Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 55.34.9.048.0000T industrial plug-in relay featuring a 48 V DC coil, 7 A rated contacts, four changeover contacts (4PDT), silver nickel contact material, integrated LED indication and monostable operation for industrial automation and electrical control applications.
£14.53
The Finder 55.34.9.048.0000T is a versatile 7 A, four-pole industrial electromechanical relay designed for electrical control panels, industrial automation, machinery and general-purpose switching applications. Part of the established Finder 55 Series, this miniature plug-in relay combines a 48 V DC coil, four independent changeover contacts and convenient socket-mounted construction.
Featuring a 4PDT (four-pole double-throw / 4 CO) contact configuration, the Finder 55.34.9.048.0000T allows four separate electrical circuits to be switched using a single control signal. Each contact set provides normally open, normally closed and common connections, making the relay particularly useful for auxiliary control, status signalling, equipment interlocking and multi-circuit switching.
This version is identified with an integrated LED indicator, helping technicians recognise when the relay's control supply is present. Its silver nickel (AgNi) contacts, 7 A rated switching current and compact 20.7 × 37.2 × 27.7 mm housing make it a practical choice for industrial electricians, control panel builders, maintenance engineers and OEM equipment manufacturers.
The Finder 55.34.9.048.0000T provides four independent changeover contact sets operated by a single 48 V DC electromagnetic coil. This arrangement is particularly useful where multiple control functions need to respond to the same switching signal.
Each contact set includes a common terminal, a normally closed terminal and a normally open terminal. When the relay coil is energised, each common contact transfers from its normally closed connection to its normally open connection. When coil power is removed, the contacts return to their normal positions.
The 4PDT configuration allows designers to control several circuits simultaneously. For example, one contact may be used for auxiliary load switching, another for status signalling and additional contacts for electrical control functions. All contact sets must remain within their specified voltage, current and load-category ratings.
Using a single four-pole relay can simplify control panel wiring compared with using multiple single-pole relays, while providing coordinated switching from one control input.
The 55.34.9.048.0000T version includes an LED indicator, providing a convenient visual reference for the relay's control supply. This can be particularly useful during electrical panel commissioning, routine inspection and troubleshooting.
When checking an industrial control circuit, the LED helps technicians determine whether the relay is receiving its intended control signal. This can assist with identifying issues such as missing control voltage, incorrect wiring or faults elsewhere in the control system.
The LED indicates the electrical control condition and should not be treated as independent confirmation that the relay contacts have physically changed state. Where contact-state verification is required, suitable feedback circuitry and testing procedures should be used.
The 48 V DC coil is designed for compatible industrial DC control systems. Its nominal resistance of 2.4 kΩ results in a rated current of approximately 20 mA, corresponding to approximately 1 W of coil consumption.
The standard operating range for the 48 V DC coil is approximately 38.4–52.8 V DC, subject to the manufacturer's specified operating conditions. This range should be considered when selecting a control power supply and assessing voltage variations within the installation.
The relay uses monostable operation, meaning the contacts return to their normal positions when the coil is de-energised. This makes the Finder 55.34.9.048.0000T suitable for general-purpose switching, signalling and auxiliary control functions where predictable contact operation is required.
The Finder 55.34.9.048.0000T is designed for plug-in socket mounting, allowing the relay to be installed in a compatible socket without direct soldering. This arrangement is especially useful in industrial control panels where relays may require inspection, testing or replacement during maintenance.
Compatible Finder 94 Series sockets provide options for electrical panel installation, depending on the selected socket and mounting arrangement. Engineers should verify the socket's compatibility with the 55.34 relay, including its contact rating, terminal arrangement and intended installation method.
The compact 20.7 × 37.2 × 27.7 mm housing helps reduce the space required for four-pole switching. The plug-in construction also supports faster replacement of a compatible relay without rewiring the entire control circuit, provided the equipment has been safely isolated.
Tick the specs you need, then view products that match.
| Device Type | Plug-in Relay | |
|---|---|---|
| Mounting Type | Plug-in socket | |
| Switching Current (A) | 7 A | |
| Manufacturer | Finder | |
| Series | 55 Series General-Purpose Relays | |
| Relay type | 55.34 | |
| Manufacturer part number | 55.34.9.048.0000T | |
| Alternative reference | 553490480000T | |
| Product category | Industrial plug-in electromechanical relay | |
| Relay technology | Electromechanical | |
| Contact configuration | Four-pole double-throw (4PDT / 4 CO / 4 Form C) | |
| Number of poles | 4 | |
| Number of changeover contacts | 4 | |
| Normally open contacts | 4, one within each changeover set | |
| Normally closed contacts | 4, one within each changeover set | |
| Common contact terminals | 4 | |
| Nominal coil voltage | 48 V DC | |
| Coil supply type | DC | |
| Nominal coil resistance | 2,400 Ω (2.4 kΩ) | |
| Nominal coil current | 20 mA | |
| Nominal coil consumption | Approximately 1 W | |
| Standard DC coil operating range | 38.4–52.8 V DC | |
| Control input polarity | Polarity-free | |
| Rated contact current | 7 A | |
| Rated contact voltage | 250 V AC | |
| Rated resistive switching capacity (AC1) | 1,750 VA | |
| Rated inductive switching capacity (AC15 at 230 V AC) | 350 VA, standard 55.34 series rating | |
| Contact material | Silver nickel (AgNi) | |
| Contact surface | Unplated | |
| LED indication | Yes | |
| Relay operating mode | Monostable / non-latching | |
| Mounting type | Plug-in socket mounting | |
| Electrical connection | Plug-in terminals | |
| Terminal arrangement | 14-pin | |
| Compatible socket family | Finder 94 Series, subject to the selected socket type | |
| Environmental protection | RT I | |
| Operating ambient temperature | −40 to +85 °C | |
| Housing width | 20.7 mm | |
| Housing height | 37.2 mm | |
| Housing depth | 27.7 mm | |
| Housing dimensions | 20.7 × 37.2 × 27.7 mm | |
| Approximate product weight | 40 g | |
| EAN / GTIN | 8012823430904 | |
| Typical applications | Industrial automation, auxiliary switching, electrical control panels and machinery |
The Finder 55.34.9.048.0000T is a four-pole industrial plug-in relay used for electrical switching in automation systems, machinery and control panels. It features a 48 V DC coil, four changeover contacts and a 7 A rated contact current.
The relay requires a 48 V DC nominal coil supply. Its nominal coil resistance is 2.4 kΩ, and its rated coil current is approximately 20 mA. The standard operating voltage range is approximately 38.4–52.8 V DC, subject to the manufacturer's operating conditions.
4PDT means four-pole double-throw, also described as 4 CO or four changeover contacts. The relay contains four independent contact sets, each with a common, normally open and normally closed connection. All four sets operate together when the coil is energised.
Yes. This version is specified with an integrated LED indicator that provides visual indication of the control supply. The LED can help technicians during commissioning and fault diagnosis, although it does not independently verify the mechanical position of the contacts.
The Finder 55.34.9.048.0000T is designed for plug-in socket mounting and can be used with an appropriately selected compatible Finder 94 Series socket. The relay itself is not a complete DIN rail interface assembly; DIN rail installation depends on the socket chosen. Always follow Finder's terminal diagram and applicable electrical safety requirements.
Finder 55 Series general-purpose relays provide versatile electromechanical switching solutions for industrial automation, electrical control and OEM equipment. The Finder 55.34.9.048.0000T combines a 48 V DC coil, four changeover contacts, a 7 A contact rating, silver nickel contacts, LED indication and convenient plug-in construction, making it a practical component for control panel builders, maintenance engineers and industrial automation professionals.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.