Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 50.12.9.110.5000 force-guided electromechanical safety relay featuring a 110 V DC coil, 8 A rated contacts, two DPDT changeover contact sets, gold-plated silver nickel contacts and PCB through-hole mounting for industrial control and safety-related monitoring applications.
£13.06
The Finder 50.12.9.110.5000 is a high-performance 8 A force-guided electromechanical relay designed for industrial control, machinery monitoring and safety-related switching applications. Part of the Finder 50 Series, this compact PCB-mounted relay combines a 110 V DC coil, two changeover contacts and mechanically linked contact operation in a robust industrial component.
Featuring a double-pole double-throw (DPDT / 2 CO) contact configuration, the Finder 50.12.9.110.5000 provides two changeover contact sets for appropriately designed control and monitoring circuits. Its force-guided contact mechanism is particularly valuable in applications where the relationship between normally open and normally closed contact positions must remain mechanically constrained, including safety monitoring and fault-detection systems.
The relay incorporates silver nickel contacts with gold plating (AgNi + Au), a 700 mW nominal DC coil and 6 kV coil-to-contact impulse withstand insulation. With compact dimensions of approximately 29 × 12.4 × 25 mm, through-hole PCB mounting and an operating temperature range of −40 to +70 °C, it offers a practical solution for OEM manufacturers, automation engineers and designers of industrial control equipment.
A distinguishing feature of the Finder 50.12.9.110.5000 is its force-guided contact construction. Unlike conventional general-purpose relays, force-guided relays use a mechanical arrangement that constrains the relative movement of normally open and normally closed contacts. This arrangement can support the detection of certain contact faults when the relay is incorporated into a properly designed monitoring circuit.
The relay provides two changeover contact sets, allowing control and feedback functions to be incorporated into the same compact component. In a suitable safety-related design, these contacts may be used as part of a monitoring strategy intended to identify abnormal switching conditions. However, the relay itself is not a complete safety controller; the required safety performance depends on the overall circuit architecture, diagnostics, protective measures and applicable machinery safety standards.
For applications requiring functional safety, designers should assess the complete system against relevant requirements and verify the manufacturer's current contact-guidance and approval documentation for the exact part number.
The 110 V DC electromagnetic coil allows the Finder 50.12.9.110.5000 to be operated from compatible DC control circuits. With a nominal resistance of 17.25 kΩ and power consumption of approximately 700 mW, the coil provides a practical balance between operating power and electromechanical switching performance.
When the coil is energised, the relay transfers its changeover contacts from their normal positions. Removing the coil voltage allows the contacts to return to their de-energised positions. The specified 10 ms operate time and 4 ms release time make it suitable for appropriately designed industrial control and monitoring functions.
The PCB through-hole construction, 5 mm terminal pitch and compact 29 × 12.4 × 25 mm housing support integration into dedicated electronic assemblies. Engineers should follow the manufacturer's PCB footprint, soldering guidance and recommended coil suppression practices when designing the surrounding circuitry.
Tick the specs you need, then view products that match.
| Device Type | Positively Guided Relay | |
|---|---|---|
| Timing Function | None (instantaneous) | |
| Switching Current (A) | 8 A | |
| Load Voltage | 400 V AC | |
| Mounting Type | PCB | |
| Terminal Type | PCB / pins | |
| Manufacturer | Finder | |
| Series | 50 Series | |
| Relay type | 50.12 | |
| Manufacturer part number | 50.12.9.110.5000 | |
| Product category | Force-guided safety relay | |
| Relay technology | Electromechanical | |
| Contact configuration | DPDT / 2 CO / 2 Form C | |
| Number of poles | 2 | |
| Number of changeover contacts | 2 | |
| Contact guidance | Mechanically force-guided | |
| Nominal coil voltage | 110 V DC | |
| Coil supply type | DC | |
| Nominal coil resistance | 17.25 kΩ | |
| Nominal coil current | Approximately 6.4 mA | |
| Nominal coil power | Approximately 700 mW | |
| Must-operate voltage | 82.5 V DC | |
| Must-release voltage | 11 V DC | |
| Rated contact current | 8 A | |
| Maximum contact current | 15 A, subject to the manufacturer's applicable switching conditions | |
| Rated resistive AC load | 8 A at 250 V AC | |
| Rated resistive DC load | 8 A at 24 V DC | |
| Maximum switching voltage (AC) | 400 V AC | |
| Maximum switching voltage (DC) | 220 V DC, subject to the DC load characteristic | |
| Contact material | Silver nickel with gold plating (AgNi + Au) | |
| Contact arrangement | Two changeover contacts with mechanically guided operation | |
| Relay operating mode | Monostable / non-latching | |
| Typical operate time | 10 ms | |
| Typical release time | 4 ms | |
| Coil-to-contact impulse withstand voltage | 6 kV | |
| Coil-to-contact dielectric strength | 4,000 V AC | |
| Dielectric strength between open contacts | 1,500 V AC | |
| Operating ambient temperature | −40 to +70 °C | |
| Mounting type | PCB through-hole | |
| Terminal type | Solder pins | |
| Terminal pitch | 5 mm | |
| Number of terminals | 8 | |
| Length | 29 mm | |
| Width | 12.4 mm | |
| Height | 25 mm | |
| Environmental protection | Flux-protected relay construction | |
| Typical application | Safety-related monitoring and industrial control circuits |
The Finder 50.12.9.110.5000 is a force-guided electromechanical relay used in industrial control, machinery monitoring and safety-related switching applications. It features a 110 V DC coil and two changeover contacts with mechanically guided operation.
The relay uses a 110 V DC nominal coil with approximately 700 mW nominal power consumption. Its nominal coil resistance is 17.25 kΩ, corresponding to approximately 6.4 mA at the rated voltage. It must not be connected directly to a 110 V AC supply.
Force-guided contacts are mechanically linked so that normally open and normally closed contacts cannot assume certain contradictory closed states, including under specified contact-fault conditions. This supports fault monitoring in properly designed safety-related circuits. It does not, by itself, make the relay a complete certified safety system.
The Finder 50.12.9.110.5000 has a rated contact current of 8 A for specified resistive switching conditions. Distributor information also identifies a higher maximum contact current of 15 A, but this must not be treated as the continuous rated switching current. Always use the manufacturer's load-specific ratings when designing the circuit.
The relay is designed for PCB through-hole mounting using solder-pin terminals. Its housing measures approximately 29 × 12.4 × 25 mm, with a 5 mm terminal pitch. Installation should follow Finder's PCB footprint, terminal diagram, soldering requirements and electrical safety guidance.
Finder 50 Series force-guided relays are designed for applications where dependable electromechanical switching and contact-state monitoring are important. The Finder 50.12.9.110.5000 combines a 110 V DC coil, two mechanically guided changeover contacts, gold-plated silver nickel contact surfaces and compact PCB mounting, making it a practical component for industrial automation engineers, OEM equipment designers and developers of safety-related control systems.