Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB T16-0.55 thermal overload relay with adjustable 0.41 to 0.55 A current range designed for motor overload and phase failure protection in industrial automation systems.
£33.90
The ABB 1SAZ711201R1017, also known as the T16-0.55 Thermal Overload Relay, is a compact and dependable electromechanical motor protection relay designed to protect three-phase motors against overload conditions and phase failure. As part of the trusted ABB T16 Thermal Overload Relay series, it delivers reliable motor protection, helping to maximise equipment uptime and extend motor service life.
The T16-0.55 incorporates Trip Class 10 protection, temperature compensation, selectable automatic or manual reset, phase loss sensitivity, integrated STOP and TEST functions, and a clear trip indication. Designed for direct mounting onto compatible ABB mini and block contactors, it provides fast installation and dependable performance within industrial motor starter assemblies.
With an adjustable current setting range of 0.41 to 0.55 A, the ABB 1SAZ711201R1017 is ideal for protecting small three-phase motors used in conveyors, pumps, compressors, fans, OEM machinery and industrial automation systems.
Thermal overload relays continuously monitor motor current and disconnect the motor circuit whenever prolonged overload conditions occur. This protects motors against overheating, reduces unplanned downtime and helps maximise the operational life of industrial equipment.
The ABB T16 series combines dependable overload protection, phase failure detection and straightforward installation, making it an excellent solution for industrial motor starters, machine builders and OEM automation equipment.
Tick the specs you need, then view products that match.
| Compatible With | AS09–AS16, B6–B7 | |
|---|---|---|
| Mounting Type | Direct mount on contactor | |
| Device Type | Thermal Overload Relay | |
| Current Range | 0.41–0.55 A | |
| Trip Class | Class 10 | |
| Current | 0.55 A | |
| Phase | Three Phase | |
| IP Rating | IP20 | |
| Series | T16 Thermal Overload Relays | |
| Product code | 1SAZ711201R1017 | |
| Product type | Thermal overload relay | |
| Setting range | 0.41–0.55 A | |
| Rated operational current AC-3 | 0.55 A | |
| Trip class | Class 10 | |
| Number of protected poles | 3 | |
| Auxiliary contacts | 1 NO + 1 NC | |
| Rated operational voltage main circuit | 690 V AC | |
| Rated insulation voltage | 690 V | |
| Rated impulse withstand voltage | 6 kV | |
| Control circuit voltage | 600 V AC/DC | |
| Frequency | 50 / 60 Hz | |
| Degree of protection | IP20 | |
| Connection type | Screw terminals | |
| Mounting type | Direct mounting to contactor | |
| Width | 45 mm | |
| Height | 76.7 mm | |
| Depth | 53.5 mm | |
| Weight | approx. 0.10 kg | |
| Ambient operating temperature | -25 °C to +60 °C | |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, IEC/EN 60947-5-1 |
It protects three-phase electric motors against overload conditions and phase failure in industrial motor control systems.
The relay has an adjustable overload setting range of 0.41 to 0.55 A.
The ABB T16-0.55 features a Trip Class 10 characteristic for dependable motor protection.
Yes. The relay supports both manual and automatic reset modes.
It is designed for direct mounting onto compatible ABB B6, BC6, B7, BC7, VB6, VBC6, VB7, VBC7 and AS09 to AS16 contactors.
ABB T16 thermal overload relays are trusted by machine builders and maintenance engineers for dependable motor protection, reliable overload detection and long-term industrial performance.