PMV70A575 - 3 PHASE LINE VOLTAGE CONTROL RELAY PMV70

PMV70A575 – 3 PHASE LINE VOLTAGE CONTROL RELAY PMV70

Lovato PMV70A575 self-powered multifunction three-phase voltage monitoring relay for 380–575 V AC systems without neutral, providing undervoltage, overvoltage, asymmetry, phase-loss and incorrect phase-sequence protection.

SKU: PMV70A575MPN: PMV70A575
Price
List Price £216.71 ex VAT
Your Price (ex VAT) Save 40%
£130.02 40% OFF
You save £86.68 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £130.02
Trade pricing is personalised to your account

Manufacturer Lead Time

£130.02

Why Choose the Lovato PMV70A575 Voltage Monitoring Relay?

The Lovato PMV70A575 is a multifunction three-phase voltage monitoring relay designed to protect industrial electrical systems against abnormal voltage and phase conditions. As part of the Lovato PMV70 monitoring relay series, it combines undervoltage, overvoltage and voltage-asymmetry monitoring with phase-loss and incorrect phase-sequence detection.

This self-powered relay continuously supervises a 380–575 V AC three-phase supply without neutral and de-energises its output contact when a monitored fault occurs. Adjustable voltage, asymmetry and timing controls allow the protection settings to be matched to motors, machinery and automation systems, helping reduce equipment damage and unplanned downtime.

With adjustable 80–95% undervoltage, 105–115% overvoltage and 5–15% asymmetry thresholds, the PMV70A575 provides several essential monitoring functions within one compact device. Its automatic reset, clear LED indication and 35 mm DIN rail mounting make it well suited to industrial control panels, switchboards and machine-building applications.

Key Advantages

  • Monitors three-phase 380–575 V AC systems without neutral.
  • Detects undervoltage, overvoltage and voltage asymmetry.
  • Provides phase-loss and incorrect phase-sequence protection.
  • Self-powered operation eliminates the need for a separate auxiliary supply.
  • Independently adjustable voltage and asymmetry thresholds.
  • Adjustable tripping and resetting delays help reduce nuisance operation.
  • Automatic resetting restores operation after normal conditions return.
  • Compact two-module design combines multiple monitoring functions.

Key Features

  • Lovato PMV70 multifunction voltage monitoring relay series.
  • 380–575 V AC rated monitoring range.
  • Designed for three-phase systems without neutral.
  • Minimum and maximum AC voltage monitoring.
  • Adjustable voltage-asymmetry monitoring.
  • Phase-loss and incorrect phase-sequence detection.
  • 80–95% adjustable undervoltage threshold.
  • 105–115% adjustable overvoltage threshold.
  • 5–15% adjustable asymmetry threshold.
  • 0.1–20 second adjustable tripping delay.
  • 0.1–20 second adjustable resetting time.
  • Automatic reset with resetting hysteresis.
  • One normally energised SPDT changeover relay output.
  • One green LED and three red LEDs for power and fault indication.
  • 35 mm DIN rail mounting with screw terminals.

Reliable Multifunction Three-Phase Protection

Undervoltage can cause motors to lose torque and draw excessive current, while overvoltage can place damaging stress on insulation and electronic components. Voltage asymmetry can also produce uneven motor currents, excessive heating and reduced operating efficiency. The Lovato PMV70A575 monitors all three conditions from a single compact relay.

The PMV70A575 also detects phase loss and incorrect phase sequence, helping prevent motor damage, stalled operation and reverse rotation. Adjustable thresholds and time delays allow the relay to distinguish between temporary supply fluctuations and persistent faults, providing dependable protection while reducing unnecessary shutdowns.

Typical Applications

  • Three-phase motor protection circuits.
  • Industrial control panels and switchboards.
  • Pumps, fans and compressors.
  • Conveyors and material handling systems.
  • Production and packaging machinery.
  • HVAC and refrigeration installations.
  • Industrial automation equipment.
  • Electrical distribution monitoring systems.

Technical Specifications

Tick the specs you need, then view products that match.

Reset Type Automatic
Monitoring Function Three-phase supply
Monitored Supply Three-phase
Time Delay Adjustable
Phase Three Phase
Manufacturer Lovato Electric
Series PMV70
Model PMV70A575
Product type Multifunction three-phase voltage monitoring relay
Monitored system Three-phase without neutral
Rated control voltage 380–575 V AC
Operating voltage range 0.7–1.2 × Ue
Rated frequency 50 / 60 Hz ±5%
Auxiliary supply Self-powered
Maximum power consumption 30 VA
Maximum power dissipation 2.5 W
Monitoring functions Minimum voltage, maximum voltage, voltage asymmetry, phase loss and incorrect phase sequence
Minimum-voltage set-point 80–95% of Ue
Maximum-voltage set-point 105–115% of Ue
Asymmetry set-point 5–15% of Ue
Tripping delay 0.1–20 seconds
Resetting time 0.1–20 seconds
Reset type Automatic
Programming method Front-mounted potentiometers
Number of relay outputs 1
Relay operating state Normally energised, de-energises on trip
Contact arrangement 1 changeover SPDT contact
Rated operational contact voltage 250 V AC
Maximum switching voltage 400 V AC
Conventional free-air thermal current 8 A
Electrical life 100,000 cycles at rated load
Mechanical life 30,000,000 cycles
Status indication 1 green LED and 3 red LEDs
Terminal type Screw terminals
Maximum terminal tightening torque 0.8 N·m
Conductor size 0.2–4 mm²
Rated insulation voltage 600 V
Rated impulse withstand voltage 6 kV
Operating temperature -20 to +60 °C
Storage temperature -30 to +80 °C
Protection rating IP40 front, IP20 terminals
Mounting type 35 mm DIN rail
Modular width 2 modules
Dimensions (W × H × D) approximately 35.8 × 104.7 × 64.9 mm
Conformity IEC/EN 60255-5, IEC/EN 61000-6-2, IEC/EN 61000-6-3, UL 508, CSA C22.2 No. 14 and IEC/EN 60335-2-89
HS Code 85364900

Frequently Asked Questions

What is the Lovato PMV70A575 used for?

The PMV70A575 monitors a three-phase 380–575 V AC supply for undervoltage, overvoltage, voltage asymmetry, phase loss and incorrect phase sequence.

Does the PMV70A575 require a neutral connection?

No. The relay is designed specifically for three-phase systems without neutral.

Does the PMV70A575 require a separate auxiliary supply?

No. The relay is self-powered directly from the monitored three-phase electrical supply.

Can the voltage and asymmetry limits be adjusted?

Yes. The undervoltage threshold is adjustable from 80% to 95% of Ue, the overvoltage threshold from 105% to 115% of Ue and the asymmetry threshold from 5% to 15% of Ue.

Does the PMV70A575 detect incorrect phase sequence?

Yes. The relay detects both phase loss and incorrect phase sequence, helping prevent motor overheating, reduced torque and reverse rotation.

How is the Lovato PMV70A575 installed?

The relay mounts onto a standard 35 mm DIN rail inside an electrical control panel, machinery cabinet or switchboard.

Trusted Industrial Voltage Monitoring

Lovato multifunction monitoring relays are widely used by panel builders, machine manufacturers and electrical engineers to provide dependable voltage and phase protection in industrial electrical systems.