Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Lovato PMV50A575 self-powered three-phase voltage monitoring relay for 380–575 V AC systems without neutral, providing minimum-voltage, maximum-voltage, phase-loss and incorrect phase-sequence protection.
£71.20
The Lovato PMV50A575 is a compact and dependable three-phase voltage monitoring relay designed to protect industrial electrical systems against undervoltage, overvoltage, phase loss and incorrect phase sequence. As part of the Lovato PMV50 monitoring relay series, it provides comprehensive voltage supervision for three-phase systems operating without a neutral conductor.
This self-powered relay continuously monitors a 380–575 V AC three-phase supply and de-energises its output contact when a voltage or phase fault is detected. Independently adjustable minimum and maximum voltage thresholds allow the protection settings to be matched to motors, machinery and control systems, helping prevent operation outside safe supply limits.
With adjustable 80–95% undervoltage and 105–115% overvoltage thresholds, configurable tripping delay and automatic reset, the PMV50A575 helps reduce the risk of motor overheating, insulation stress, incorrect rotation and unexpected downtime. Its two-module enclosure and 35 mm DIN rail mounting enable straightforward installation inside industrial control panels and switchboards.
Undervoltage can cause motors to draw excessive current, lose torque and overheat, while overvoltage can place damaging stress on insulation and connected electrical components. The Lovato PMV50A575 continuously supervises the three-phase supply and changes the state of its output relay when the measured voltage moves outside the configured limits.
The relay also detects phase loss and incorrect phase sequence, helping prevent motor damage, reduced performance and reverse rotation. Its adjustable voltage thresholds and tripping delay allow the protection characteristics to be tailored to the connected equipment while reducing unnecessary trips caused by short supply fluctuations.
Tick the specs you need, then view products that match.
| Reset Type | Automatic | |
|---|---|---|
| Monitoring Function | Three-phase supply | |
| Monitored Supply | Three-phase | |
| Time Delay | Adjustable | |
| Phase | Three Phase | |
| Manufacturer | Lovato Electric | |
| Series | PMV50 | |
| Model | PMV50A575 | |
| Product type | Three-phase voltage monitoring relay | |
| Monitored system | Three-phase without neutral | |
| Rated control voltage | 380–575 V AC | |
| Operating voltage range | 0.7–1.2 × Ue | |
| Rated frequency | 50 / 60 Hz | |
| Auxiliary supply | Self-powered | |
| Maximum power consumption | 30 VA | |
| Monitoring functions | Minimum voltage, maximum voltage, phase loss and incorrect phase sequence | |
| Minimum-voltage set-point | 80–95% of Ue | |
| Maximum-voltage set-point | 105–115% of Ue | |
| Tripping delay | 0.1–20 seconds | |
| Reset type | Automatic | |
| Programming method | Potentiometers | |
| Number of relay outputs | 1 | |
| Relay operating state | Normally energised, de-energises on trip | |
| Contact arrangement | 1 changeover SPDT | |
| Rated operational contact voltage | 250 V AC | |
| Maximum switching voltage | 400 V AC | |
| Conventional free-air thermal current | 8 A | |
| Electrical life | 100,000 cycles | |
| Mechanical life | 30,000,000 cycles | |
| Status indication | 1 green LED and 2 red LEDs | |
| Terminal type | Screw terminals | |
| Conductor size | 0.2–4 mm² | |
| Operating temperature | -20 to +60 °C | |
| Mounting type | 35 mm DIN rail | |
| Modular width | 2 modules | |
| Dimensions (W × H × D) | 35.8 × 104.7 × 64.9 mm | |
| Conformity | IEC/EN 60255-5, IEC/EN 61000-6-2, IEC/EN 61000-6-3, UL 508, CSA C22.2 No. 14 and IEC/EN 60335-2-89 | |
| HS Code | 85364900 |
The PMV50A575 monitors a three-phase 380–575 V AC supply for undervoltage, overvoltage, phase loss and incorrect phase sequence, helping protect motors and industrial equipment.
No. The relay is self-powered directly from the monitored three-phase circuit.
Yes. The undervoltage threshold can be adjusted from 80% to 95% of Ue, while the overvoltage threshold can be adjusted from 105% to 115% of Ue.
Yes. The relay detects both phase loss and incorrect phase sequence, helping prevent motor damage and reverse rotation.
The relay mounts onto a standard 35 mm DIN rail and occupies two modular units inside an electrical control panel or switchboard.
Lovato monitoring relays are widely used by panel builders, machine manufacturers and maintenance engineers to provide dependable voltage and phase protection in industrial electrical systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.