Finder 62.33.8.024.0000 is a 16 A plug-in electromagnetic power relay with a 24 V AC coil and three changeover contacts for industrial control and automation applications.
The Finder 62.33.8.024.0000 is a robust 16 A electromagnetic power relay designed for dependable switching in industrial automation, electrical control panels and power management systems. As part of the established Finder 62 Series, it combines three changeover contacts with a 24 V AC coil, allowing multiple electrical circuits to be controlled simultaneously.
This relay provides reinforced insulation between the coil and contacts in accordance with EN 60335-1, with 6 mm clearance and 8 mm creepage distance. Its durable construction, high switching capacity and plug-in configuration make it suitable for frequent control duties in demanding industrial environments.
With a rated contact current of 16 A, a rated switching voltage of 250 V AC and a maximum switching voltage of 400 V AC, the 62.33.8.024.0000 is suitable for controlling contactors, solenoid valves, lighting, heating equipment and industrial machinery. Its plug-in format supports Finder 92 Series sockets or direct connection through Faston 187 terminals.
Electromagnetic power relays such as the Finder 62.33.8.024.0000 allow a low-voltage control circuit to operate several higher-current electrical circuits. Its three changeover contacts provide normally open and normally closed switching paths, supporting flexible control logic in machinery, process equipment and automation systems.
The plug-in design allows the relay to be removed from a compatible Finder socket without rewiring the control panel. This helps reduce maintenance time and makes relay inspection or replacement more straightforward when servicing industrial equipment.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Mounting Type | Plug-in socket | |
| Switching Current (A) | 16 A | |
| Load Voltage | 400 V AC | |
| Contacts | 3 C/O | |
| HS Code | 85364900 | |
| Manufacturer | Finder | |
| Series | 62 Series | |
| Model | 62.33.8.024.0000 | |
| Product type | Electromagnetic power relay | |
| Contact configuration | 3 CO (3PDT) | |
| Rated contact current | 16 A | |
| Rated switching voltage | 250 V AC | |
| Maximum switching voltage | 400 V AC | |
| Rated load AC1 | 4,000 VA | |
| Rated load AC15 at 230 V AC | 750 VA | |
| Motor rating at 230/400 V AC | 0.8/1.5 kW | |
| DC1 breaking capacity at 24/110/220 V | 16/1.1/0.7 A | |
| Minimum switching load | 1,000 mW (10 V / 10 mA) | |
| Nominal coil voltage | 24 V AC | |
| Coil frequency | 50/60 Hz | |
| Coil current | 90 mA at 50 Hz | |
| Coil resistance | 74 Ω | |
| Rated coil power | 2.2 VA at 50 Hz | |
| Coil operating range | 19.2–26.4 V AC | |
| Contact material | AgCdO | |
| Mounting type | Plug-in / Faston 187 | |
| Terminal size | 4.8 × 0.5 mm | |
| Operate/release time | 11/4 ms | |
| Mechanical life | 10 million AC cycles | |
| Electrical life at rated AC1 load | 100,000 cycles | |
| Insulation between coil and contacts | 6 kV impulse withstand | |
| Dielectric strength between coil and contacts | 4,000 V AC | |
| Dielectric strength between open contacts | 1,500 V AC | |
| Environmental protection | RT I | |
| Ambient temperature range | −40 to +70 °C | |
| Dimensions (H × W × D) | 49.1 × 35.8 × 38.2 mm |
This power relay controls multiple electrical circuits in industrial machinery, automation systems and control panels using a 24 V AC control supply.
The relay has three changeover contacts in a 3PDT configuration, providing normally open and normally closed switching paths across three poles.
The Finder 62.33.8.024.0000 has a rated contact current of 16 A and a rated switching voltage of 250 V AC.
This model uses a 24 V AC coil designed for operation at 50/60 Hz, with a rated coil power of 2.2 VA at 50 Hz.
The relay can be installed in a compatible Finder 92 Series socket or connected directly using its 4.8 × 0.5 mm Faston 187 terminals.
Finder 62 Series power relays are widely used by control panel builders, automation engineers and equipment manufacturers for dependable high-current switching and straightforward integration into industrial electrical systems.