrical maintenance professionals and machine builders for dependable industrial switching. The Finder 62.82.9.024.4500 combines a 24 V DC control coil, two 16 A changeover contacts, silver tin oxide contact material, additional coil-to-contact separation and robust rear flange mounting, providing a practical solution for industrial machinery, electrical control panels and automation equipment.