Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB RD3M-48 is a DIN-rail Type A residual current relay with 12–48 V AC/DC operation, frequency filtering and a 60% pre-alarm threshold for industrial earth leakage monitoring and protection.
£347.05
The ABB RD3M-48 is a DIN-rail mounted electronic Type A residual current relay designed to provide residual current protection and earth leakage monitoring in industrial low-voltage installations. As part of ABB’s Earth Monitoring Devices range, it operates with an external ABB TR-series toroidal transformer and can be combined with suitable circuit-breaking equipment to create a complete residual current protection system.
The RD3M-48 provides adjustable sensitivity and operating time together with a 60% pre-alarm threshold and frequency filtering. The frequency filter helps the relay operate reliably in installations containing electronic equipment and other loads capable of producing higher-frequency leakage components, while the pre-alarm function enables developing leakage conditions to be identified before the main trip threshold is reached.
Designed for a 12–48 V AC/DC operating voltage, the RD3M-48 is particularly suitable for industrial control systems using low-voltage auxiliary supplies. Its compact three-module DIN-rail format allows straightforward installation within distribution boards and control panels alongside ABB S200 miniature circuit breakers and compatible Tmax moulded-case circuit breakers.
The ABB RD3M-48 operates with an external toroidal transformer through which the active conductors of the protected circuit are routed. Under normal conditions, the currents through the toroid balance each other. An earth fault or insulation leakage creates a residual current imbalance that is detected by the transformer and transmitted to the RD3M-48 for evaluation.
Adjustable sensitivity and operating delay allow the relay to be configured for the requirements of the installation, while the 60% pre-alarm threshold provides advance warning before the main residual current operating level is reached. When used with an appropriate tripping device, the RD3M-48 can be combined with ABB S200 miniature circuit breakers and Tmax moulded-case circuit breakers up to T5 to provide coordinated residual current protection in industrial installations.
Tick the specs you need, then view products that match.
| Time Delay | Adjustable | |
|---|---|---|
| Monitored Supply | AC/DC | |
| Monitoring Function | Earth leakage / residual current | |
| Product group | Earth Monitoring Devices | |
| Series | RD3 Residual Current Relays | |
| ABB order code | 2CSJ202001R0001 | |
| Product type | Electronic residual current relay / residual current monitor | |
| Residual current type | Type A | |
| Application | Residual current protection and earth leakage monitoring | |
| Function | For mixed systems | |
| Rated voltage | 48 V | |
| Rated operational voltage | 12–48 V AC/DC | |
| Rated control supply voltage | 48 V AC/DC | |
| Frequency | 50–60 Hz | |
| Pre-alarm threshold | 60% | |
| Delay time | 0–10 s adjustable | |
| Filter option | Frequency filter | |
| Number of contacts | 2 | |
| Changeover contacts | 1 | |
| Power loss | 0.6 W | |
| Sensor type | External toroidal transformer | |
| Mounting type | DIN rail | |
| Module width | 3 modules | |
| Dimensions (H × W × D) | 85 × 52.8 × 65 mm | |
| Protection rating | IP20 | |
| Maximum terminal conductor section | 2.5 mm² | |
| Standard | IEC/EN 60947-2 Annex M | |
| Net weight | 223 g | |
| RoHS status | Compliant with EU Directive 2011/65/EU | |
| EAN | 8012542733935 |
The ABB RD3M-48 is an electronic Type A residual current relay used with an external toroidal transformer to provide earth leakage monitoring and residual current protection in industrial low-voltage installations.
The RD3M-48 has a 12–48 V AC/DC rated operational voltage and a rated control supply voltage of 48 V AC/DC.
Yes. The RD3M-48 provides a 60% pre-alarm threshold, allowing developing residual current conditions to be indicated before the main operating threshold is reached.
Yes. The RD3M-48 is designed to operate with a compatible external ABB TR-series toroidal transformer, which detects residual current imbalance in the protected circuit conductors.
The RD3M-48 is designed for DIN-rail mounting and occupies three modules, making it suitable for integration into industrial switchboards, distribution boards and control panels.
ABB RD3 residual current relays provide configurable earth leakage monitoring and protection for industrial installations, with the RD3M-48 combining Type A detection, low-voltage AC/DC operation, frequency filtering and a 60% pre-alarm threshold in a compact DIN-rail format.