Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB RD2-48 Type A electronic residual current relay with 48–150 V AC/DC supply, selectable 0.03–2 A sensitivity and adjustable instantaneous-to-5-second intervention time for earth leakage monitoring.
£259.42
The ABB RD2-48 is a compact Type A electronic residual current relay designed for earth leakage monitoring and protection in low-voltage electrical installations. As part of the ABB RD2 residual current relay series, it operates with an external ABB TR-series toroidal transformer to detect leakage currents and provide a switching output for associated protection equipment.
The RD2-48 provides selectable residual current sensitivity and intervention time through front-accessible minidip settings, allowing the protection characteristics to be adapted to different circuits. Sensitivity settings range from 0.03–2 A, while selectable tripping times include instantaneous operation and delays up to 5 seconds, supporting coordinated residual current protection.
Designed for 48–150 V AC/DC auxiliary supplies, the RD2-48 is particularly suitable for industrial control systems and electrical panels using low-voltage control power. Its compact 2-module DIN-rail format, Type A residual current detection and compatibility with ABB TR toroidal transformers make it a practical solution for earth leakage monitoring in industrial and commercial installations.
Residual current relays operate with an external toroidal transformer installed around the active conductors of the monitored circuit. The toroid detects an imbalance caused by leakage to earth and supplies the corresponding signal to the relay, allowing the RD2-48 to operate its output contact when the selected residual current threshold and intervention conditions are reached.
The ABB RD2-48 is designed specifically for use with ABB TR-family external toroidal transformers. Its selectable sensitivity and time-delay settings allow the monitoring system to be adapted to different applications while the compact DIN-rail format enables straightforward installation in distribution boards and industrial control panels.
Tick the specs you need, then view products that match.
| Monitored Supply | AC/DC | |
|---|---|---|
| Monitoring Function | Earth leakage / residual current | |
| Series | RD2 | |
| ABB order code | 2CSM242120R1201 | |
| Product group | Earth Monitoring Devices | |
| Product type | Electronic residual current relay | |
| Residual current type | Type A | |
| Operating voltage | 48–150 V AC/DC | |
| Frequency | 50 / 60 Hz | |
| Sensitivity settings | 0.03 / 0.1 / 0.3 / 0.5 / 1 / 2 A | |
| Tripping-time settings | Instantaneous / 0.3 / 0.5 / 1 / 2 / 5 s | |
| Output contact type | NC-C-NO changeover | |
| Output contact capacity | 10 A at 250 V AC, resistive load | |
| Operating temperature | -5 to +40 °C | |
| Protection rating | IP20 | |
| Mounting type | DIN rail | |
| Width | 2 modules / 35 mm | |
| Dimensions (H × W × D) | 85 × 35 × 65 mm | |
| Product net weight | 0.105 kg | |
| Standard | IEC/EN 62020 | |
| EAN | 8012542537809 |
The ABB RD2-48 is used for residual current and earth leakage monitoring in low-voltage electrical systems, operating with an external toroidal transformer to detect leakage currents and control associated protection equipment.
The RD2-48 operates from a 48–150 V AC/DC supply, making it suitable for industrial installations using low-voltage auxiliary control power.
The relay provides selectable sensitivity settings of 0.03, 0.1, 0.3, 0.5, 1 and 2 A, allowing its response threshold to be configured for different applications.
Yes. The RD2-48 provides instantaneous, 0.3, 0.5, 1, 2 and 5 second intervention-time settings, enabling coordination with other protection devices.
The RD2-48 is designed for use with compatible ABB TR-family external toroidal transformers, which detect residual current in the monitored conductors and provide the sensing signal to the relay.
ABB RD2 residual current relays provide configurable earth leakage monitoring for low-voltage electrical systems, combining external TR-series toroidal sensing with adjustable sensitivity and intervention-time settings in a compact DIN-rail format.
We use cookies