62.32.9.110.4006 Finder Power relay 2pole 16A DC 110VNO

62.32.9.110.4006 Finder Power relay 2pole 16A DC 110VNO

Finder 62.32.9.110.4006 is a 62 Series electromechanical power relay featuring a 110 V DC coil, two 16 A changeover contacts, silver tin oxide contact material, rear flange mounting and Faston 187 quick-connect terminals. Suitable for industrial automation, machinery control and electrical switching applications.

SKU: 62.32.9.110.4006Alt SKU: 623291104006MPN: 62.32.9.110.4006
Price on application Contact us for pricing and availability.
Call 01708 343600

Why Choose the Finder 62.32.9.110.4006 Power Relay?

The Finder 62.32.9.110.4006 is a robust 16 A two-pole electromechanical power relay designed for dependable electrical switching in industrial automation, machinery control and electrical control equipment. Part of the established Finder 62 Series, this model combines a 110 V DC operating coil, two changeover contacts and a rear flange mounting arrangement, making it suitable for applications requiring secure mechanical installation.

Featuring a 2 CO (DPDT) contact configuration, the Finder 62.32.9.110.4006 enables two independent electrical circuits to be switched simultaneously using a single control signal. Each changeover contact provides common, normally open and normally closed connections, offering flexibility for electrical interlocking, auxiliary power switching, signalling and industrial control logic. Its silver tin oxide (AgSnO2) contacts provide good resistance to contact welding and support reliable operation with appropriately rated electrical loads.

A distinguishing feature of the Finder 62.32.9.110.4006 is its rear flange mounting configuration, identified by the final digit 6 in the manufacturer part number. This mounting arrangement provides an additional installation option for machinery and industrial equipment. Combined with a 16 A contact rating, 4,000 VA resistive switching capacity, Faston 187 quick-connect terminals and reinforced insulation between coil and contacts, the relay is a practical choice for industrial panel builders, electrical engineers and equipment maintenance professionals.

Key Advantages

  • 16 A electromechanical power relay for industrial electrical switching applications.
  • 110 V DC operating coil suitable for compatible DC control systems.
  • Two changeover contacts (2 CO / DPDT) enable simultaneous switching of two independent circuits.
  • Rear flange mounting configuration supports secure mechanical installation in industrial equipment.
  • 250 V AC rated contact voltage for appropriately rated electrical loads.
  • 4,000 VA rated resistive switching capacity (AC1).
  • Silver tin oxide (AgSnO2) contacts provide resistance to contact welding.
  • Faston 187 quick-connect terminals support convenient electrical connections.
  • Reinforced insulation between coil and contacts supports separation of control and load circuits.
  • Monostable operation automatically returns the contacts to their normal positions when the coil is de-energised.
  • Standard configuration without integrated electronic coil accessories allows external suppression to be selected according to the application.
  • Industrial-grade construction suitable for machinery, control panels and auxiliary switching equipment.

Key Features

  • Finder 62 Series industrial power relay.
  • 62.32 two-pole relay configuration.
  • 110 V DC nominal coil voltage.
  • Direct-current electromagnetic coil operation.
  • Two changeover contacts (2 CO / DPDT).
  • 16 A rated contact current.
  • 250 V AC rated contact voltage.
  • 400 V AC maximum switching voltage.
  • 4,000 VA rated resistive switching load (AC1).
  • 750 VA rated AC15 switching load at 230 V AC.
  • Silver tin oxide (AgSnO2) contact material.
  • 110 V DC coil operating range of 88–121 V DC.
  • 9,420 Ω nominal coil resistance.
  • 11.7 mA nominal coil current.
  • Rear flange mounting for mechanical attachment.
  • Faston 187 quick-connect terminals measuring 4.8 × 0.5 mm.
  • Reinforced coil-to-contact insulation.
  • 6 kV rated impulse withstand voltage between coil and contacts.
  • Monostable electromagnetic switching.
  • Cadmium-free AgSnO2 contact material.
  • No integrated LED, test button or flyback diode in the standard 4006 configuration.

Reliable 110 V DC Switching with Rear Flange Mounting

The Finder 62.32.9.110.4006 uses an electromagnetic switching mechanism to control two independent changeover contacts. When the 110 V DC coil is energised, the internal armature transfers both common contacts from their normally closed positions to their normally open positions. This allows a single DC control signal to switch two separate electrical circuits. When the coil supply is removed, the contacts return automatically to their normal positions, providing conventional monostable operation.

The rear flange mounting arrangement distinguishes this version from the otherwise similar Finder 62.32.9.110.4000. The final digit 6 specifies the rear flange mounting option, while the 4000 version uses the standard mounting configuration. This distinction is important when selecting a replacement relay or designing a mounting arrangement. The relay's Faston 187 terminals support convenient electrical connection, and its reinforced coil-to-contact insulation provides electrical separation between the control circuit and switched loads. Where electronic outputs drive the coil, suitable external transient suppression should be considered because this version does not incorporate a flyback diode.

Typical Applications

  • Industrial automation and machinery control systems.
  • 110 V DC electrical control circuits.
  • Industrial machinery requiring rear flange relay mounting.
  • Electrical control panels and industrial switching assemblies.
  • Auxiliary power switching and electrical control circuits.
  • Electrical interlocking and multi-circuit control systems.
  • Industrial signalling and monitoring equipment.
  • Motor control and contactor auxiliary circuits within specified ratings.
  • Industrial process control and manufacturing machinery.
  • Control of actuators, contactors and auxiliary electrical equipment.
  • OEM industrial equipment and machinery manufacturing.
  • Maintenance and replacement of compatible rear flange mounted Finder 62 Series relays.

Technical Specifications

Tick the specs you need, then view products that match.

Device Type Power Relay
Terminal Type Faston / flat-pin
Switching Current (A) 16 A
Load Voltage 400 V AC
Manufacturer Finder
Series 62 Series Power Relays
Manufacturer part number 62.32.9.110.4006
Product type Electromechanical power relay
Relay configuration 2 CO / DPDT
Number of poles 2
Contact arrangement Two independent changeover contacts
Nominal coil voltage 110 V DC
Coil supply type Direct current (DC)
Coil operating voltage range 88–121 V DC
Nominal coil resistance 9,420 Ω
Nominal coil current 11.7 mA
Nominal coil consumption Approximately 1.3 W
Relay operating mode Monostable / non-latching
Rated contact current 16 A
Rated contact voltage 250 V AC
Maximum switching voltage 400 V AC
Rated resistive load (AC1) 4,000 VA
Rated AC15 load at 230 V AC 750 VA
Single-phase motor rating at 230 V AC 0.8 kW
DC1 breaking capacity at 24 V DC 16 A
DC1 breaking capacity at 110 V DC 0.6 A
DC1 breaking capacity at 220 V DC 0.4 A
Minimum switching load 1,000 mW
Contact material Silver tin oxide (AgSnO2)
Contact material characteristic Cadmium-free
Mechanical durability 30 million operations for the DC coil version
Electrical durability at rated AC1 load 100,000 operations
Typical operating time 11 ms
Typical release time 4 ms
Rated impulse withstand voltage between coil and contacts 6 kV
Dielectric strength between coil and contacts 4,000 V AC
Dielectric strength between open contacts 1,500 V AC
Coil-to-contact insulation Reinforced
Coil-to-contact clearance 6 mm
Coil-to-contact creepage distance 8 mm
Operating temperature −40 to +70 °C
Environmental protection category RT I
Mounting configuration Rear flange mount
Terminal type Faston 187 quick-connect
Terminal dimensions 4.8 × 0.5 mm
Integrated LED indicator Not included
Integrated flyback diode Not included
Manual test button Not included
Mechanical flag indicator Not included
Operating principle Electromagnetic switching
Typical applications Industrial automation, machinery control, electrical interlocking and auxiliary power switching

Frequently Asked Questions

What is the Finder 62.32.9.110.4006 used for?

The Finder 62.32.9.110.4006 is a two-pole electromechanical power relay used for switching electrical circuits in industrial automation, machinery control and electrical equipment. Its two changeover contacts allow two independent circuits to be controlled simultaneously using a single 110 V DC control signal. The rear flange mounting arrangement supports secure installation in suitable machinery and control assemblies.

What coil voltage does the Finder 62.32.9.110.4006 require?

The relay requires a 110 V DC nominal coil supply. Its specified operating voltage range is 88–121 V DC, with a nominal coil current of 11.7 mA and approximately 1.3 W coil consumption. It is designed for DC control circuits and should not be connected directly to a 110 V AC supply.

What is the contact rating of the Finder 62.32.9.110.4006?

The relay features a 16 A rated contact current, a 250 V AC rated contact voltage and a 4,000 VA rated resistive switching capacity (AC1). DC switching capacities depend on voltage and load characteristics; for example, the specified DC1 breaking capacity at 110 V DC is 0.6 A.

What is the difference between Finder 62.32.9.110.4006 and 62.32.9.110.4000?

Both models feature a 110 V DC coil, two 16 A changeover contacts and silver tin oxide contact material. The key difference is the mounting arrangement: the 62.32.9.110.4006 features rear flange mounting, while the 62.32.9.110.4000 is the standard mounting version. The correct model should be selected according to the equipment's mechanical installation requirements.

Does the Finder 62.32.9.110.4006 include an LED indicator or flyback diode?

No. The 62.32.9.110.4006 is supplied without an integrated LED indicator, flyback diode, mechanical flag or manual test button. Its final digit identifies the rear flange mounting option rather than an electronic accessory. Where coil indication or transient suppression is required, an appropriate external solution should be selected.

Trusted by Industrial Automation Professionals Worldwide

Finder 62 Series power relays are designed for dependable electrical switching in industrial automation, machinery and electrical control equipment. The Finder 62.32.9.110.4006 combines a 110 V DC operating coil, two 16 A changeover contacts, silver tin oxide contact technology and rear flange mounting, making it a practical choice for electrical engineers, industrial panel builders and machinery maintenance professionals.