11RFA905 - T/O RELAY RFA9 0.3-0.5A

11RFA905 – T/O RELAY RFA9 0.3-0.5A

Lovato 11RFA905 is a three-pole thermal motor protection relay with a 0.3–0.5 A adjustable current range, automatic reset and phase failure sensitivity for direct mounting on BG06, BG09 and BG12 mini-contactors.

SKU: 11RFA905Alt SKU: RFA905MPN: 11RFA905
Price
List Price £73.99 ex VAT
Your Price (ex VAT) Save 40%
£44.40 40% OFF
You save £29.60 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £44.40
Trade pricing is personalised to your account

Manufacturer Lead Time

£44.40

Why Choose the Lovato 11RFA905 Thermal Overload Relay?

The Lovato 11RFA905 is a compact and reliable thermal motor protection relay designed to protect three-phase motors against overload and phase failure conditions. As part of the Lovato 11RFA9 motor protection relay series, it combines thermal overload protection with phase failure sensitivity and automatic resetting for dependable motor protection in industrial control applications.

Designed for direct mounting on Lovato BG06, BG09 and BG12 mini-contactors, the 11RFA905 enables a compact motor starter assembly without requiring separate relay mounting. Its Class 10A tripping characteristic, integrated test button and trip indicator provide practical motor protection and straightforward fault identification.

With an adjustable operational current range of 0.3–0.5 A and a rated operational voltage of up to 690 V, the 11RFA905 is suitable for protecting small three-phase motors. Its IP20 frontal protection and robust industrial design support reliable operation in machinery, automation equipment and electrical control panels.

Key Advantages

  • Reliable thermal overload protection for three-phase motors.
  • 0.3–0.5 A adjustable operational current range for small motor applications.
  • Integrated phase failure sensitivity for enhanced motor protection.
  • Automatic reset supports convenient system operation.
  • Direct mounting on Lovato BG06, BG09 and BG12 mini-contactors.
  • Integrated test button and trip indicator simplify testing and fault identification.

Key Features

  • Lovato 11RFA9 motor protection relay series.
  • 0.3–0.5 A operational current range.
  • Three-pole thermal motor protection relay.
  • Phase failure and single-phase sensitive operation.
  • Automatic reset mode.
  • Class 10A tripping characteristic.
  • Integrated test button and trip indicator.
  • Direct mounting on BG06, BG09 and BG12 mini-contactors.

Reliable Motor Protection for Industrial Machinery

Thermal overload relays such as the Lovato 11RFA905 protect electric motors by responding to sustained overcurrent conditions that can cause excessive heating and equipment damage. Phase failure sensitivity provides additional protection when abnormal phase conditions occur in a three-phase motor circuit.

The 11RFA905 is designed to integrate directly with compatible Lovato BG mini-contactors, creating a compact motor starter assembly. Its automatic reset function, Class 10A tripping characteristic, test button and trip indicator make it well suited to industrial machinery, automation equipment and control-panel applications requiring dependable motor protection.

Typical Applications

  • Small three-phase motor protection.
  • Industrial machinery and automation equipment.
  • Compact motor starter assemblies.
  • Pumps, fans and conveyor systems.
  • Electrical control panels.
  • OEM machinery using Lovato BG mini-contactors.

Technical Specifications

Tick the specs you need, then view products that match.

Current Range 0.3–0.5 A
Device Type Thermal Overload Relay
Compatible With BG06–BG12
Terminal Type Screw
Monitored Supply Single-phase
Reset Type Automatic
Load Voltage 690 V
Monitoring Function Temperature / thermistor
IP Rating IP20
Manufacturer Lovato Electric
Series 11RFA9
Model 11RFA905
Product type Thermal motor protection relay
Number of poles 3
Operational current 0.3–0.5 A
Rated operational voltage 690 V
Rated insulation voltage Ui 690 V
Rated impulse withstand voltage Uimp 8 kV
Operational frequency 0–400 Hz
Tripping class 10A
Reset mode Automatic
Phase failure detection Yes
Protection rating IP20 frontal
Terminal type Screw and washer
Terminal screw M4
Operating temperature -20 to 55 °C
Storage temperature -55 to 70 °C
Maximum altitude 3000 m
Normal operating position Vertical plane
Permitted mounting position ±30°
Mounting type Direct mounting on BG06, BG09 and BG12 mini-contactors
Weight 116 g

Frequently Asked Questions

What is the Lovato 11RFA905 used for?

The Lovato 11RFA905 is a thermal motor protection relay designed to protect three-phase motors against overload and phase failure conditions.

What current range does the Lovato 11RFA905 support?

The relay has an adjustable operational current range of 0.3–0.5 A.

Does the Lovato 11RFA905 reset automatically?

Yes. The 11RFA905 features an automatic reset mode.

Which contactors can the Lovato 11RFA905 be mounted on?

The relay is designed for direct mounting on Lovato BG06, BG09 and BG12 mini-contactors.

Does the Lovato 11RFA905 provide phase failure protection?

Yes. The 11RFA905 features phase failure detection and is designed to provide additional protection for three-phase motors.

Trusted Motor Protection from Lovato Electric

Lovato Electric 11RFA9 thermal motor protection relays provide compact overload and phase failure protection for compatible BG mini-contactor motor starter assemblies in industrial control applications.