Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB ELR48V24P is a compact 48 mm Type A residual current monitor with a 24–48 V AC/DC supply, adjustable 0.03–30 A sensitivity and adjustable trip delay for low-voltage earth leakage monitoring.
£344.71
The ABB ELR48V24P is a compact electronic Type A residual current monitor and relay designed for monitoring and protection of low-voltage electrical distribution networks. As part of ABB’s Earth Monitoring Devices range, it operates with an external toroidal transformer to detect residual current and control associated circuit protection equipment when the configured threshold is exceeded.
Designed for 48 × 48 mm front-panel mounting, the ELR48V24P combines adjustable residual current sensitivity and trip delay with selectable Fail Safe and automatic reset functions. Front-mounted TEST and RESET controls, together with ON and FAULT LED indication, provide straightforward commissioning and operational status monitoring.
The ELR48V24P operates from a 24–48 V AC/DC auxiliary supply and provides adjustable residual current sensitivity from 0.03–30 A with a configurable delay from 0–5 s. Its compact construction makes it particularly suitable for industrial control panels, machinery and switchboards where panel space is limited but configurable earth leakage monitoring is required.
The ABB ELR48V24P operates with an external toroidal transformer through which the active conductors of the protected circuit are routed. Under normal operating conditions, the vector sum of the currents through the toroid is effectively zero. An insulation fault or leakage to earth creates a residual current imbalance, which is detected by the toroidal transformer and transmitted to the ELR48V24P.
The monitor compares this residual current with the selected sensitivity setting and operates its output contact when the configured threshold and time delay conditions are reached. With sensitivity adjustable between 0.03 and 30 A, delay adjustable up to 5 s and selectable Fail Safe and automatic reset functions, the ELR48V24P provides flexible residual current monitoring for commercial and industrial low-voltage systems.
Tick the specs you need, then view products that match.
| Time Delay | Adjustable | |
|---|---|---|
| Monitored Supply | AC/DC | |
| Monitoring Function | Earth leakage / residual current | |
| Product group | Earth Monitoring Devices | |
| Series | ELR Residual Current Relays | |
| ABB order code | 2CSG452211R1202 | |
| Product type | Residual current monitor / electronic residual current relay | |
| Residual current type | Type A | |
| Application | Low-voltage residual current and earth leakage monitoring | |
| Function | For mixed systems | |
| Rated voltage | 24–48 V | |
| Auxiliary supply voltage | 24–48 V AC/DC | |
| Auxiliary supply tolerance | ±20% | |
| Frequency | 50–60 Hz | |
| Residual current sensitivity | 0.03–30 A adjustable | |
| Trip delay | 0–5 s adjustable | |
| Output contact capacity | 5 A at 250 V | |
| Maximum consumption | 3 VA | |
| Fail Safe function | Selectable | |
| Automatic reset | Selectable | |
| Pre-alarm threshold | No | |
| Sensor type | External ABB TR-series toroidal transformer | |
| Mounting type | Front-panel mounting | |
| Front dimensions (H × W) | 48 × 48 mm | |
| Panel cut-out | 45 × 45 mm | |
| Protection rating | IP52 front with cover; IP40 front; IP20 terminals | |
| Operating temperature | -10 to +60 °C | |
| Storage temperature | -20 to +70 °C | |
| Maximum relative humidity | ≤95% | |
| Terminal conductor capacity | 2.5 mm² | |
| Standard | IEC/EN 60947-2 Annex M | |
| Weight | approx. 120 g | |
| EAN | 8012542734826 |
The ABB ELR48V24P is a compact Type A residual current monitor and relay used with an external toroidal transformer to monitor earth leakage and provide residual current protection for low-voltage electrical distribution systems.
The ELR48V24P provides adjustable residual current sensitivity from 0.03–30 A, allowing the operating threshold to be configured for different applications.
The ELR48V24P operates from a 24–48 V AC/DC auxiliary supply with a ±20% supply tolerance.
Yes. The ELR48V24P is designed for use with a compatible ABB TR-series external toroidal transformer, which detects residual current imbalance in the protected conductors.
The ELR48V24P has a compact 48 × 48 mm front-panel format and requires an approximately 45 × 45 mm panel cut-out.