Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 62.32.8.120.4050 is a 62 Series plug-in electromechanical power relay featuring a 120 V AC coil, two 16 A changeover contacts, silver tin oxide contact material, Faston 187 terminals, an integrated LED indicator and a lockable test button for industrial automation and electrical control applications.
The Finder 62.32.8.120.4050 is a high-performance 16 A two-pole electromechanical power relay designed for reliable electrical switching in industrial automation, machinery control and electrical distribution equipment. Part of the established Finder 62 Series, this model features a 120 V AC operating coil, two changeover contacts and a plug-in mounting arrangement that supports convenient installation and maintenance.
Featuring a 2 CO (DPDT) contact configuration, the relay allows two independent electrical circuits to be switched simultaneously using a single control signal. Each changeover contact provides common, normally open and normally closed connections, offering flexibility for industrial control logic, electrical interlocking and auxiliary switching. Its silver tin oxide (AgSnO2) contact material provides good resistance to contact welding and supports dependable operation with appropriately rated electrical loads.
A key advantage of the Finder 62.32.8.120.4050 is its combination of a lockable manual test button and integrated LED indicator. The test button enables controlled manual operation during commissioning and maintenance, while the LED provides visual indication of coil energisation. Together with Faston 187 quick-connect terminals and compatibility with suitable Finder 92 Series relay sockets, this relay is a practical choice for industrial control panels where switching reliability, visual diagnostics and convenient replacement are important.
The Finder 62.32.8.120.4050 uses an electromagnetic operating mechanism to control two independent changeover contacts. When the 120 V AC coil is energised, the internal armature transfers the common terminals from their normally closed positions to their normally open positions. Both poles operate together, allowing a single control signal to manage two separate circuits. When the coil is de-energised, the contacts return to their normal positions.
The integrated LED indicator and lockable test button make this model particularly useful in industrial control panels where clear status indication and convenient maintenance are important. The LED helps technicians identify when the coil is energised, while the test button permits manual contact operation for commissioning and fault-finding. The plug-in Faston terminal arrangement also supports convenient relay replacement when used with an appropriately selected Finder 92 Series socket. Manual testing and maintenance must be performed by competent personnel using suitable electrical safety procedures.
Tick the specs you need, then view products that match.
| Device Type | Power Relay | |
|---|---|---|
| Terminal Type | Faston / flat-pin | |
| Load Voltage | 400 V AC | |
| Mounting Type | Plug-in socket | |
| Switching Current (A) | 16 A | |
| Manufacturer | Finder | |
| Series | 62 Series Power Relays | |
| Manufacturer part number | 62.32.8.120.4050 | |
| Product type | Electromechanical power relay | |
| Relay configuration | 2 CO / DPDT | |
| Number of poles | 2 | |
| Contact arrangement | Two independent changeover contacts | |
| Nominal coil voltage | 120 V AC | |
| Coil supply type | Alternating current (AC) | |
| Coil frequency | 50/60 Hz | |
| Coil operating voltage range | 96–132 V AC | |
| Nominal coil consumption | 2.2 VA | |
| Nominal coil current | 18.6 mA | |
| Coil resistance | Approximately 1.94 kΩ | |
| Relay operating mode | Monostable / non-latching | |
| Rated contact current | 16 A | |
| Rated contact voltage | 250 V AC | |
| Maximum switching voltage | 400 V AC | |
| Rated resistive load (AC1) | 4,000 VA | |
| Rated AC15 load at 230 V AC | 750 VA | |
| Single-phase motor rating at 230 V AC | 0.8 kW | |
| DC1 breaking capacity at 24 V DC | 16 A | |
| DC1 breaking capacity at 110 V DC | 0.6 A | |
| DC1 breaking capacity at 220 V DC | 0.4 A | |
| Contact material | Silver tin oxide (AgSnO2) | |
| Mechanical durability | 10 million operations for AC coil versions | |
| Electrical durability at rated AC1 load | 100,000 operations | |
| Typical operating time | 11 ms | |
| Typical release time | 4 ms | |
| Rated impulse withstand voltage between coil and contacts | 6 kV | |
| Dielectric strength between open contacts | 1,500 V AC | |
| Coil-to-contact insulation | Reinforced | |
| Coil-to-contact clearance | 6 mm | |
| Coil-to-contact creepage distance | 8 mm | |
| Operating temperature | −40 to +70 °C | |
| Environmental protection category | RT I | |
| Manual test function | Lockable test button | |
| Electrical status indication | Integrated LED indicator | |
| Mounting type | Plug-in / quick-connect | |
| Terminal type | Faston 187 | |
| Terminal dimensions | 4.8 × 0.5 mm | |
| Number of electrical terminals | 8 | |
| Compatible socket family | Finder 92 Series, subject to socket selection | |
| Operating principle | Electromagnetic switching | |
| Typical applications | Industrial automation, machinery control, electrical interlocking and auxiliary power switching |
The Finder 62.32.8.120.4050 is a two-pole electromechanical power relay used for switching electrical circuits in industrial automation, machinery control and electrical panels. Its two changeover contacts control two independent circuits, while its LED indicator and lockable test button support commissioning and maintenance.
The relay requires a 120 V AC nominal coil supply operating at 50/60 Hz. Its specified operating voltage range is 96–132 V AC. It is intended for compatible AC control circuits and must not be connected directly to a 120 V DC supply.
The relay features a 16 A rated contact current, a 250 V AC rated contact voltage and a 4,000 VA rated resistive switching capacity (AC1). The permissible load depends on the switching voltage, load characteristics and installation conditions.
The LED indicator provides a visual indication that the relay coil is energised. The lockable test button allows the contacts to be operated manually for commissioning and diagnostic purposes. Manual operation should only be performed by competent personnel under suitable electrical safety conditions.
The relay features Faston 187 quick-connect terminals measuring 4.8 × 0.5 mm and can be installed using a suitably selected Finder 92 Series relay socket. This plug-in arrangement supports convenient installation in industrial control panels and straightforward replacement during maintenance.
Finder 62 Series power relays provide dependable electrical switching for industrial automation, machinery and control equipment. The Finder 62.32.8.120.4050 combines a 120 V AC coil, two 16 A changeover contacts, silver tin oxide contact technology, an integrated LED indicator and a lockable manual test button, making it a practical choice for electrical engineers, industrial panel builders and maintenance professionals.