Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 70.42.8.400.2032 is a DIN rail-mounted three-phase voltage monitoring relay for 380–415 V AC supplies, featuring phase failure, phase sequence, phase asymmetry, undervoltage and overvoltage monitoring, two 8 A changeover contacts and an adjustable 0.5–60 second actuation delay.
£93.28
The Finder 70.42.8.400.2032 is an electronic three-phase voltage monitoring relay designed to supervise the condition of industrial three-phase electrical supplies. Part of the Finder Series 70 monitoring relay range, this device detects potentially damaging supply abnormalities, including phase failure, incorrect phase sequence, phase asymmetry, undervoltage and overvoltage.
Designed for three-phase 380–415 V AC, 50/60 Hz electrical systems, the Finder 70.42.8.400.2032 monitors the connected supply and provides two changeover (DPDT) output contacts rated at 8 A at 250 V AC. Its adjustable 0.5–60 s contact actuation delay supports integration into control systems requiring a defined response to supply abnormalities.
With a compact 35 mm DIN rail mounting arrangement, screw terminals, an IP20 protection rating and an operating temperature range of −20 to +60 °C, this monitoring relay is suitable for industrial control panels, motor control centres, electrical distribution equipment and automated machinery installations.
The Finder 70.42.8.400.2032 helps improve the reliability of industrial electrical installations by continuously supervising the three-phase supply. Abnormal voltage conditions can affect motors, contactors, control equipment and connected machinery, potentially causing unexpected shutdowns, overheating or equipment damage.
Phase failure monitoring detects the loss of a phase in the electrical supply. This is particularly important for three-phase motors, where operation under phase-loss conditions can cause excessive current in the remaining phases and potentially damage the motor.
Phase sequence monitoring identifies an incorrect phase rotation order. In motor-driven applications, incorrect phase sequence can result in unintended reverse rotation, which may be hazardous for pumps, compressors, conveyors and other rotating machinery.
Undervoltage and overvoltage monitoring help identify supply conditions outside acceptable operating limits, while phase asymmetry monitoring detects voltage imbalance between phases. These functions provide useful supervisory information for industrial electrical protection and automation systems.
The relay's two changeover output contacts can be connected to compatible contactor control circuits, alarm indicators or programmable logic controllers. Its adjustable 0.5–60 s actuation delay allows the monitoring response to be configured for the requirements of the installation.
As a monitoring relay, the Finder 70.42.8.400.2032 does not itself provide short-circuit or overload protection. It should be incorporated into a properly designed electrical protection system using appropriately rated contactors, circuit breakers, fuses and other protective devices.
Tick the specs you need, then view products that match.
| Mounting Type | DIN rail | |
|---|---|---|
| Monitoring Function | Three-phase supply | |
| Monitored Supply | Three-phase | |
| Manufacturer | Finder | |
| Series | 70 | |
| Type | 70.42 | |
| Manufacturer part number | 70.42.8.400.2032 | |
| Product category | Voltage Monitoring Relays | |
| Product type | Three-phase voltage monitoring relay | |
| Monitored electrical system | Three-phase AC | |
| Rated supply voltage | 3 × 380–415 V AC | |
| Rated frequency | 50/60 Hz | |
| Supply arrangement | Powered from monitored electrical system | |
| Monitored conditions | Overvoltage, undervoltage, phase failure, phase sequence and phase asymmetry | |
| Output contact configuration | 2 CO (DPDT) | |
| Number of changeover contacts | 2 | |
| Rated output contact current | 8 A | |
| Rated output contact voltage | 250 V AC | |
| Rated AC-1 switching capacity | 2,000 VA | |
| Rated AC-15 switching capacity at 230 V AC | 400 VA | |
| Motor load rating at 230 V AC | 0.3 kW | |
| Adjustable contact actuation delay | 0.5–60 s | |
| Operating temperature | −20 to +60 °C | |
| Degree of protection | IP20 | |
| Mounting method | 35 mm DIN rail | |
| Electrical connection | Screw terminals | |
| Terminal tightening torque | 0.8 Nm | |
| Width | 35 mm | |
| Height | 88.8 mm | |
| Depth | 60.8 mm | |
| EAN / GTIN-13 | 8012823398945 |
The Finder 70.42.8.400.2032 is a three-phase voltage monitoring relay used to detect overvoltage, undervoltage, phase failure, incorrect phase sequence and phase asymmetry in industrial electrical systems.
This relay is designed for three-phase 380–415 V AC electrical systems operating at 50/60 Hz.
The Finder 70.42.8.400.2032 provides two changeover output contacts (2 CO / DPDT), each with an 8 A rating at 250 V AC.
Yes. The relay monitors phase sequence and can detect an incorrect phase rotation order, making it useful for electrical systems containing three-phase motors and rotating machinery.
Yes. Phase failure detection is one of the relay's monitoring functions, allowing the control system to respond when a phase is lost from the monitored supply.
The Finder 70.42.8.400.2032 has an adjustable contact actuation delay of 0.5–60 s, allowing its response timing to be configured for the application.
The relay is designed for 35 mm DIN rail mounting inside a suitable electrical control enclosure and uses screw-type terminals for electrical connections.
No. The Finder 70.42.8.400.2032 monitors supply conditions and provides relay outputs for control or signalling. It does not replace appropriately rated short-circuit protection, overload protection or electrical isolation equipment.
The Finder 70.42.8.400.2032 provides comprehensive three-phase voltage supervision in a compact DIN rail-mounted monitoring relay. With phase failure, phase sequence, phase asymmetry, undervoltage and overvoltage detection, together with two 8 A changeover contacts and an adjustable response delay, it offers a practical solution for electrical engineers, industrial panel builders, automation specialists and maintenance professionals.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.