Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 62.33.8.120.4000 is a 16 A industrial plug-in power relay with a 120 V AC coil, three changeover contacts, silver tin oxide contact material and Faston 187 terminals for machinery, automation and electrical control applications.
£12.76
The Finder 62.33.8.120.4000 is a 16 A industrial plug-in power relay from the Finder 62 Series, designed for dependable electrical switching in industrial automation, machinery and control panel applications. Featuring a 120 V AC operating coil and three changeover contacts (3PDT / 3 CO), this relay enables three independent electrical circuits to be controlled simultaneously using a single alternating-current control signal.
Unlike two-pole relays, the Finder 62.33.8.120.4000 provides three independent changeover contact sets, each offering normally open and normally closed switching functions. This makes it particularly useful for applications involving multiple auxiliary circuits, electrical interlocking, control logic and coordinated equipment operation. Its silver tin oxide (AgSnO2) contacts provide a cadmium-free contact material suited to demanding industrial switching duties.
With a 16 A rated contact current, 250 V AC rated contact voltage and 4000 VA AC-1 switching capacity, the relay is suitable for appropriately rated industrial electrical loads. Its plug-in construction, Faston 187 quick-connect terminals and compatibility with selected Finder 92 Series sockets support convenient installation and maintenance. The standard 4000 configuration provides straightforward electromagnetic switching without an integrated LED indicator or manual test button.
The Finder 62.33.8.120.4000 operates through an electromagnetic coil that controls three independent changeover contacts. When the 120 V AC coil is energised, each common contact transfers from its normally closed position to its normally open position. When the coil supply is removed, all three contacts return to their normal positions. This 3PDT arrangement allows three circuits to be switched together, making it useful for auxiliary control, electrical interlocking, equipment sequencing and industrial automation applications.
The relay's three-pole contact arrangement offers greater switching flexibility than a two-pole relay without requiring multiple separate devices. Its Faston 187 terminals and plug-in construction allow straightforward replacement when used with an appropriately rated Finder 92 Series socket. The 120 V AC coil must be supplied from a compatible AC control circuit, and the switching capacity of each contact must be checked against the connected load. In particular, the 16 A AC contact rating must not be assumed to apply to high-voltage DC loads, which have substantially different breaking-capacity limits.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Terminal Type | Faston / flat-pin | |
| Load Voltage | 400 V AC | |
| Mounting Type | Plug-in socket | |
| Switching Current (A) | 16 A | |
| Manufacturer | Finder | |
| Series | 62 Series Power Relays | |
| Manufacturer part number | 62.33.8.120.4000 | |
| Product type | Industrial plug-in electromagnetic power relay | |
| Relay configuration | 62.33 | |
| Contact configuration | 3PDT / 3 CO | |
| Number of poles | 3 | |
| Contact arrangement | Three independent changeover circuits | |
| Rated contact current | 16 A | |
| Rated contact voltage | 250 V AC | |
| Maximum switching voltage | 400 V AC | |
| Maximum specified DC switching voltage | 220 V DC, subject to the DC breaking-capacity limits | |
| Rated switching load (AC-1) | 4000 VA | |
| Rated switching load (AC-15 at 230 V AC) | 750 VA | |
| Single-phase motor rating at 230 V AC | 0.8 kW | |
| DC-1 breaking capacity at 30 V DC | 16 A | |
| DC-1 breaking capacity at 110 V DC | 0.6 A | |
| DC-1 breaking capacity at 220 V DC | 0.4 A | |
| Minimum switching load | 1000 mW (10 V / 10 mA) | |
| Nominal coil voltage | 120 V AC | |
| Coil frequency | 50/60 Hz | |
| Coil type | AC, non-latching | |
| Nominal AC coil consumption | 2.2 VA | |
| Nominal coil current | Approximately 18.6 mA | |
| Nominal coil resistance | Approximately 1.94 kΩ | |
| Contact material | Silver tin oxide (AgSnO2) | |
| Mechanical endurance | 10 million operations under specified conditions | |
| Electrical endurance | 100,000 operations at the specified AC-1 rated load | |
| Typical operate time | Approximately 11–15 ms, depending on test conditions | |
| Operating temperature | −40 to +70 °C | |
| Coil-to-contact insulation | Reinforced | |
| Coil-to-contact clearance | 6 mm | |
| Coil-to-contact creepage distance | 8 mm | |
| Mounting type | Plug-in / socket mounting | |
| Compatible socket family | Finder 92 Series, subject to exact socket selection | |
| Terminal type | Faston 187 quick-connect terminals | |
| Terminal dimensions | 4.8 × 0.5 mm | |
| Number of terminals | 11 | |
| Approximate dimensions | 35.8 × 38.2 × 51.1 mm | |
| Manual test button | Not included in the standard 4000 configuration | |
| LED indicator | Not included in the standard 4000 configuration | |
| Relay operation | Electromagnetic, monostable | |
| Coil version code | 8 (AC coil) | |
| Contact material code | 4 (AgSnO2) | |
| Contact circuit code | 0 (changeover contacts) | |
| Option code | 0 (standard version without additional indication or test-button option) |
The Finder 62.33.8.120.4000 is a 16 A industrial plug-in power relay used for electrical switching in machinery, automation systems and control panels. It features a 120 V AC coil and three changeover contacts, enabling three independent circuits to be controlled simultaneously.
The relay requires a nominal 120 V AC supply at 50/60 Hz. Its nominal coil consumption is approximately 2.2 VA, with a coil current of approximately 18.6 mA. It is an AC-coil relay and should not be connected directly to a 120 V DC supply.
The relay features three independent changeover contacts (3PDT / 3 CO). Each pole has a common, normally closed and normally open connection, allowing three circuits to change state when the coil is energised. The relay has 11 terminals in total, including its two coil connections.
The main difference is the number of contact poles. The 62.33.8.120.4000 has three changeover contacts (3PDT), while the 62.32.8.120.4000 has two changeover contacts (DPDT). Both part numbers specify a 120 V AC coil and AgSnO2 contacts, but their terminal layouts and socket requirements differ.
The relay is designed for plug-in mounting using a compatible Finder 92 Series socket or suitable Faston 187 connections. Its quick-connect terminals measure 4.8 × 0.5 mm. The selected socket must support the three-pole contact configuration and the intended electrical ratings. Installation should follow Finder's current terminal identification and mounting instructions.
Finder 62 Series power relays provide dependable switching solutions for industrial machinery, automation systems and electrical control panels. With a 120 V AC operating coil, three independent changeover contacts, a 16 A rated contact current and silver tin oxide contact material, the Finder 62.33.8.120.4000 offers versatile switching performance for demanding control applications. Its plug-in construction and Faston 187 terminals support convenient installation, maintenance and replacement in compatible industrial equipment.