PMV70A600 - 3 PHASE LINE VOLTAGE CONTROL RELAY 600V

PMV70A600 – 3 PHASE LINE VOLTAGE CONTROL RELAY 600V

Lovato PMV70A600 self-powered multifunction three-phase voltage monitoring relay for 480–600 V AC systems without neutral, providing undervoltage, overvoltage, voltage asymmetry, phase-loss and incorrect phase-sequence protection.

SKU: PMV70A600MPN: PMV70A600
Price
List Price £390.71 ex VAT
Your Price (ex VAT) Save 40%
£234.43 40% OFF
You save £156.28 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £234.43
Trade pricing is personalised to your account

Manufacturer Lead Time

£234.43

Why Choose the Lovato PMV70A600 Voltage Monitoring Relay?

The Lovato PMV70A600 is a multifunction three-phase voltage monitoring relay designed to protect industrial electrical systems against abnormal voltage and phase conditions. As part of the Lovato PMV70 monitoring relay series, it combines undervoltage, overvoltage and voltage asymmetry monitoring with phase-loss and incorrect phase-sequence detection for reliable protection of motors and automation equipment.

This self-powered relay continuously supervises a 480–600 V AC three-phase supply without neutral and de-energises its output relay whenever a monitored fault occurs. Adjustable voltage, asymmetry and timing controls allow the protection settings to be tailored to the application, helping reduce equipment damage, costly downtime and unnecessary maintenance.

With adjustable 80–95% undervoltage, 105–115% overvoltage and 5–15% voltage asymmetry thresholds, the PMV70A600 provides comprehensive monitoring from a single compact device. Automatic reset, LED status indication and 35 mm DIN rail mounting make it an excellent choice for industrial control panels, switchboards and OEM machinery.

Key Advantages

  • Monitors three-phase 480–600 V AC systems without neutral.
  • Detects undervoltage, overvoltage and voltage asymmetry.
  • Provides phase-loss and incorrect phase-sequence protection.
  • Self-powered operation removes the need for an auxiliary supply.
  • Independently adjustable voltage and asymmetry thresholds.
  • Adjustable tripping delays minimise nuisance operation.
  • Automatic reset restores operation once supply conditions return to normal.
  • Compact two-module DIN rail design simplifies installation.

Key Features

  • Lovato PMV70 multifunction voltage monitoring relay series.
  • 480–600 V AC rated monitoring range.
  • Designed for three-phase systems without neutral.
  • Minimum and maximum AC voltage monitoring.
  • Voltage asymmetry monitoring.
  • Phase-loss and incorrect phase-sequence detection.
  • 80–95% adjustable undervoltage threshold.
  • 105–115% adjustable overvoltage threshold.
  • 5–15% adjustable asymmetry threshold.
  • 0.1–20 second adjustable tripping delay.
  • 0.5 second resetting time.
  • Automatic reset with 3% resetting hysteresis.
  • One normally energised SPDT relay output rated at 8 A.
  • Green power LED and three red fault indication LEDs.
  • 35 mm DIN rail mounting with screw terminals.

Reliable Multifunction Three-Phase Protection

The Lovato PMV70A600 continuously supervises the incoming three-phase supply and responds whenever undervoltage, overvoltage, phase imbalance or phase sequence faults occur. By disconnecting control circuits before damage develops, it helps extend the service life of motors, drives and industrial equipment.

The adjustable thresholds and configurable timing functions enable the relay to distinguish between brief supply disturbances and genuine electrical faults. This improves system reliability while reducing unnecessary production interruptions.

Typical Applications

  • Three-phase motor protection systems.
  • Industrial control panels and switchboards.
  • Pumps, fans and compressors.
  • Conveyors and material handling equipment.
  • Packaging and production machinery.
  • HVAC and refrigeration installations.
  • Industrial automation systems.
  • High-voltage three-phase distribution monitoring.

Technical Specifications

Tick the specs you need, then view products that match.

Reset Type Automatic
Monitored Supply Three-phase
Time Delay Adjustable
Monitoring Function Three-phase supply
Voltage 600 V
Phase Three Phase
Manufacturer Lovato Electric
Series PMV70
Model PMV70A600
Product type Multifunction three-phase voltage monitoring relay
Monitored system Three-phase without neutral
Rated control voltage 480–600 V AC
Operating voltage range 0.7–1.2 × Ue
Rated frequency 50 / 60 Hz ±5%
Auxiliary supply Self-powered
Maximum power consumption 19 VA
Maximum power dissipation 2.5 W
Monitoring functions Minimum voltage, maximum voltage, voltage asymmetry, phase loss and incorrect phase sequence
Minimum-voltage set-point 80–95% of Ue
Maximum-voltage set-point 105–115% of Ue
Asymmetry set-point 5–15% of Ue
Tripping delay 0.1–20 seconds
Resetting time 0.5 seconds
Resetting hysteresis 3%
Instantaneous trip threshold Below 70% of Ue
Phase-loss tripping time 60 ms
Repeat accuracy Better than ±0.1%
Reset type Automatic
Relay outputs 1
Relay operating state Normally energised, de-energises on trip
Contact arrangement 1 changeover SPDT contact
Rated operational contact voltage 250 V AC
Maximum switching voltage 400 V AC
Conventional free-air thermal current 8 A
Electrical life 100,000 cycles
Mechanical life 30,000,000 cycles
Status indication 1 green LED and 3 red LEDs
Terminal type Screw terminals
Maximum terminal tightening torque 0.8 N·m
Conductor size 0.2–4 mm²
Rated insulation voltage 600 V
Rated impulse withstand voltage 6 kV
Power-frequency withstand voltage 4 kV
Operating temperature -20 to +60 °C
Storage temperature -30 to +80 °C
Protection rating IP40 front, IP20 terminals
Mounting type 35 mm DIN rail
Modular width 2 modules
Dimensions (W × H × D) 35.8 × 104.7 × 64.9 mm
Weight Approximately 130 g
HS Code 85364900

Frequently Asked Questions

What is the Lovato PMV70A600 used for?

The PMV70A600 monitors a three-phase 480–600 V AC supply for undervoltage, overvoltage, voltage asymmetry, phase loss and incorrect phase sequence.

Does the PMV70A600 require a neutral connection?

No. The relay is specifically designed for three-phase systems without neutral.

Does the PMV70A600 require an auxiliary power supply?

No. The relay is self-powered directly from the monitored three-phase electrical supply.

Can the voltage and asymmetry thresholds be adjusted?

Yes. The undervoltage threshold is adjustable from 80% to 95% of Ue, the overvoltage threshold from 105% to 115% of Ue and the voltage asymmetry threshold from 5% to 15% of Ue.

Does the PMV70A600 detect incorrect phase sequence?

Yes. The relay detects both phase loss and incorrect phase sequence, helping prevent reverse motor rotation and equipment damage.

How is the Lovato PMV70A600 installed?

The relay mounts onto a standard 35 mm DIN rail inside electrical control panels, switchboards and industrial machinery.

Trusted Industrial Voltage Monitoring

Lovato multifunction monitoring relays are widely used by panel builders, machine manufacturers and industrial engineers to provide dependable voltage and phase protection in demanding electrical installations.