62.33.9.024.4360 Finder Power relay 3 pole 16A DC 24V

62.33.9.024.4360 Finder Power relay 3 pole 16A DC 24V

Finder 62.33.9.024.4360 is a 62 Series electromechanical power relay with a 24 V DC coil, three normally open contacts rated at 16 A, a minimum 3 mm contact gap, silver tin oxide contacts, integrated LED indication, a flyback suppression diode and Faston 187 quick-connect terminals. Suitable for industrial automation, PLC-controlled switching and machinery control.

SKU: 62.33.9.024.4360Alt SKU: 623390244360MPN: 62.33.9.024.4360
Price on application Contact us for pricing and availability.
Call 01708 343600

Why Choose the Finder 62.33.9.024.4360 Power Relay?

The Finder 62.33.9.024.4360 is a robust 16 A three-pole electromechanical power relay designed for dependable switching in industrial automation, machinery control and electrical control panels. Part of the established Finder 62 Series, this model features a 24 V DC operating coil, three normally open contacts (3 NO / 3PST-NO), an integrated LED indicator and a built-in flyback diode.

A defining characteristic of the 62.33.9.024.4360 is its three normally open contacts with a contact gap of at least 3 mm. Unlike three-pole changeover relays, which provide both normally open and normally closed connections, this version is designed to close three separate circuits when its coil is energised. The larger contact gap provides increased physical separation between open contacts, making this configuration suitable for industrial applications requiring enhanced contact separation.

The relay also incorporates an LED coil indicator and an integrated suppression diode. The LED provides convenient visual confirmation of coil energisation, while the diode helps suppress the inductive voltage transient generated when the DC coil is switched off. Combined with silver tin oxide (AgSnO2) contacts, Faston 187 quick-connect terminals and a plug-in construction, the Finder 62.33.9.024.4360 is a practical choice for industrial panel builders, automation engineers and maintenance professionals.

Key Advantages

  • 16 A three-pole power relay for industrial electrical switching.
  • 24 V DC operating coil suitable for compatible industrial control systems.
  • Three normally open contacts (3 NO / 3PST-NO) for simultaneous switching of three circuits.
  • Minimum 3 mm contact gap for increased separation between open contacts.
  • Integrated LED indicator provides visual confirmation of coil energisation.
  • Built-in flyback diode helps protect compatible electronic control outputs from coil switching transients.
  • 16 A contact rating for appropriately rated resistive loads.
  • 250 V AC rated contact voltage for industrial switching applications.
  • Silver tin oxide contacts provide good resistance to contact welding.
  • Faston 187 quick-connect terminals simplify electrical connections.
  • Plug-in construction supports installation and replacement using compatible sockets.
  • Monostable operation returns all contacts to their open positions when the coil is de-energised.
  • Three independent contact circuits provide flexible auxiliary switching.
  • Integrated coil suppression reduces the need for an external flyback diode.

Key Features

  • Finder 62 Series industrial power relay.
  • 62.33 plug-in relay configuration.
  • 24 V DC nominal coil voltage.
  • Three normally open contacts (3 NO / 3PST-NO).
  • Three independent single-pole, single-throw contact sets.
  • Minimum 3 mm open-contact gap.
  • 16 A nominal contact current.
  • 250 V AC rated contact voltage.
  • 400 V AC maximum switching voltage.
  • Silver tin oxide (AgSnO2) contact material.
  • Integrated LED coil-status indicator.
  • Integrated flyback suppression diode.
  • Polarity-sensitive DC coil connections.
  • 3 W nominal coil consumption.
  • 125 mA nominal coil current.
  • 192 Ω nominal coil resistance.
  • Faston 187 quick-connect terminals.
  • 4.8 × 0.5 mm terminal dimensions.
  • Plug-in mounting arrangement.
  • Monostable electromagnetic switching.
  • 30 million mechanical operations under specified test conditions.
  • 100,000 electrical operations under specified rated-load conditions.
  • Suitable for compatible PLC and electronic control systems.

Reliable Three-Pole Normally Open Switching with a 3 mm Contact Gap

The Finder 62.33.9.024.4360 uses an electromagnetic mechanism to control three independent normally open contact sets. When the 24 V DC coil is energised with the correct polarity, the internal armature moves and closes all three contact circuits. When the coil supply is removed, the contacts return to their normally open positions.

The 3PST-NO contact configuration is particularly useful where an application requires three circuits to be energised together without the normally closed connections associated with a changeover relay. The minimum 3 mm contact gap distinguishes this model from standard changeover versions of the Finder 62.33 family. However, a larger contact gap alone does not establish suitability as a safety isolator; any isolation or safety-related application must be assessed against the relevant equipment standards and manufacturer's approvals.

Integrated LED Indication and DC Coil Suppression

The integrated LED indicator provides visual confirmation that the relay coil is energised. This feature helps technicians identify active control signals during installation, commissioning and troubleshooting. The LED indicates the electrical status of the coil rather than independently confirming the condition of each switching contact.

The built-in flyback diode helps limit the voltage transient generated when the relay's electromagnetic coil is switched off. This is beneficial when the relay is driven by a compatible PLC output, transistor driver or electronic controller. Because the diode provides a discharge path for the coil current, it may also increase the contact release time compared with an unsuppressed relay.

Correct polarity is essential. The relay's positive and negative coil terminals must be connected according to the manufacturer's terminal markings. Reversing the DC supply can forward-bias the suppression diode and cause excessive current flow. The relay's 125 mA nominal coil current should also be checked against the switching capability of the control output.

Finder 62.33.9.024.4360 vs 62.33.9.024.4060

Although both models use a 24 V DC coil and include an LED indicator and flyback diode, their contact configurations are different.

  • Finder 62.33.9.024.4360: Three normally open contacts (3PST-NO), minimum 3 mm contact gap, 3 W coil consumption and 125 mA nominal coil current.
  • Finder 62.33.9.024.4060: Three changeover contacts (3PDT), standard changeover contact arrangement and lower nominal coil consumption.

The two relays should not be treated as direct electrical equivalents. Their contact arrangements, terminal functions and coil requirements differ. Before replacing one model with another, verify the complete part number, wiring diagram, coil supply capacity and compatible socket.

Typical Applications

  • Industrial automation and machinery control systems.
  • 24 V DC electrical control circuits.
  • PLC-controlled auxiliary switching.
  • Three-pole normally open switching applications.
  • Industrial electrical control panels and cabinets.
  • Multi-circuit power and control switching.
  • Industrial process control and manufacturing machinery.
  • Control of contactors and auxiliary equipment.
  • Industrial signalling and monitoring circuits.
  • Electrical control assemblies requiring LED indication.
  • Electronic control circuits requiring suitable coil transient suppression.
  • Heating, ventilation and air conditioning control systems.
  • OEM industrial machinery and equipment manufacturing.
  • Maintenance and replacement of compatible Finder 62.33 relays.

Technical Specifications

Tick the specs you need, then view products that match.

Device Type Power Relay
Terminal Type Faston / flat-pin
Switching Current (A) 16 A
Load Voltage 400 V AC
Mounting Type Plug-in socket
Manufacturer Finder
Series 62 Series Power Relays
Manufacturer part number 62.33.9.024.4360
Product type Electromechanical power relay
Relay configuration 3 NO / 3PST-NO / 3 Form A
Number of poles 3
Contact arrangement Three independent normally open contacts
Contact gap At least 3 mm
Nominal coil voltage 24 V DC
Coil supply type Direct current (DC)
Nominal coil consumption 3 W
Nominal coil current 125 mA
Nominal coil resistance 192 Ω
Must-operate voltage 20.4 V DC
Must-release voltage 4.8 V DC
Coil polarity Polarity-sensitive due to integrated suppression diode
Coil suppression Integrated flyback diode
Relay operating mode Monostable / non-latching
Rated contact current 16 A
Rated contact voltage 250 V AC
Maximum switching voltage 400 V AC
Resistive AC contact rating 16 A at 250 V AC
Resistive DC contact rating 16 A at 24 V DC
Contact material Silver tin oxide (AgSnO2)
Contact material characteristic Cadmium-free
Mechanical durability 30 million operations
Electrical durability 100,000 operations under specified conditions
Typical operate time Approximately 11 ms
Release time Dependent on coil suppression and test conditions
Operating temperature −40 to +50 °C
Integrated LED indicator Included
Integrated flyback diode Included
Manual test button Not included
Mounting type Plug-in / socket mounting
Terminal type Faston 187 quick-connect
Terminal dimensions 4.8 × 0.5 mm
Number of terminals 8
Approximate body dimensions 35.8 × 38.2 × 51.1 mm
Approximate gross weight 90 g
EAN 8012823332000
Operating principle Electromagnetic switching
Typical applications Industrial automation, PLC-controlled switching, machinery control and electrical control panels

Frequently Asked Questions

What is the Finder 62.33.9.024.4360 used for?

The Finder 62.33.9.024.4360 is a three-pole electromechanical power relay used for industrial automation, machinery control and electrical switching. It features three normally open contacts, a 24 V DC coil, integrated LED indication and a flyback diode. Its contacts have a minimum 3 mm open-contact gap.

What coil voltage and current does the Finder 62.33.9.024.4360 require?

The relay requires a 24 V DC nominal coil supply. Its nominal coil current is 125 mA, nominal coil resistance is 192 Ω and nominal coil consumption is 3 W. The integrated diode makes the coil polarity-sensitive, so the supply must be connected according to the manufacturer's terminal markings.

Does the Finder 62.33.9.024.4360 have changeover contacts?

No. The Finder 62.33.9.024.4360 has three normally open contacts (3 NO / 3PST-NO), not three changeover contacts. Each contact closes when the coil is energised and opens when the coil is de-energised. The contact gap is at least 3 mm.

Does the Finder 62.33.9.024.4360 include an LED indicator and flyback diode?

Yes. The relay includes an integrated LED indicator and a flyback suppression diode. The LED indicates coil energisation, while the diode helps limit voltage transients when the DC coil is switched off. Correct coil polarity is essential, and the relay does not include a manual test button.

What is the difference between Finder 62.33.9.024.4360 and 62.33.9.024.4060?

The 62.33.9.024.4360 has three normally open contacts with a minimum 3 mm gap and a 3 W, 125 mA coil. The 62.33.9.024.4060 has three changeover contacts and a lower-power coil. Both models use a 24 V DC supply and include LED indication and diode suppression, but they are not direct electrical substitutes.

Trusted by Industrial Automation Professionals Worldwide

The Finder 62.33.9.024.4360 combines a 24 V DC operating coil, three 16 A normally open contacts, a minimum 3 mm contact gap, silver tin oxide contact technology and integrated LED and diode functions. Its industrial construction makes it a versatile choice for automation engineers, electrical panel builders and maintenance professionals seeking reliable multi-circuit switching.