Lovato PMVF51 CEI 0-21 interface protection unit for single-phase and three-phase 230 V and 400 V AC low-voltage generation systems with dual-threshold voltage and frequency protection.
£984.03
The Lovato PMVF51 is a dedicated interface protection system unit designed for low-voltage electricity generation installations operating in parallel with the public distribution network. It continuously monitors voltage and frequency conditions and controls the external interface device when electrical parameters move outside permitted operating limits.
Compliant with the Italian CEI 0-21 standard, the PMVF51 is suitable for single-phase and three-phase systems with or without a neutral conductor. It provides dual-threshold minimum and maximum voltage protection together with dual-threshold minimum and maximum frequency supervision for dependable grid connection protection.
The unit supports 230 V and 400 V AC networks, includes inputs for external 1 A or 5 A current transformers and provides two SPDT relay outputs. Its six-module DIN rail housing, removable screw terminals and optional communication expansion modules make it suitable for photovoltaic, cogeneration and other distributed generation control panels. The PMVF51 is listed by Lovato Electric as out of catalogue, so availability should be confirmed before ordering.
Electricity generation systems connected in parallel with a public distribution network must be disconnected when voltage or frequency conditions exceed authorised limits. The Lovato PMVF51 continuously supervises the connected supply and operates the external interface device when an abnormal network condition is detected.
Its configurable dual protection thresholds enable coordinated responses to different voltage and frequency events. Support for single-phase and three-phase systems makes the PMVF51 suitable for a broad range of low-voltage renewable energy and distributed generation installations.
| Manufacturer | Lovato Electric |
|---|---|
| Series | PMVF |
| Model | PMVF51 |
| Product type | Interface protection system unit |
| System type | Single-phase or three-phase, with or without neutral |
| Network voltage | 230 / 400 V AC |
| Applicable standard | CEI 0-21 |
| Operating supply range | 85–264 V AC / 93.5–300 V DC |
| Rated auxiliary supply | 100–240 V AC / 110–250 V DC |
| Rated frequency | 45–55 Hz |
| Maximum operational voltage | 400 V AC line-to-line / 230 V AC line-to-neutral |
| Voltage measurement range | 20–480 V AC line-to-line / 10–276 V AC line-to-neutral |
| Current transformer input | 1 A or 5 A secondary |
| Current measurement range | 0.01–1.2 A on 1 A scale / 0.01–6 A on 5 A scale |
| Measurement method | RMS |
| Current overload withstand | 50 A for 1 second |
| Relay outputs | 2 × SPDT changeover contacts |
| Normally open contact rating | 5 A at 250 V AC AC-1 / 5 A at 30 V DC |
| Normally closed contact rating | 2 A at 250 V AC AC-1 / 2 A at 30 V DC |
| Digital inputs | 4 isolated negative PNP inputs |
| Digital input voltage | 12 V DC |
| Terminal type | Removable screw terminals |
| Maximum terminal torque | 0.8 N·m |
| Mounting type | Modular DIN rail mounting |
| Housing width | 6 modules |
| Protection rating | IP40 front / IP20 terminals |
| Dimensions (W × H × D) | 108 × 105.4 × 63 mm |
| Weight | Approximately 470 g |
| Product status | Out of catalogue |
| Conformity | IEC/EN 60255-5, IEC/EN 61010-1, IEC/EN 61000-6-2 and IEC/EN 61000-6-3 |
| HS Code | 85364900 |
The PMVF51 monitors voltage and frequency at the connection between a local electricity generation system and the public low-voltage distribution network. It controls an external interface device when abnormal grid conditions are detected.
Yes. The PMVF51 is suitable for single-phase and three-phase systems, including installations with or without a neutral conductor.
The unit is designed for low-voltage 230 V and 400 V AC networks.
The PMVF51 supports external current transformers with either 1 A or 5 A secondary outputs.
Lovato Electric lists the PMVF51 as out of catalogue. Customers should contact LED Controls to confirm remaining availability or discuss a suitable current replacement.